Page 11
User Manual LineTroll R400D
CB-trip OFF:
The time stamp on the message will be the time when the indicator
has validated the fault. The validation time can be set between 3 sec
to 15 sec after a fault occurs.
CB-trip ON:
The time stamp on the message will be the time when the indicator
detects that the circuit-breaker has tripped after a fault.
2.5 Reset
The indicator can be reset in four different ways:
1. Voltage reset
The voltage reset can be switched OFF. When switched ON a delay from the line is energized
until the indicator is reset can be set.
The following voltage reset delay selections can be made: 5s, 10s, 15s, 20s, 25s or 30s.
2. Automatic timer-reset
The timer reset can be set to any value between 1,5h and 48h.
3. Manual reset
LineTroll R400D can be reset by turning the lens clockwise to "RESET" position.
A magnet is permanently mounted in the lens.
A special hot-stick-attachable tool is available for resetting of the indicator from the ground
when mounted on a pole.
4. Remote reset
The remote reset feature has limited value as the GSM modem is switched off unless the
indicator has something to send. The reset command will only be received during a polling
sequence, heartbeat message or alarm sending.