background image

IQ-318/E/C Installation Manual —

  P/N 52864:J3  9/29/15 

43

Releasing Applications

Applications

Circuit Requirements.   

When connecting a releasing device, note the following:

1. The control panel provides four NAC/Releasing Circuits (Style Y or Z). Each circuit can 

provide 1.5 A. Total current drawn from the power supply cannot exceed 7.4 A in an alarm 
condition (refer to Table 6.2, “System Draw Current Calculations,” on page 52). Use 
compatible UL-listed 24 VDC appliances only. For more information on compatible 
appliances, refer to the 

Device Compatibility Document

.

2. Refer to the Releasing Applications appendix in the 

IQ-318/E Programming Manual

 for 

configuration details (such as setting the Soak Timer).

3. For applications using power-limited circuits:

a) Use an in-line supervisory device (P/N REL-2.2K) with control panel releasing circuits. 
Connect the End-of-Line device as shown in Figure 4.7.
b) Program the releasing circuit for Type Code REL CKT ULC.
c) Circuits are supervised against opens and shorts. 

4. For applications not requiring power-limited circuits – 

a) If the application does not require supervising the releasing device against shorts, in-line 
supervisory devices (P/N REL-2.2K) are not required.
b) In non-power-limited applications, program the releasing circuit for Type Code 
RELEASE CKT.
c) Limited energy cable cannot be used to wire a non-power-limited releasing device circuit
d) Maintain a 0.25 inch (6.35 mm) spacing between the non-power-limited releasing circuit 
device wiring and any power-limited circuit wiring.) 

5. The releasing circuit must be programmed with a releasing type code listed in the 

IQ-318/E 

Programming Manual

 

Figure 4.8  Releasing Circuits (Option 1)

 

Figure 4.9  Releasing Circuits (Option 2)

NOTE:

As per UL 864 9

th

 Edition, a supervisory signal must be indicated at the panel whenever 

a releasing circuit is physically disconnected. Use a monitor module to monitor dry contacts off the 
switch. See 4.11.

IQAc

tua

tor

sa.

w

m

f

IQA

ctua

tor

sb

.wmf

Summary of Contents for AUTOPULSE IQ-318

Page 1: ...AUTOPULSE IQ 318 E C ANALOG ADDRESSABLE CONTROL SYSTEM Fire Alarm Control Panel Installation Manual Meets the Requirements of UL 864 9th Edition J3 P N 52864 J3 ECN 15 230 Document 52864 9 29 15 Rev ...

Page 2: ...ave little visible smoke Detectors that have ion izing type sensing chambers tend to detect fast flaming fires better than smoldering fires Because fires develop in different ways and are often unpredictable in their growth neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warn...

Page 3: ... to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads r...

Page 4: ...priate version for a specific application Documentation Feedback Your feedback helps us keep our documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printe...

Page 5: ...ling EIA 485 Devices 28 3 11 Installing Remote Printers and or CRT 28 3 12 Wiring a Signaling Line Circuit SLC 33 3 13 Connecting a PC for Off Line Programming 34 Section 4 Applications 35 4 1 Overview 35 4 2 Devices Requiring External Power Supervision 35 4 3 NFPA 72 Central or Remote Station Fire Alarm System Protected Premises Unit 36 4 4 Central Station Fire Alarm System Canadian Requirements ...

Page 6: ...Alarm Systems NFPA 72 Inspection Testing and Maintenance for Fire Alarm Systems NFPA 72 Notification Appliances for Fire Alarm Systems Underwriters Laboratories UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors Single and Multiple Station UL 228 Door Closers Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detecto...

Page 7: ... documents referenced in this manual as well as documents for selected other compatible devices The document series chart DOC ANS provides the current document revision A copy of this document is included in every shipment Compatible Conventional Devices Non addressable Document Number Part no if applicable Device Compatibility Document 50054 Fire Alarm Control Panel FACP and Main Power Supply Ins...

