background image

 

 

LineTroll 110E

/110Eµr User Guide September 2009                    Page 3 of 16

 

1.

 

LINETROLL 110Tµr 
OVERVIEW 

 
The 

LINETROLL 110T

r

 is

 

a line 

mounted fault indicator for local and remote 
indication.

  

The 

LINETROLL 110T

r

 has an 

integrated radio that can communicate with a 
pole-mounted Nortroll Collector device 
(CmT 115C or others). The Collector can be 
interfaced to a SCADA-RTU or a 
communication device by means of dry relay 
contacts or serial-port for remote indication 
of faults.. 
 
The LT 110T

r is a single phase unit, 

however they are normally used in groups of 
3 to fully cover the different fault 
configurations which can occur. Deliveries 
come as a kit of 

3 units 

to each package. 

 
The LT 110T

r Fault Passage Indicator; 

detects down-streams faults in the OH-
distribution network. Detectable faults 
include short circuit and earth fault, if the 
network provides sufficient earth fault 
current.  
 
The indicators are placed at strategic 
locations along the line, such as after 
branching points and sectionalisers. The 
indicators mount directly on the high voltage 
conductor. 
Live line mounting is easily and rapidly 
done with a shotgun type Hot-Stick. 
 
Upon fault sensing, all indicators installed in 
the faulty phase(s) between the feeding 
substation and the fault will operate. The 
indicators placed behind the fault or in the 
non-damaged phase(s) remain idle. 
Upon detecting a fault on the line, indication 
is by means of an intermittent LED- flash (1 
super intensive red LED’s for a permanent 
fault and 1 regular Green LED for transient 
faults).  
The LED-flash can be seen within 100-200 
metres distance. The lens of the indicator 
allows for uniform 360 degrees monitoring. 
 

LINETROLL 110E

r provides fast fault 

location through remote indication, enabling 
reduction in outage times. This represents 
enhanced service to the customer thereby 
improving the utility image.  
 
Another important aspect of using fault 
indicators is that unnecessary operations of 
circuit breakers and sectionalisers to locate 
faults can be avoided. In this way the 
indicators can help to reduce wear and tear, 
as the reclosing cycle can cause stress to 
switchgear. 
 

2.

 

FUNCTIONAL DESCRIPTION 

 
The LINETROLL 110T

r continuously 

monitors the line voltage and phase current, 
the two sources of information it needs to 
operate. The unit is fully self contained, no 
external transformers or connections are 
required.  
During normal line conditions; the indicator 
does not flash. 
 
The device is looking for a specific sequence 
of line conditions to occur before it starts 
indicating locally and remotely. The general 
sequence is as follows: 
 
A.  The line is energised (voltage or current 

present) for at least 5 seconds. 

B.  The line current increases 

instantaneously by a user defined set 
value (the step level), or exceeds a user 
defined threshold value (if enabled). 

C.  The line is de-energised. Voltage or 

current not present (optional auto reset 
when the line is re-energised) 

 
The user can program the criteria for 
operation to suit his local requirement by 
manipulating a bank of micro-switches 
inside the indicator. 
 

Note: Voltage or current present as start 
and stop criteria is user programmable. 

Summary of Contents for LineTroll 110Tmr

Page 1: ...LineTroll 110T r User Manual...

Page 2: ...sing a healthy line 7 4 2 Connecting a faulty line while the indicator is activated 7 4 3 Transient faults 8 4 4 Fused lines 8 4 5 Multiple faults 8 4 6 Capacitive discharges 9 4 7 PROGRAMMING 10 5 MA...

Page 3: ...ermanent fault and 1 regular Green LED for transient faults The LED flash can be seen within 100 200 metres distance The lens of the indicator allows for uniform 360 degrees monitoring LINETROLL 110E...

Page 4: ...ush current it s di dt sensor is blocked for 5 sec upon energising of a line While the blocking time elapses the line current can stabilise so as not to cause triggering of the di dt sensor A fault du...

Page 5: ...d giving more than 1500 hours of flashing capacity The battery is fitted with a connector for simple replacement Figure 3 Initial battery capacity Figure 4 Remaining battery capacity as a function of...

Page 6: ...ce there may be an indication in a branch due to a non permanent fault while another branch without an indicator installed may be faulty yet remain unidentified as such Near line points with sectional...

Page 7: ...blocking time a shows the sequence when a fault occurs less than 5 sec after line has been energised No Indication If upon re energising of a line the unit is already indicating due to a previous fau...

Page 8: ...tion within 5 sec followed by an automatic reclosing causing a fuse operation the indication starts but will reset after 30 sec If the automatic reset is switched off the indicator will continue flash...

Page 9: ...wnstream of the indicator is added Underground cables have larger capacitance than overhead lines This has to be taken into account when an overhead line feeds an underground cable The following simpl...

Page 10: ...et 4 7 5 Auto Reset Programming of the automatic indication reset AR If enables reset occurs when the line has been energised for more than 30 sec voltage or current Switch 7 Auto reset on return of v...

Page 11: ...y is replaced with a new battery the battery monitoring must be reset With the battery disconnected reset can be done setting Rotary switch to position see figure 11b while at the same time powering t...

Page 12: ...Flashing 1500 flashing hours Battery replacement normally every 7 10 years Indication 1 Super intensive red Flash every 3 sec 10 sec after 12 hours 1 green LED for transient fault 1 amber Yellow LED f...

Page 13: ...e indicators at strategic points along the line 9 1 Before mounting Make sure the indicator is programmed see 4 7 Programming and battery connected before mounting on the line 9 2 Live line mounting b...

Page 14: ...capacity remains and that there is a need for a battery replacement The LT 110T r will in addition transmit a Low Battery message to the Collector Programming Open the indicator by unscrewing the top...

Page 15: ...transient fault Permanent fault GREEN RED Comments The Permanent Fault indication red LEDs is delayed 70 sec to verify a permanent fault Both red and green LED s will flash on permanent faults until r...

Page 16: ...equence 1 2 3 4 Amber 5 Green RESET sequence If the line is energised the GREEN LED only flashes for 3 sec If the line is de energised line the RED LED s only flashes for 3 sec 3 s 3 s 2s Test sequenc...

Reviews: