Page 22
INERTIA-2464
Technical & Programming Manual
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
FAULT TEST
FAULT TEST
#
ENTER
The fault test function momentarily disconnects the detection zone(s) under test and simulates the worst case
condition for fault.
A resistor load equal to worst case fault is placed on the zone continuously for 5 seconds then the zone is
returned back to it's normal condition.
If several zones are being tested consecutively and are being entered at a rate faster than the 5-second fault
timer, the fault timeout will occur 5 second after the last entry was completed.
Once the zone has registered a fault, all outputs relating to that zone are initiated similar to a real fault.
The zone may be isolated prior to fault test if desired. This will prevent any outputs from operating.
The character "#" in the keystroke requires any one of the following entries;
1,2,3,4........, 63,64 or "ALL"
If only one zone is to be tested, use the appropriate zone number. Alternatively the "ALL" button can be used
to simultaneously test all zones.
To perform a fault test on a particular zone or on all zones;
1.
Press the "FAULT TEST" button once.
2.
The buzzer will give 2 short beeps to indicate that fault test mode has been entered.
3.
LCD display will read "FAULT TEST MODE, ENTER ZONE No.".
4.
Enter the zone number ("#").
5.
Please "ENTER".
A long beep will signify an incorrect entry and the panel will revert back to normal operating mode. The
"FAULT TEST" button will need to be pressed again to re-enter fault test mode.
If a correct entry is made, fault testing on the zone commences and the fault LED will illuminate.