LineTro110Tµr User Guide  

June 2011               Page 8 of 16 

4.3.

 

Transient faults 

 

Transient faults cleared within the last 
automatic reclosing, can be detected by the 
green LED. The green LED will flash for 24 
hours as extended transient indication. 

 

 

 

 

 

 

 

 

If a new fault occurs within timeout (24h), 
the indicator will reset the green LED and 
indicate for the new fault. 
 

4.4.

 

Fused lines 

 
One operation criterion (assuming automatic 
voltage reset is enabled) is that, after a fault, 
three-phase disconnection of the line has to 
be carried out.  
If, instead of a three-phase trip, a fuse 
operates in one or two phases, then the 
voltage of the healthy phase(s) may result in 
no indication or a reset of indication. 
This is true for indicators placed before a 
fuse as well as after it.  
 
When the criterion of automatic voltage 
reset is enabled, the LINETROLL-110T

r is 

not activated unless the fault causes a three-
phase trip within 5 seconds after the 
occurrence of the fault. 
If there is only one disconnection within 5 
sec, followed by an automatic reclosing 
causing a fuse-operation, the indication 
starts, but will reset after 30 sec. 
 
If the automatic reset is switched off, the 
indicator will continue flashing until it is 
reset manually or after the automatic timer 
period has elapsed.    
 

4.5.

 

Multiple faults 

 
Multiple faults can sometimes occur. 
Defective network components may burn or 
break due to the electro-dynamic force of a 
fault current and cause a second fault.  
 
Another cause of multiple faults for network 
where the neutral is isolated from earth or 
earthed via a resistor, is an increase in the 
phase to ground voltage on healthy phases 
due to an initial earth fault. 
The phase to ground voltage may reach up to 
1.7 times the nominal voltage, depending on 
the total impedance of the earth loop. If there 
are any weak points in the line, they may not 
withstand such a large voltage increase. This 
type of fault may be difficult to find as they 
often are non-permanent and only appear in 
situations like the ones mentioned here.  
 

Note: In this situation the indicators may 
show non-consequent indication. 

 
 
 

<5s 

Line 

Indication 

24h 

Extended transient fault 
indication 

Green 
 LED 

Summary of Contents for LineTroll 110Tmr

Page 1: ...LineTroll 110T r User Manual...

Page 2: ...sing a healthy line 7 4 2 Connecting a faulty line while the indicator is activated 7 4 3 Transient faults 8 4 4 Fused lines 8 4 5 Multiple faults 8 4 6 Capacitive discharges 9 4 7 PROGRAMMING 10 5 MA...

Page 3: ...ermanent fault and 1 regular Green LED for transient faults The LED flash can be seen within 100 200 metres distance The lens of the indicator allows for uniform 360 degrees monitoring LINETROLL 110E...

Page 4: ...ush current it s di dt sensor is blocked for 5 sec upon energising of a line While the blocking time elapses the line current can stabilise so as not to cause triggering of the di dt sensor A fault du...

Page 5: ...d giving more than 1500 hours of flashing capacity The battery is fitted with a connector for simple replacement Figure 3 Initial battery capacity Figure 4 Remaining battery capacity as a function of...

Page 6: ...ce there may be an indication in a branch due to a non permanent fault while another branch without an indicator installed may be faulty yet remain unidentified as such Near line points with sectional...

Page 7: ...blocking time a shows the sequence when a fault occurs less than 5 sec after line has been energised No Indication If upon re energising of a line the unit is already indicating due to a previous fau...

Page 8: ...tion within 5 sec followed by an automatic reclosing causing a fuse operation the indication starts but will reset after 30 sec If the automatic reset is switched off the indicator will continue flash...

Page 9: ...wnstream of the indicator is added Underground cables have larger capacitance than overhead lines This has to be taken into account when an overhead line feeds an underground cable The following simpl...

Page 10: ...et 4 7 5 Auto Reset Programming of the automatic indication reset AR If enables reset occurs when the line has been energised for more than 30 sec voltage or current Switch 7 Auto reset on return of v...

Page 11: ...y is replaced with a new battery the battery monitoring must be reset With the battery disconnected reset can be done setting Rotary switch to position see figure 11b while at the same time powering t...

Page 12: ...Flashing 1500 flashing hours Battery replacement normally every 7 10 years Indication 1 Super intensive red Flash every 3 sec 10 sec after 12 hours 1 green LED for transient fault 1 amber Yellow LED f...

Page 13: ...e indicators at strategic points along the line 9 1 Before mounting Make sure the indicator is programmed see 4 7 Programming and battery connected before mounting on the line 9 2 Live line mounting b...

Page 14: ...capacity remains and that there is a need for a battery replacement The LT 110T r will in addition transmit a Low Battery message to the Collector Programming Open the indicator by unscrewing the top...

Page 15: ...transient fault Permanent fault GREEN RED Comments The Permanent Fault indication red LEDs is delayed 70 sec to verify a permanent fault Both red and green LED s will flash on permanent faults until r...

Page 16: ...equence 1 2 3 4 Amber 5 Green RESET sequence If the line is energised the GREEN LED only flashes for 3 sec If the line is de energised line the RED LED s only flashes for 3 sec 3 s 3 s 2s Test sequenc...

Reviews: