LineTro110Tµr User Guide  

June 2011               Page 14 of 16 

Test of the battery. 

 
Battery can be tested by placing a magnet on 
the yellow spot marked: 

RESET

 
After 2 sec the indicator will respond by 
flashing all the LED’s, see section 

10. 

Flashing sequences -Test/Reset

.  

 
During the last few months of the battery’s 
life, an amber/yellow LED with a low 
flashing frequency (1/10 Hz) will indicate 
that less than 20% of battery capacity 
remains and that there is a need for a battery 
replacement.  
 
The LT-110Tµr will in addition, transmit a 
“Low-Battery” message to the Collector. 

 
Programming. 

 
Open the indicator by unscrewing the top-
cap from the lens.

 See 

Figure 17

. 

Pull out the electronics board just as far as to 
enable operation of the switch-bank levers.

 

See 

Feil! Fant ikke referansekilden.

 

18

.

 

Set the switches as required. Push the 
electronics board back into position. 
Align the top-cap arrow with the lens label 
arrow before closing the unit. See section 
4.7 for programming instructions. 

 

Figure 17: Opening/ closing the LINETROLL 110Tµ. 

 

 

 

Summary of Contents for LineTroll 110Tmr

Page 1: ...LineTroll 110T r User Manual...

Page 2: ...sing a healthy line 7 4 2 Connecting a faulty line while the indicator is activated 7 4 3 Transient faults 8 4 4 Fused lines 8 4 5 Multiple faults 8 4 6 Capacitive discharges 9 4 7 PROGRAMMING 10 5 MA...

Page 3: ...ermanent fault and 1 regular Green LED for transient faults The LED flash can be seen within 100 200 metres distance The lens of the indicator allows for uniform 360 degrees monitoring LINETROLL 110E...

Page 4: ...ush current it s di dt sensor is blocked for 5 sec upon energising of a line While the blocking time elapses the line current can stabilise so as not to cause triggering of the di dt sensor A fault du...

Page 5: ...d giving more than 1500 hours of flashing capacity The battery is fitted with a connector for simple replacement Figure 3 Initial battery capacity Figure 4 Remaining battery capacity as a function of...

Page 6: ...ce there may be an indication in a branch due to a non permanent fault while another branch without an indicator installed may be faulty yet remain unidentified as such Near line points with sectional...

Page 7: ...blocking time a shows the sequence when a fault occurs less than 5 sec after line has been energised No Indication If upon re energising of a line the unit is already indicating due to a previous fau...

Page 8: ...tion within 5 sec followed by an automatic reclosing causing a fuse operation the indication starts but will reset after 30 sec If the automatic reset is switched off the indicator will continue flash...

Page 9: ...wnstream of the indicator is added Underground cables have larger capacitance than overhead lines This has to be taken into account when an overhead line feeds an underground cable The following simpl...

Page 10: ...et 4 7 5 Auto Reset Programming of the automatic indication reset AR If enables reset occurs when the line has been energised for more than 30 sec voltage or current Switch 7 Auto reset on return of v...

Page 11: ...y is replaced with a new battery the battery monitoring must be reset With the battery disconnected reset can be done setting Rotary switch to position see figure 11b while at the same time powering t...

Page 12: ...Flashing 1500 flashing hours Battery replacement normally every 7 10 years Indication 1 Super intensive red Flash every 3 sec 10 sec after 12 hours 1 green LED for transient fault 1 amber Yellow LED f...

Page 13: ...e indicators at strategic points along the line 9 1 Before mounting Make sure the indicator is programmed see 4 7 Programming and battery connected before mounting on the line 9 2 Live line mounting b...

Page 14: ...capacity remains and that there is a need for a battery replacement The LT 110T r will in addition transmit a Low Battery message to the Collector Programming Open the indicator by unscrewing the top...

Page 15: ...transient fault Permanent fault GREEN RED Comments The Permanent Fault indication red LEDs is delayed 70 sec to verify a permanent fault Both red and green LED s will flash on permanent faults until r...

Page 16: ...equence 1 2 3 4 Amber 5 Green RESET sequence If the line is energised the GREEN LED only flashes for 3 sec If the line is de energised line the RED LED s only flashes for 3 sec 3 s 3 s 2s Test sequenc...