Annunciators
1. Product Description
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
21
Annunciators
ACS Series LED Zone Type Annunciators
The “Annunciator Control System” Series annunciators remotely display system status. Connections
are through an EIA-485 serial connection from TB5 on the control panel.
For information and installation instructions refer to
Annunciator Control System
manual.
Refer to "System Edit" on page 49, for information on programming the AFP-100 for annunciator use.
Below are brief descriptions of Annunciator Control and Annunciator Expander Modules used with the
control panel.
Annunciator Control Module - ACM-16AT
Provides features for audible and visual indication of alarm and trouble
conditions at each annunciator. They include:16 red alarm LEDs, 16
yellow trouble LEDs, 16 momentary touch-pad switches for controlling
each point, System trouble LED, Online/Power LED, Local sounder,
Silence/Acknowledge switch, and Remote functions.
Annunciator Expander Module - AEM-16AT
Expands the ACM-16AT by 16 system points and is identical in size and
appearance. Three expander modules are supported by one control module
providing a maximum of 64 system points.
Note:
An AEM-16AT cannot be used to expand an ACM-32A.
Annunciator Control Module - ACM-32A
Provides features for audible and visual indication of alarm and trouble
conditions at each annunciator. They include: 32 red alarm LEDs, System
trouble LED, Online/Power LED, Local sounder, and Silence/
Acknowledge switch.
Annunciator Expander Module - AEM-32A
Expands the ACM-32A by 32 system points and is identical in size and
appearance. One expander module is supported by the control module
providing a maximum of 64 system points.
Note:
An AEM-32A cannot be used to expand an ACM-16AT.
A
C
M
-16A
T
.cdr
Alarm Zone
Alarm Zone
Alarm Zone
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Alarm Zone
Alarm Zone
Alarm Zone
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
A
C
M-3
2A
.cdr
Technical Manuals Online! - http://www.tech-man.com