INERTIA-2464
Technical & Programming Manual
Page 27
Copyright (c) 1996,
INERTIA FIRE SYSTEMS
PROGRAMMABLE OPTIONS
GLOBAL
ANCILLARY TRIP
1
LATCHING
NORMALLY DE-ENERGISED
2
NON-LATCHING
NORMALLY DE-ENERGISED
3
LATCHING
NORMALLY ENERGISED
4
NON-LATCHING
NORMALLY ENERGISED
ALARM VERIFICATION
1
DISABLED
2
2 MINUTES
3
3 MINUTES
4
4 MINUTES
5
5 MINUTES
TIME
(DD) / (MM) / (YY)
(HH) : (MM)
ZONES
DESCRIPTION
INPUT DELAY
1
Standard Latching
2 seconds
2
Standard Latching
2 seconds with AVF
3
Non Latching
2 seconds
4
Non Latching
20 seconds
5
Time Delay
10 seconds
6
Time Delay
20 seconds
7
Time Delay
30 seconds
8
Time Delay
40 seconds
9
Time Delay
50 seconds
10
Time Delay
60 seconds
Type Output Description
1
Indicate Only
2
Indicate, Bell
3
Indicate, Bell, General Alarm
4
Indicate, Bell, General Alarm, Ancillary
5
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1
6
Indicate, Bell, General Alarm, Ancillary Brigade Relay #2
7
Indicate, Bell, General Alarm, Ancillary, Brigade Relay #1, & Brigade Relay #2