Page 8: ...l Smoke and HVAC Control Station 15712 DPI 232 Direct Panel Interface Manual 51499 TM 4 Installation Document Reverse Polarity Transmitter 51490 UDACT Manual Universal Digital Alarm Communicator Transmitter 50050 UDACT 2 Manual Universal Digital Alarm Communicator Transmitter 54089 RA100Z Remote LED Annunciator Installation Document I56 0508 Table 1 1 Reference Documentation 2 of 2 CAUTION Informa...

Page 9: ...ard Notification Appliance Circuits NAC Class A or B Alarm Trouble Supervisory and Security relays Support for 32 annunciator addresses with 10 special annunciator groups Supports Style 4 Style 6 Style 7 SLC loops Releasing service using on board NACs or FCM 1 modules Logic Equations Display scroll selection Alarm verification supervisory indication NYC Supervisory duct detectors Supports Intellig...

Page 10: ...on and CPS 24 E IQ318 E is the control panel itself and the heart of the system it ships with a grounding cable battery interconnect cables and document kit CPS 24 E mounts directly on the control panel The system ships pre installed in its cabinet NOTE The CPS 24 E is an integral part of the IQ318 and is not available separately A primary display KDM R2 keypad display Batteries are ordered separa...

Page 11: ...for many functions including Powering the IQ 318 E Powering a variety of UL listed 24 VDC notification appliances from four built in NAC outputs Providing up to 1 25 A of resettable power for four wire smoke detectors Providing up to 1 25 A of non resettable power for external devices such as the TM 4 Transmitter Module Providing auxiliary 24 VDC power 0 5 A and 5 VDC power 0 15 A Fuse 8 amps 250 ...

Page 12: ... See Figure 3 6 on page 22 TB12 EIA 232 Printer Connection Figure 3 15 on page 33 TB12 EIA 232 PC Terminal Connection CRT Figure 3 16 on page 31 J1 Network Service Connection NUP power limited supervised J2 USB A VeriFire Tools Connection J3 USB B VeriFire Tools Connection TB8 NAC 2 All NAC Circuits power limited supervised Figure 3 9 on page 24 TB9 NAC 1 TB7 NAC 3 TB6 NAC 4 Output Relays power li...

Page 13: ...Silenced LED LED4 System Trouble LED LED8 Fire Alarm LED LED1 Power on LED AC or battery System Switches No Keyboard Operation SW5 Acknowledge SW6 Silence SW7 Reset CPU320 KAPS 291809 wmf CPU2 640 JP1 SLC Ground Fault Jumper SW1 Ground Fault Detection Enable Disable LED3 Earth Fault LED general board ground fault Figure 2 3 IQ318 and Power Supply Jumpers LEDs and Switches LED5 24V Aux LED LED6 5V ...

Page 14: ...ight 5 81 in 14 76 cm depth Door 18 187 in 46 195 cm width 18 40 in 46 736 cm height 0 75 in 1 905 cm depth When using trim ring TR 320 mount backbox with at least 1 inch 2 54 cm between wall surface and front of backbox to allow door to open fully past the trim ring The TR 320 molding width is 0 905 in 2 299 cm Additional Options The IQ 318 E control panel provides space for one or two additional...

Page 15: ...Combination Photoelectric Heat Detector FSH 751 HARSH Smoke Detector HPX 751 Intelligent HARSH Detector FSL 751 VIEW Low Profile Laser Detector FSM 101 Pull Station Monitor Module FRM 1 Relay Module FSP 751 FSP 851 Photo Detector FDRM 1 Dual Monitor Dual Relay FSP 751T FSP 851T Photo Thermal Detector DNR W Intelligent Non Relay Photoelectric Duct Detector FST 751 FST 851 Thermal Detector FST 751R ...

