3. Programming
Initial Power-up
42
AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002
Initial Power-up
After completing the wiring of addressable devices to the SLC, power up the fire alarm system. Because
the addressable devices are not programmed into the control panel, their LEDs will not flash, the
System Trouble LED will be on and the LCD display will alternate between the following two displays:
If the system remains unprogrammed, the panel sounder will activate after two minutes. It can be
silenced by pressing the
ACKNOWLEDGE
/
STEP
key, but it will continue to resound until the system is
programmed.
Menu Selections
1 = Programming
There are two programming levels:
•
Program Level 1
is for system configuration in which data relating to device types, zoning,
messages, etc. is entered into the system memory. Refer to "Program Change – Level One" on
page 44.
•
Program Level 2
is where a qualified operator can access features such as Disable, Clear
History, Walktest, Time Change and Program Check. For Program Level 2, the SW1 Write
Protect switch should remain in the up 'Write Protect' position. Refer to "Program Change –
Level Two" on page 51.
2 = Read Status
Entering Read Status allows the user to read the status of any point/zone in the system plus display or
print the history file or print the entire user program. The Read Status feature is NOT password
protected. Read Status is explained in "Read Status" on page 69.
3 = AC/BAT
Entering AC/BAT allows the user to read the battery voltage and the AC line voltage. The AC/BAT
feature is NOT password protected. The following screen is displayed upon entering AC/BAT:
TROUBLE IN SYSTEM
PROGRAM CORRUPTED
TROUBLE IN SYSTEM
NO DEVICES INSTALL
BATTERY: 24.00 V
AC LINE: 120.00V
BATTERY: 24.00 V
AC LINE: 240.00V
For the
AFP-100
For the
AFP-100E