Multi
Serial
Interface
for
NOTIFIER
AM
Series
Control
Panels
MOD-PRT-M
CEIA660
FEATURES
Multi
‐
address
interface
for
NOTIFIER
AM
Series
control
panels
(fire
and
gas);
provides
a
serial
output
with
7
wires
for
printer
and
four
serial
output
with
3
wires
CEI
‐
ABI/MODBUS
suitable
for
supervision
system
connection,
as
NotiNet
2000
and
EuroNet.
Printer
output
performs
3
printing
modes:
on
‐
line
log
system
INSTALLATION
MOD
‐
PRT
‐
M
interface
is
designed
and
realized
to
be
installed
inside
AM
Series
control
panels
or
nearby
(max.
length
of
serial
cables
=
15mt).
Remove
power
supply
before
proceeding
with
electrical
connection.
FUNCTIONING
MOD
‐
PRT
‐
M
interface,
after
AM
Series
contorl
panel
serial
connection,
acquires
data
through
an
alignment.
During
this
alignment
the
LED
flahses
according
to
cycle
2
seconds
off,
0.1
seconds
on
(green
light);
the
and
serial
CHANNELs
A,
B,
C
and
D
are
blocked.
New
programming
carried
out
on
AM
control
panel,
if
any,
automatically
will
set
a
new
alignment.
Once
the
alignment
is
completed,
the
interface
starts
saving
events
into
non
volatile
memory
–
the
memory
capacity
is
4096
events.
MOD
‐
PRT
‐
M
interface
saves
for
each
serial
CHANNEL
(printer,
serial
A,
B,
C,
D)
the
ID
of
the
last
sent
event
and
in
case
of
communication
stop
it
restarts
from
the
point
of
interruption.
To
eliminate
the
spooled
events
for
all
the
CHANNELs,
push
RST
button
for
more
than
5
seconds,
the
LED
L1
is
switched
off
for
2
seconds
and
then
it
becomes
green
lighted.
COMMUNICATION
INTERRUPTION
WITH
AM
CONTROL
PANEL
The
communication
interruption
with
AM
Series
control
panel
is
notified
by
quick
flashing
green
LED.
Every
communication
interruption
will
start
a
new
MOD
‐
PRT
‐
M
alignment.
ON
‐
LINE
On
‐
line
is
a
pre
‐
set
mode
of
functioning
(fixed
green
LED).
The
saved
events
are
sent
to
the
printer,
starting
from
last
printed
event,
as
soon
as
the
printer
CHANNEL
is
connected.
LOG
This
function
mode
allows
printing
the
last
1000
events
saved
into
MOD
‐
PRT
‐
M.
To
carry
out
the
log
print,
push
RST
button
(with
LED
L1
fixed
green
lighted
or
quick
flashing)
for
more
than
2
seconds
until
the
LED
L1
turns
into
fixed
red
lighted,
then
release
the
button
and
push
it
again
for
less
than
2
seconds;
the
LED
L1
turns
into
quick
red
flashing
and
the
starts.
SYSTEM
This
function
mode
allows
printing
the
list
of
sensors
(with
related
chamber
value
in
%),
input
and
output
modules.
To
carry
out
the
system
print,
push
RST
button
(with
LED
L1
fixed
green
lighted)
for
more
than
2
seconds
until
the
LED
L1
turns
into
fixed
red
lighted,
then
release
the
button
and
push
it
again
for
more
than
2
seconds
until
the
LED
L1
turns
into
slow
yellow
flashing;
once
the
alignment
is
completed
the
LED
turns
into
quick
yellow
flashing
and
the
starts
INTERRUPTION
To
interrupt
the
log
or
system
and
return
to
on
‐
line
mode,
push
RST
button,
the
LED
L1
turns
into
fixed
greed.
When
the
LED
is
fixed
red
or
yellow
and
the
will
not
start
within
10
seconds,
MOD
‐
PRT
‐
M
interface
will
automatically
return
to
on
‐
line
mode
and
the
LED
is
fixed
green.
CHANNELS
A,
B,
C,
D
The
serial
CHANNELs
are
transparent.
For
each
CHANNEL
it
is
possible
to
select
communication
protocol
CEI
‐
ABI
or
MODBUS
and
the
connection
in
232
or
485.
During
MOD
‐
PRT
‐
M
or
CHANNELs
alignment
every
command
is
ignored.
The
CHANNELs
can
carry
out
the
alignment
simultaneously.
For
any
CHANNEL,
after
the
related
alignment,
only
new
event
will
be
sent.
During
the
alignment
the
LEDs
flash
according
to
cycle
2
seconds
off,
on,
off,
on
as
quick
sequence:
Green
for
CHANNELs
A
‐
C
Red
for
CHANNELs
B
‐
D
Yellow
for
CHANNELs
A+B
–
C+D
TECHNICAL
DATA
Power
9
‐
30
Vcc
Max.
Current
at
12V
325
mA
Max.
Current
at
24V
175
mA
Temperature
range
‐
10
+50
°C
Dimensions
170X150X30
mm