7. Programming and setup
It is highly recommended to do all the programming/setting before the units are taken to the
field for installation on the pole.
Normally, most indicators will have the same configuration settings in all the units installed in
one network. The exception could be the trip-level which should be verified for each
installation site.
All configuration properties can be changed remotely from a cell-phone or NetTroll FDP
configuration utility at any time, also after installation in the field. Some settings can also be
made from NetTroll.
The COMTROLL APP for Android smartphones can also be used to configure the unit.
A detailed description of the configuration properties is given in the Configuration
Manual for the RIS system.
This manual covers all possible methods of configuration.
The most important setting to notice:
✓
Trip level for Earth Faults (PtE) and trip level for Short Circuit Faults (PtP)
✓
Relative current increase (Di/Dt in %)
✓
Fault duration (in number of periods) for PtG and PtP.
✓
Inrush blocking time
✓
Voltage reset delay
✓
Timer reset
✓
CB Trip delay
Resetting configuration parameters back to factory values
All settings can be reset back to its default values. This must be done in the indicator by
pressing the manual activation button in the indicator at the same time as the unit is powered
up or the lens twisted to RESET position.
Please note that all settings will be set back to default values and the recipient’s number will
be deleted.