Power Connections
2. Installation
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
29
Power Connections
Caution:
You can connect different sources of power to the control panel. Before servicing, disconnect
all sources of power. Damage to the control panel and associated equipment can result when removing
and/or inserting cards, modules or interconnecting cables while the control panel is energized.
AC Connections
Primary power required for the AFP-100 control panel is 110/120 VAC, 60 Hz, 2.3 amps and for the
AFP-100E is 220/240 VAC, 50 HZ, 1.2 amps.
Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code
(NEC) and/or local codes. Use #14 AWG (2.00 mm
2
) or larger wire with 600 VAC insulation rating.
In order for the AFP-100E to comply with Compatibility Directive 89/336/EEc for European
Communities (EU Requirements), a ferrite bead P/N: 29085, must be installed on the Mains for RF
filtering. Refer to Document #50404 for details.
The figure below shows connections for AC power:
Figure 7 AC Power Connections
Earth Ground Connections
Connect a wire from the labeled grounding stud located inside the backbox to a known solid earth
ground. This connection is vital for maintaining the control panel's immunity to unwanted transients
generated by lightning and electrostatic discharge.
!