2. Installation
UL Power-limited Wiring Requirements
34
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
UL Power-limited Wiring Requirements
General
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet.
All power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) away from any
nonpower-limited circuit wiring.
Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit
the cabinet through different knockouts and/or conduits.
A typical wiring diagram for the AFP-100 is shown below.
Figure 13 Typical UL Power-limited Wiring Requirements
RTM-8F
Nonpower-limited and power-limited wiring must have a minimum distance of 0.25 inches
wire-to-wire. If this module is used to drive nonpower-limited and power-limited circuits, follow the
instructions below:
1. Skip a set of dry contacts to maintain the 0.25 inches required space between power-limited and
nonpower-limited circuits.
2. If this module is needed to drive power-limited and nonpower-limited relays that are next to each
other, make no connection to the Normally Open contact which separates the two groups of relays.
Refer to the wiring diagram above.
Note:
Refer to "Installing a RTM-8F Module" on page 35, for additional information on the RTM-8F.
24V UNREG 24V NONRS 24V RST
BELL 2 POWER
BELL 1 POWER
SUPV
ALAR M
TROUBLE
PC/PRINTER TERM COMM
G
ND F
A
U
LT
D
ISA
BL
E
TR
A
N
SF
ORM
E
R
1
TR
AN
SF
O
R
M
E
R 2
- +
BATTERY
RS
-2
32
PC
/P
R
IN
T
ER
RS
-4
8
5
TE
R
M
. M
O
D
E
TR
O
U
B
LE
+ - + - + -
B+ A+ A- B-
B+ A+ A- B-
NO C NO NC C NO NC C
A B B+ A+ B- A-
1 COMM 2
ACS
SHIELD
SLC
SLC
OUT+ IN + OUT- IN -
T
B
4
T
B
2
T
B
1
T
B
3
T
B
7
T
B
5
T
B
6
J16
J6
JP3
JP1
CAUTION
HIGH VOLTAGE
J3
TB8
J19
J17
JP4
SW1
SW3
SW2
CA
UTIO
N!
HI
G
H
V
O
L
TAG
E
GNDFAULT
C
C
C
C
C
C
C
C
NC
NC
NC
NC
NC
NC
NC
NC
NO
NO
NO
NO
NO
NO
NO
NO
Power-limited
Circuits
Power-limited
Circuits
Nonpower-limited
Circuits
Power-limited
Circuits
Nonpower-limited
Circuits
AC Power
This output is only nonpower-
limited if programmed as a
municipal box output.
No connection
9200p
w
rl
.cdr
Grounding Stud
Technical Manuals Online! - http://www.tech-man.com