Page 16: ...revious Editions of UL 864 NOTE The products in this list have not received UL 864 9th Edition certification and may only be used in retrofit applications ACM 16AT Annunciator Control Module ACM 32A Annunciator Control Module ACPS 2406 Auxiliary Charger Power Supply AEM 16AT Annunciator Expander Module AEM 32A Annunciator Expander Module APS 6R Auxiliary Power Supply BGX 101L Addressable Manual Pu...

Page 17: ...nd Local codes for fire alarm systems Do not draw wiring into the bottom 9 inches 22 86 cm of the cabinet except when using a separate battery cabinet this space is for internal battery installation Review installation instructions in Section 3 2 Installation Checklist 3 1 1 Standards and Codes In addition installers should be familiar with the following standards and codes NEC Article 300 Wiring ...

Page 18: ...up Alarm Switches 4 Connect AC wiring place batteries into backbox without connecting them and run cable to optional power supplies DC power outputs NACs and relays CAUTION Do not apply AC or DC power at this time Section 3 5 Connecting the Power Cables 5 Optional Install output devices such as a printer or CRT terminal Section 3 11 Installing Remote Printers and or CRT 6 Wire annunciators Relevan...

Page 19: ... Select and punch open the appropriate knock outs For selection guidelines see Section 3 9 UL Power limited Wiring Requirements 3 Using the keyholes mount the backbox over the two screws 4 Mark the location for the two lower holes remove the backbox and drill the mounting holes 5 Mount the backbox over the top two screws then install the remaining fasteners Tighten all fasteners securely 6 Feed wi...

Page 20: ...onics on the lower option board 4 Secure the top option board with four 4 40 screws supplied 5 Re attach KDM R2 Installing a Transmitter Module TM 4 TM 4 is power limited Connections are on TB10 nonresettable output and TB11 EIA 485 ACS Mode Refer to the Transmitter Module TM 4 installation document for installation details Figure 3 2 Removing and Reinstalling KDM R2 320_assembly_tech_pubs_5 2 wmf...

Page 21: ...l Panel to AC Power Connect primary power as follows see Figure 3 4 1 Turn off the circuit breaker at the main power distribution panel 2 Open the hinged insulating cover on TB1 3 Connect the service ground to terminal marked Ground Earth 4 Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to terminal marked HOT 5 Close the hinged insulating cover over TB1 3 5 3 ...

Page 22: ...ence of steps in Section 3 2 Installation Checklist Table 3 1 this is part of Step 4 Component Status Control panel circuit board The green AC Power indicator on the system Trouble indicator on because batteries are not connected Each option board In an unconfigured system the yellow Trouble indicator may come on for approximately 10 seconds after applying AC power Each auxiliary power supply The ...

Page 23: ...s circuit to power devices that require low noise 24 VDC power such as annunciator model ACM 24AT or the transmitter module TM 4 Connect external field wires to power supply terminals TB10 NONRESET and to provide up to 1 25 A of non resettable current for powering external devices such as annunciators See Figure 3 6 above TB2 on CPS 24 TB10 and all 4 NACs share a maximum of 3 0 A in standby and 6 ...

Page 24: ...ances only refer to the Device Compatibility Document nfs640 nacout cdr Style Y Class B Connection Style Z Class A Connection Unused Circuits UL listed ELR 2 2K 1 2 W supplied Figure 3 8 Notification Appliance Circuit NAC Connections Figure 3 9 NAC Terminals and NAC LEDs TB9 NAC 1 TB8 NAC 2 TB7 NAC 3 TB6 NAC 4 CPU 320 NACS wmf A A A A A A A A B B B B B B B B NOTE Any NAC can be programmed as a rel...

Page 25: ...le Stat X devices installed in series the REL 2 2K is installed on the last device on the releasing circuit as shown A REL 2 2K is required for ULC applications Stat X devices are not to be used with the FCM 1 or FCM 1 REL 3 7 Output Relay Connections The panel provides a set of Form C relays These are rated for 2 0 A at 30 VDC resistive Alarm TB4 Trouble TB4 Supervisory TB5 Security TB5 These are...

Page 26: ...n on if the corresponding switch was enabled The alarm will activate during microcontroller failure regardless of the settings of switches SW1 SW4 SW1 NAC 1 SW2 NAC 2 SW3 NAC 3 SW4 NAC 4 So for example if SW1 and SW4 were enabled at the time of an alarm during microcontroller failure NAC 1 and NAC 4 would activate Follow sequence of steps in Section 3 2 Installation Checklist Table 3 1 WARNING Do ...

Page 27: ...is routed away from power limited wiring 640 2 PWRLMTWIR ISO2 wmf Figure 3 13 Typical Wiring for UL Power limited Wiring Requirements Shown with relays as connected to power limited modules NOTE AC and battery wiring are not power limited Maintain at least 0 25 inches 6 35 mm between power limited and non power limited circuit wiring Install tie wraps and adhesive squares to secure the wiring Use ...

Page 28: ... 10 Installing EIA 485 Devices Figure 3 14 provides a closer view of the EIA 485 connections provided on TB11 Because specific connections can vary by the type of device being connected refer to the product installation manual for details Figure 3 14 EIA 485 Connections 3 11 Installing Remote Printers and or CRT 3 11 1 Custom Cable Fabrication A custom cable needs to be fabricated to connect the P...

Page 29: ...prietary Fire Alarm System a remote printer requires a secondary power source battery backup Because a secondary power source is not provided use a separate Uninterruptable Power Supply UPS that is UL listed for Fire Protective Signaling You may use your building emergency power supply so long as it meets the power continuity requirements of NFPA 72 Refer to NFPA 72 for further details Connect the...

Page 30: ...or end of the custom cable into the EIA 232 port of the CRT 2 Tighten securely 3 Set parameters as discussed in Table 3 16 Figure 3 15 Remote Printer Connections DB 25 connector on PRN series printer female socket shown DB 9 Connector on PRN series Printer CPU2 640 PRN WMF Control Panel NOTE Outputs are power limited but are not supervised Terminate one end of shield at backbox DB9printer wmf Opti...

Page 31: ...space bar to view the options for each parameter When finished programming all setup groups press the Pause key To save all changes press Y Table 3 4 shows the standard settings for using the CRT 2 with the IQ 318 E for one instance where these settings may change slightly see Section 3 11 4 Connecting Multiple Printers CRTs or CRT PRN Combination The basic settings for using the CRT 2 with IQ 318...

Page 32: ...de ASCII Key Repeat Off Keyboard Present Yes Key Mode ASCII Margin Bell Off F5 Keys Prior key Enter Key CR Alt Key Meta Pound Key U S Return Key CR Disconnect Pause Backspace BS DEL Desk Acc Disabled F6 Ports Next key EIA Baud Rate 9600 Aux Baud Rate 9600 EIA Xmt Xon Xoff Aux Xmt Xon Xoff EIA Break Off Aux Break Off EIA Data Format 8 1 N Aux Data Format 8 1 N EIA Recv Xon Xoff XPC Aux Recv Xon Xof...

Page 33: ...monitor and control modules Units employing multiple detector operation shall include a minimum of two detectors in each protected space and reduce the detector installation spacing to 0 7 times the linear spacing in accordance with National Fire Alarm Code NFPA For spacing requirements refer to the detector s installation instructions Installation This control panel supports one SLC loop which co...

Page 34: ...onnect the PC to USB B via a standard USB B cable 2 For PCs without USB Ports connect the PC s serial port to the Control Panel s Network Service Connection J1 NUP Note T Tapping is not allowed on a four wire SLC SLC B output loop SLC A loop return SLC B SLC A Style 4 SLC Loops Style 6 SLC Loops SLC Loop Connections on FACP s main circuit board TB13 on IQ 318 E nfs640 slcloops cdr CPU 320 SLC TB w...

Page 35: ...Premises Unit How to install UDACT UDACT 2 with the control panel for use as a NFPA Central or Remote Station Fire Alarm System Protected Premises Unit Section 4 5 NFPA 72 Proprietary Fire Alarm Systems How to set up a Protected Premises Unit to communicate with a listed compatible Protected Premises Receiving Unit Section 4 6 Fire Security Applications How to use the control panel as a combinatio...

Page 36: ...Manual or UDACT 2 Instruction Manual Device to be Supervised Non resettable 24 VDC Power from a listed source SLC from FACP N C Supervision Relay Contact Part of EOLR 1 Not required for FlashScan type codes that provide built in power supervision Power Supervision Relay EOLR 1 Not required for FlashScan type codes that provide built in power supervision 3030 external power suptpH wmf If the SLC de...

Page 37: ...ound To supervised phone lines Ferrite cores P N 29090 FACP Cabinet EIA 485 ACS Mode 24 VDC Nonresettable power Supervised and power limited EIA 485 and power wiring CPU 320 udact wmf Figure 4 2 Typical Wiring Diagram for a Central Station Fire Alarm System NOTE Install a UL listed 120 ohm End of Line resistor P N 71244 UDACT TB1 terminals 3 and 4 if this is the last or only device on EIA 485 line...

Page 38: ...ire Alarm System Protected Premises Unit For information on installing and programming the Receiving unit refer to the documentation for that control panel 0 NO ON NC C 18 24 115 230 1 1 S 5 W LED3 LED4 LED1 LED2 S 1 W ELR TXACS RXACS POWER TROUBLE SW4 REMOTE STATION ALARM ACS TB2 TB1 ACS REF REMOTE STATION SUPERVISORY MUNICIPAL BOX REMOTE STATION TROUBLE T 3 B S 2 W S 3 W SW6 NON ISOLATED DISABLE...

Page 39: ...cate a door tamper condition whenever the door is open If the control panel indicates a Security alarm you can acknowledge silence and reset the condition from the control panel When the system resets a 30 second exit timer starts During this time the tamper switch and all Security alarms are ignored There is no entrance delay timer For bypass of security zones use the DISABLE routine covered in t...

Page 40: ...ule s to be used for security 2 Select the Type Code SECURITY 4 6 5 Wiring for Proprietary Security Alarm Applications Table 4 6 shows typical wiring for proprietary security alarm applications with modules Note the following The module is programmed with software SECURITY Type Code For use with UL listed systems only application not for ULC security usage NAC devices used for security cannot be s...

Page 41: ...SLC device does not match the one in this figure refer to the SLC manual appendix which contains wiringconversion charts for type V and type H modules WARNING When used for CO2 releasing applications observe proper precautions as stated in NFPA 12 Do not enter the protected space unless physical lockout and other safety procedures are fully completed Do not use software disable functions in the pa...

Page 42: ...power loss with power supervision relay Type Code REL CKT ULC For use in UL or ULC applications Requires REL device at solenoid Power limited wiring Supervised for open circuit and shorts Supervised for power loss with power supervision relay To connect Refer to A releasing device to the control panel Section 4 7 4 Connecting a Releasing Device to the Control Panel A releasing device to the FCM 1 ...

Page 43: ...igure 4 7 b Program the releasing circuit for Type Code REL CKT ULC c Circuits are supervised against opens and shorts 4 For applications not requiring power limited circuits a If the application does not require supervising the releasing device against shorts in line supervisory devices P N REL 2 2K are not required b In non power limited applications program the releasing circuit for Type Code R...

Page 44: ...uirements When connecting a releasing device to the FCM 1 module note the following 1 Refer to the Releasing Applications appendix in the IQ 318 E Programming Manual for configuration details such as setting the Soak Timer IQActuatorsb wmf GasDisconnect wmf Compatible UL listed 24 VDC releasing device REL 47K Use with Type Code Rel Ckt ULC or see Circuit Requirement 3 Brown Red Non resettable 24 V...

Page 45: ...lications not requiring power limited circuits a In line supervisory devices P N REL 47K are not required however the releasing device circuit is not supervised against shorts b In non power limited applications program the releasing circuit for Type Code RELEASE CKT c Limited energy cable cannot be used to wire a non power limited releasing device circuit d Maintain a 0 25 inch 6 35 mm spacing be...

Page 46: ...mum Module polarities are shown in alarm condition All wiring shown is supervised and power limited Figure 4 13 NPFA Style Y Class B Wiring of the FCM 1 REL Compatible UL listed 24 VDC releasing device One 1 device maximum Non resettable 24 VDC power SLC SLC Figure 4 13 NPFA Style Z Class A Wiring of the FCM 1 REL Module polarities are shown in alarm condition All wiring shown is supervised and po...

Page 47: ...sing Device to the Control Panel on page 42 If using FCM 1 see Circuit Requirements for Section 4 7 5 Connecting a Releasing Device to the FCM 1 Module on page 44 SLC loop to FACP FCM 1 FRM 1 FMM 1 FMM 101 Black Red Yellow Violet Black Red Non resettable 24 VDC from main power supply Manual Abort Manual Release Normal Release NBG 12LRA See Document 51369 for installation details ELR mode R 47K sup...

Page 48: ...epartment and the central alarm receiving station if transmitting alarm conditions b notify facility personnel of the test so that alarm sounding devices are disregarded during the test period and c when necessary disable activation of alarm notification appliances and speakers to prevent their sounding Disconnect all releasing devices to prevent accidental activation in accordance with NFPA 2001 ...

Page 49: ... a leaking or damaged battery Batteries should be replaced in accordance with the battery manufacturer s recommendations If a battery leaks and contact is made with the Sulfuric Acid immediately flush skin and or eyes with water for at least 15 minutes Water and household baking soda provides a good neutralizing solution for Sulfuric Acid If Sulfuric Acid gets into eyes seek immediate medical atte...

Page 50: ...d several types of external devices continuously during non fire alarm conditions Use column 1 in Table 6 2 to calculate the Non Fire Alarm Load on the power supply regulator when applying primary power The main power supply must also provide a finite amount of additional current during a fire alarm condition Use column 2 in Table 6 2 to calculate the additional current needed during fire alarms T...

Page 51: ...each set of devices in calculation columns 1 2 and 3 Calculation Column 1 Primary Non Fire Alarm Current in amps Add the contents of calculation column 1 to get the current drawn from the power supply during a non alarm condition with AC power applied This current draw cannot exceed 3 9 A without an auxiliary power supply Calculation Column 2 Primary Fire Alarm Current in amps Calculation column 2...

Page 52: ...0 0643 x 0 100 x 0 025 x x x 0 0643 x 0 050 FZM 1 MMX 2 Auxiliary power x 0 0115 x 0 090 x 0 0115 RPT 485W RPT 485WF x 0 017 x 0 017 x 0 017 UDACT Communicator UDACT 2 Communicator NFV 25 50 see manual x 0 040 x 0 052 x x 0 100 x 0 087 x x 0 040 x 0 052 x Four Wire Smoke Detectors x x x x x x Power Supervision Relay EOLR 1 x 0 020 x 0 020 x 0 020 Notification Appliance powered from Main Power Supp...

Page 53: ...taken from Table 6 3 below assume that while in a fire alarm condition batteries must feed the main power supply and any additional supplies such as the APS2 6R with the maximum rated power each supply can provide Device Quantity Current in amps Total Current Type Alarm Current from Table 6 2 col 2 APS2 6R Actual load current may be used in place of maximum rated supply current To calculate actual...

Page 54: ...ystems requires 24 hours of standby power followed by 5 minutes in alarm 2 NFPA 72 Auxiliary and Remote Station Systems require 24 hours of standby power followed by 5 minutes in alarm 3 Batteries installed in a system powered by an automatic starting engine generator need to provide at least 4 hours of standby power 4 Factory Mutual requires 90 hours of standby for deluge preaction systems 5 Emer...

Page 55: ...hat are within the acceptable battery charger range Write the amp hours requirements on the Protected Premises label The maximum battery size that can be mounted inside the IQ 318 s cabinet is 26AH Battery Size Voltage Rating Number Required Part Number Backbox Part Number 18 AH 12 volts two BAT 12180 IQ 318 enclosure BB 25 26 AH 12 volts two BAT 12260 IQ 318 enclosure BB 25 100 AH 12 volts four f...

Page 56: ... an auxiliary power supply such as FCPS 24S6 S8 or APS 6R refer to the documentation for that equipment Charger Description Specifications CPS 24 E Main Power Supply An internal battery charger for 18 AH to 200 AH Normal Charge 27 6 VDC 0 24 VDC Charging Current 2 0 A or 5 7 A Software selectable CHG 120 Battery Charger An external battery charger designed to charge lead acid batteries between 26 ...

Page 57: ...Refer to the Device Compatibility Document for compatible devices and notification appliances Item Value Max wiring voltage drop 2 VDC Retrofit note SLCs with old CMX modules are restricted to 1 2 VDC NAC Nominal operating voltage 24 VDC regulated 1 5 A max Special Applications for Releasing Circuits 20 16 26 42 VDC Current for all external devices connected to the control panel s power supply 7 4...

Page 58: ...usceptibility to transients generated by lightning and electrostatic discharge Operating Power Secondary Power Source Batteries The battery charger is current limited and can recharge sealed lead acid type batteries The battery charger shuts off when the control panel is in alarm 7 2 Wire Requirements Each type of circuit within the Fire Alarm Control System requires use of a specific wire type to...

Page 59: ...8 AWG 0 82 mm2 minimum 20 feet 6 1 m without modem 16 AWG 1 31 mm2 IDC Initiating Device Circuit FMM 1 FMM 101 FDM 1 XP10 M XP6 MA power limited 12 18 AWG 3 31 to 0 82 mm2 Maximum circuit resistance is 20 ohms 12 to 18 AWG 3 31 to 0 82 mm2 NAC Notification Appliance Circuit FCM 1 XP6 C power limited 12 18 AWG 3 31 to 0 82 mm2 At alarm current level no more than a 1 2 V drop at the end of the circu...

Page 60: ...21 22 E Electrical connections 21 Electrical Specifications 56 Ematch Protection Device 25 EOLR 1 see Power Supervision Relay External Power Supervision 35 F FCM 1 also see Releasing Applications Circuit Requirements 44 FCM 1 REL also see Releasing Applications 46 Connections 46 Fire Security Applications 39 41 Form C relays 25 57 Four wire Smoke Detector Specifications 57 I Installation Checklist...

Page 61: ...easing Circuits Connections 24 Releasing Applications 41 47 Specifications 57 Releasing Device Circuit Requirements 42 Connections 42 FCM 1 REL Connections 46 S Security Relays see Form C Relays 25 Security Tamper Switch 39 40 Service 48 SLC Device Capacity 33 Installation 33 Maximum Wiring Distance 33 specifications 56 SLC See also SLC Wiring Manual 33 Specifications 56 57 Standard equipment 10 S...

Page 62: ...008 Tyco International Ltd TYCO SAFETY PRODUCTS ONE STANTON STREET MARINETTE WI 54143 2542 715 735 7411 No 434184 01 Copyright 2008 Tyco International Ltd TYCO SAFETY PRODUCTS ONE STANTON STREET MARINETTE WI 54143 2542 715 735 7411 ...

Reviews: