LineTro110Tµr User Guide  

June 2011               Page 9 of 16 

4.6.

 

Capacitive discharges 

 
The LINETROLL-110T

r indicator is not 

directional, it therefore detects current 
without discriminating direction. In case of 
an earth fault, the network capacitive energy 
discharges in the fault point. It should be 
checked that the capacitive discharge current 
downstream of the indicator is below the 
preset trip level in order to avoid the 
indicator erroneously activating upon earth 
faults.  
 
If the total capacitive current exceeds the trip 
level, it is advisable to change the trip level 
or install the indicators in the branching 
points instead of in the main line. The 
capacitive discharge of a branching point is 
limited by its own capacitance, while in the 
main line the capacitive current of all the 
branches downstream of the indicator is 
added. Underground cables have larger 
capacitance than overhead lines. This has to 
be taken into account when an overhead line 
feeds an underground cable.  
 
The following simplified formula may be 
used to estimate the capacitive discharge 
current for a line: 

 

 

Ic    =   U * La     +     U * Lc 

 

              300                  K 

 
 

Ic  =  Capacitive current in A 

 

U  =  Nominal voltage in kV 

 

La =  Overhead line length in km 

 

Lc =  Cable length in km 

 

K  =  10; for oil impregnated  

cables 

 

           5; for PEX cables 

 

           3; for PVC cables 

 

In order to avoid that the LINETROLL-
110T

r is activated by an earth fault 

downstream of the indicator, the following 
criterion has to be met.  

 

 

Ic  <   It  

where 

 

Ic   = capacitive current downstream of 
 

the indicator. 

It   =   Setting of sensitivity (500 or 1000A)

 

 
 

To estimate the capacitive discharge current 
at any line point, you have to calculate the 
contribution from all the overhead lines and 
underground cables lengths beyond that 
point only. 
 

 

Figure 8: Capacitive discharge current calculation 
example 

Proposed location 

for LT 110Tµr 

Summary of Contents for LineTroll 110Tmr

Page 1: ...LineTroll 110T r User Manual...

Page 2: ...sing a healthy line 7 4 2 Connecting a faulty line while the indicator is activated 7 4 3 Transient faults 8 4 4 Fused lines 8 4 5 Multiple faults 8 4 6 Capacitive discharges 9 4 7 PROGRAMMING 10 5 MA...

Page 3: ...ermanent fault and 1 regular Green LED for transient faults The LED flash can be seen within 100 200 metres distance The lens of the indicator allows for uniform 360 degrees monitoring LINETROLL 110E...

Page 4: ...ush current it s di dt sensor is blocked for 5 sec upon energising of a line While the blocking time elapses the line current can stabilise so as not to cause triggering of the di dt sensor A fault du...

Page 5: ...d giving more than 1500 hours of flashing capacity The battery is fitted with a connector for simple replacement Figure 3 Initial battery capacity Figure 4 Remaining battery capacity as a function of...

Page 6: ...ce there may be an indication in a branch due to a non permanent fault while another branch without an indicator installed may be faulty yet remain unidentified as such Near line points with sectional...

Page 7: ...blocking time a shows the sequence when a fault occurs less than 5 sec after line has been energised No Indication If upon re energising of a line the unit is already indicating due to a previous fau...

Page 8: ...tion within 5 sec followed by an automatic reclosing causing a fuse operation the indication starts but will reset after 30 sec If the automatic reset is switched off the indicator will continue flash...

Page 9: ...wnstream of the indicator is added Underground cables have larger capacitance than overhead lines This has to be taken into account when an overhead line feeds an underground cable The following simpl...

Page 10: ...et 4 7 5 Auto Reset Programming of the automatic indication reset AR If enables reset occurs when the line has been energised for more than 30 sec voltage or current Switch 7 Auto reset on return of v...

Page 11: ...y is replaced with a new battery the battery monitoring must be reset With the battery disconnected reset can be done setting Rotary switch to position see figure 11b while at the same time powering t...

Page 12: ...Flashing 1500 flashing hours Battery replacement normally every 7 10 years Indication 1 Super intensive red Flash every 3 sec 10 sec after 12 hours 1 green LED for transient fault 1 amber Yellow LED f...

Page 13: ...e indicators at strategic points along the line 9 1 Before mounting Make sure the indicator is programmed see 4 7 Programming and battery connected before mounting on the line 9 2 Live line mounting b...

Page 14: ...capacity remains and that there is a need for a battery replacement The LT 110T r will in addition transmit a Low Battery message to the Collector Programming Open the indicator by unscrewing the top...

Page 15: ...transient fault Permanent fault GREEN RED Comments The Permanent Fault indication red LEDs is delayed 70 sec to verify a permanent fault Both red and green LED s will flash on permanent faults until r...

Page 16: ...equence 1 2 3 4 Amber 5 Green RESET sequence If the line is energised the GREEN LED only flashes for 3 sec If the line is de energised line the RED LED s only flashes for 3 sec 3 s 3 s 2s Test sequenc...

Reviews: