Page 16
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
INDICATORS
Qty
Descriptor
Colour
Function
Buzzer
1
MAINS ON
Green
Illuminates when there is 200/220/240 VAC supply to
the panel.
1
BATT FAULT
Yellow Illuminates if the battery fails a battery test.
Illuminates if batteries are disconnected >30 seconds.
Illuminates if batteries are short circuit >30 seconds.
Yes
1
CHARGER HIGH
Yellow Illuminates if the power supply / battery charger
exceeds the recommended float charge voltage.
Yes
1
CHARGER LOW
Yellow Illuminates if the power supply / battery charger falls
below the recommended float charge voltage for > 15
seconds.
Yes
1
COMMON FAULT
Yellow Illuminates if;
Any de-isolated zone goes into fault.
ACF output is open circuit
Bell output is open circuit
Battery Fault LED
Charger High LED is on.
MAF Isolate LED is on.
Yes
1
MAF ACT
Red
Illuminates if any zone goes into alarm and transmits
a general alarm signal.
1
MAF ISO
Yellow Illuminates if an external brigade switch is isolated.
Also used for fault on added devices eg. Evac unit.
1
ACF ACT
Red
Illuminates if the ACF output has been activated.
1
ACF FLT
Yellow Illuminates if there is no load on the ancillary circuit,
(an open circuit ), ie: no relay or EOL resistor. The
LED will extinguish if the load is restored.
Yes
1
ACF ISO
Yellow Illuminates if the ancillary output has been manually
isolated.
1
BELL ACT
Red
Illuminates if the bell output has been energised. This
LED will extinguish if bells are silenced or the alarm is
removed.
1
BELL FLT
Yellow Illuminates if there is no load on the bell circuit (an
open circuit ), ie: no bell or EOL resistor. The LED will
extinguish if the load is restored.
Yes
1
BELL ISO
Yellow Illuminates if the bell output has been manually
isolated. Flashing = silenced.
1
BUZZER ISO
Yellow Illuminates if the panel's internal piezo buzzer has
been manually isolated. Flashing = silenced.
8
ALARM LEDS
Red
This LED will flash if it's corresponding zone goes
into alarm. It will remain on until the alarm is reset. If
the zone is programmed as a time delay type, a steady
LED indicates the “pre-alarm” condition. If the zone is
isolated and in alarm it will also be steady.
Yes
8
FAULT LEDS
Yellow This LED illuminates if it's corresponding zone goes
into fault. It will remain on until the fault is removed.
Yes
8
ISOLATE LEDS
Yellow This LED illuminates if its corresponding zone is
isolated. It will remain on until the zone is de-isolated.