ComTroll 230, Remote Terminal Unit 

The ComTroll 230 is designed for a complete and modular functionality for monitoring and 

control of primary and secondary functions in the distribution network. 

The rack-mounted system can control and monitor a wide range of objects such as pole-

mounted sectionalizers, breakers, earthing switches, relay protection, fault indicators, tap-

changers and more through its serial, digital and analog interface. 

The analog inputs can be connected to different sensors reading values for power frequency, 

active/reactive power, bus-bar voltage, load current and more. 

 

Based on the RTU-30 Controller unit, ComTroll 230 offers both local- and remote control of 

the connected equipment. 

ComTroll 230 can be connected to a wide range of transceivers for different communication 

solutions: 

 

 

Radio 

 

Fibre optics 

 

Power Line 

 

Leased Lines 

 

Ethernet 

 

 

SLC-200+

CRU-200

RTU-30

RTU-30i

RTU-30i

 

 

 

With the extensible backplane solution, ComTroll 230 can be supplied in a 10.5” single frame 

rack where up to three RTU-30/RTU-30i cards can be fitted. It can also be supplied in a full 

19” single frame rack with space for up to eight RTU-30/RTU-30i cards. 

RTU-30 is acting as a master for the additional RTU-30i cards. One RTU-30 can communicate 

with 14 RTU-30i cards on the I

2

C-bus. 

Summary of Contents for ComTroll 230

Page 1: ...Page 1 ComTroll 230 ComTroll 230T ComTroll 230S User Manual...

Page 2: ...ERVICE NORTROLL AS RTU 30i LOCAL REMOTE OFF REMOTE CLOSE OPEN SERVICE RESET TX RX CLOSED OPEN SERVICE NORTROLL AS RTU 30i LOCAL OFF CLOSE OPEN SERVICE RESET TX RX CLOSED OPEN SERVICE NORTROLL AS RTU 3...

Page 3: ...230 REMOTE TERMINAL UNIT 4 COMMUNICATION 5 POWER SUPPLY 6 CONNECTIONS 6 Main backplane 06310a 6 Link Settings 7 J3 pin overview 7 J7 Bridge overview 8 COMTROLL 230T 8 Installing the TSU 25 8 COMTROLL...

Page 4: ...reactive power bus bar voltage load current and more Based on the RTU 30 Controller unit ComTroll 230 offers both local and remote control of the connected equipment ComTroll 230 can be connected to...

Page 5: ...al Unit can communicate with the central unit SCADA on different communication media The most commonly used is low power radio and fiber optics but the flexible communication platform can utilize almo...

Page 6: ...30 card Each additional RTU 30i card in a rack needs a separate backplane The RTU cards are tied together on the Local Bus Bridge Cable where also supply voltage is transferred to the next unit NORTRO...

Page 7: ...al Input 1 on the NTM 20 25 Modem Only used in repeaters Default set open F2 Connects either External DC input or the Battery Input to the Analog Input 4 on the first RTU 30 card Battery voltage is mo...

Page 8: ...substation can be precisely time tagged by the use of GPS Time Synchronization Unit TSU 25 The TSU25 utilizes the accurate time signal broadcasts from the GPS satellite network The TSU 25 has an integ...

Page 9: ...ondition The TSU will activate the GPS every 660s 11min or 2500s 42min dependent upon the measured temperature When the interval expires the GPS will be activated and the Sync LED will start flashing...

Page 10: ...ote worst case 7 sec every 24 hour period ComTroll 230S ComTroll 230S is a gateway that resides on the ComTroll Network and connects to Modbus devices over EIA 232 or EIA 485 The controller module RTU...

Page 11: ...03 0200 01 CRU 200 SPM Radio and modem without router module Product nr 03 0200 02 CRU 200 DC Radio and modem with router module Product nr 03 0030 50 RTU 30 Additional Modbus Object AMO Product nr 03...