Page 32
User Manual LineTroll R400D
TEST
The indicator can be tested by turning the display-unit counter-clockwise until it stops and
back to normal position within 9 seconds. The Indicator will then send test-messages to the
recipients as follows:
✓
Transient Fault
✓
Low Battery
✓
Status OK
✓
Permanent Fault
✓
Loss of Voltage
✓
Status OK
The above messages will be sent even if one or more of the messages are disabled.
If the message filters are set, the messages will be routed to the recipients according to the
filter definition.
Manual installation
The indicator must be installed on an energized line. After the unit is mounted on the pole the
unit has to be adapted to the Electromagnetic field at the installation point and to adjust the
internal gain for the sensor inputs.
1.
Turn the display unit counter-clockwise (
→
TEST) until it stops. Leave the display
unit in the test position. After the lens has been put into the TEST position, the
red, green and yellow LED’s will start flashing.
2.
Climb down more than 1 meters below the indicator while the LED’s are f
lashing
3.
After approx. 9 seconds the adaption to the line conditions will start. The LED’s
will be OFF during the adaption.
4.
After the adaption is finished the LED will show the result of the adaption as
follows:
GREEN LED
Installation OK
RED LED
E-field too low
Place the indicator closer to the line.
YELLOW LED
Absolute PtP setting too low.
Change the absolute trip level for PtP faults to a higher value
5.
Twist the lens back to normal position. It is not necessary to reset the indicator
after the installation.
Remote Installation
It is also possible to run the installation process from ground, using the FDP-15 hand-held unit
or from NetTroll or any cell-phone by sending SMS.
The TEST and RESET options are also available.
See the configuration manual for details.
Verifying the installation
If the installation /adaption to the local conditions on the installation point were successful,
the variable
Id#38_Last_installation_OK
will be set to TRUE in the indicator.
If the installation fails, the variable will be set to FALSE.
This variable can be read from NetTroll FDP at any time.
See the configuration manual for details.