BATTERY TEST
BATT
TEST
This function tests the performance of the batteries fitted to the system. Pressing this button will initiate a
battery test as specified.
The test will temporarily disconnect the batteries from the panel and apply load on the batteries for 60
seconds. If the batteries are OK, the test will be performed for 60 seconds and then the panel will return to
normal. If the batteries fail the test, the “Battery Fault” LED will illuminate and the buzzer will sound.
The pressing of any key during the test period will abort the battery test and return the system back to normal
mode.
•
NOTE: The batteries are also monitored for open or short circuit. If the batteries are open or short-
circuited for a period of 30 seconds the “Battery Fault” LED will illuminate and provide a common
fault. This automatic battery monitoring functions in quiescent mode and is therefore disabled if
there is an alarm present to avoid confusion.
AUTO TEST MODE
AUTO
TEST
This function will perform a fixed automatic test procedure to the panel. This mode cannot be selected if any
zone(s) is in alarm.
Auto test will perform the following test functions;
Turn on ALL LEDs for 0.5 seconds
•
Test LCD Backlight
•
Test E
2
ROM
•
Test RAM
•
Test LCD
•
Isolate all alarm zones
•
Fault test all alarm zones
•
Alarm test all alarm zones
•
Test buzzer
TEXT The pressing of any key during "AUTO TEST" will abort the tests and return the system back to normal
mode once the current test is complete.
Note: During "AUTO TEST", all zones are treated as zone type #1 (standard latching type with 2 second
delay). Once AUTO TEST has finished, all zones will be reset and returned back to their previously
configured types.