background image

 

Page 8 

 

 

J7 Bridge overview 

 

12 Vdc

GND

I2C

TP-Net

 

 

The backplane for additional RTU-30 cards have the same connectors and pin-out as the main 
backplane. 

 
ComTroll 230T 

 

 

Installing the TSU-25

 

Before powering the TSU-25, connect the antenna to the connector located on the front 
panel. 

The GPS antenna needs to be located with a good clear 360 degree view of the sky. 

The ideal location for the antenna is a roof-top. However, in practice the TSU-25 antenna 

All events in a substation can be precisely time tagged by the use of 

GPS Time Synchronization Unit, TSU-25. 

The TSU25 utilizes the accurate time signal broadcasts from the GPS 

satellite network. 

  

The TSU-25 has an integrated GPS receiver that constantly tracks up to 

8 satellites simultaneously to provide a highly accurate time reference.  

A software clock on the RTU-30t card will be calibrated every minute to 

time-stamp events that occur in the digital and analog inputs. The time 

information will be sent together with the alarm/message to the 

SCADA. 

  

Up to 7 RTU-30t cards can be calibrated from one TSU-25. 

The RTU-30t has the same functions and I/O package as RTU-30 and 

RTU-30i. 

  

 

Summary of Contents for ComTroll 230

Page 1: ...Page 1 ComTroll 230 ComTroll 230T ComTroll 230S User Manual...

Page 2: ...ERVICE NORTROLL AS RTU 30i LOCAL REMOTE OFF REMOTE CLOSE OPEN SERVICE RESET TX RX CLOSED OPEN SERVICE NORTROLL AS RTU 30i LOCAL OFF CLOSE OPEN SERVICE RESET TX RX CLOSED OPEN SERVICE NORTROLL AS RTU 3...

Page 3: ...230 REMOTE TERMINAL UNIT 4 COMMUNICATION 5 POWER SUPPLY 6 CONNECTIONS 6 Main backplane 06310a 6 Link Settings 7 J3 pin overview 7 J7 Bridge overview 8 COMTROLL 230T 8 Installing the TSU 25 8 COMTROLL...

Page 4: ...reactive power bus bar voltage load current and more Based on the RTU 30 Controller unit ComTroll 230 offers both local and remote control of the connected equipment ComTroll 230 can be connected to...

Page 5: ...al Unit can communicate with the central unit SCADA on different communication media The most commonly used is low power radio and fiber optics but the flexible communication platform can utilize almo...

Page 6: ...30 card Each additional RTU 30i card in a rack needs a separate backplane The RTU cards are tied together on the Local Bus Bridge Cable where also supply voltage is transferred to the next unit NORTRO...

Page 7: ...al Input 1 on the NTM 20 25 Modem Only used in repeaters Default set open F2 Connects either External DC input or the Battery Input to the Analog Input 4 on the first RTU 30 card Battery voltage is mo...

Page 8: ...substation can be precisely time tagged by the use of GPS Time Synchronization Unit TSU 25 The TSU25 utilizes the accurate time signal broadcasts from the GPS satellite network The TSU 25 has an integ...

Page 9: ...ondition The TSU will activate the GPS every 660s 11min or 2500s 42min dependent upon the measured temperature When the interval expires the GPS will be activated and the Sync LED will start flashing...

Page 10: ...ote worst case 7 sec every 24 hour period ComTroll 230S ComTroll 230S is a gateway that resides on the ComTroll Network and connects to Modbus devices over EIA 232 or EIA 485 The controller module RTU...

Page 11: ...03 0200 01 CRU 200 SPM Radio and modem without router module Product nr 03 0200 02 CRU 200 DC Radio and modem with router module Product nr 03 0030 50 RTU 30 Additional Modbus Object AMO Product nr 03...

Reviews: