background image

Multi

 

Serial

 

Interface

 

for

 

NOTIFIER

 

AM

 

Series

 

Control

 

Panels

 

MOD-PRT-M  

CEIA660

 

 

 

FEATURES

 

Multi

address

 

interface

 

for

 

NOTIFIER

 

AM

 

Series

 

control

 

panels

 

(fire

 

and

 

gas);

 

provides

 

a

 

serial

 

output

 

with

  

7

 

wires

 

for

 

printer

 

and

 

four

 

serial

 

output

 

with

 

3

 

wires

 

CEI

ABI/MODBUS

 

suitable

 

for

 

supervision

 

system

 

connection,

 

as

 

NotiNet

 

2000

 

and

 

EuroNet.

 

Printer

 

output

 

performs

 

3

 

printing

 

modes:

 

 

on

line

 

 

log

 

 

system

 

INSTALLATION

 

MOD

PRT

M

 

interface

 

is

 

designed

 

and

 

realized

 

to

 

be

 

installed

 

inside

 

AM

 

Series

 

control

 

panels

 

or

 

nearby

 

(max.

 

length

 

of

 

serial

 

cables

 

=

 

15mt).

 

Remove

 

power

 

supply

 

before

 

proceeding

 

with

 

electrical

 

connection.

 

FUNCTIONING

 

MOD

PRT

M

 

interface,

 

after

 

AM

 

Series

 

contorl

 

panel

 

serial

 

connection,

 

acquires

 

data

 

through

 

an

 

alignment.

 

During

 

this

 

alignment

 

the

 

LED

 

flahses

 

according

 

to

 

cycle

 

2

 

seconds

 

off,

 

0.1

 

seconds

 

on

 

(green

 

light);

 

the

 

print

 

and

 

serial

 

CHANNELs

 

A,

 

B,

 

C

 

and

 

D

 

are

 

blocked.

 

New

 

programming

 

carried

 

out

 

on

 

AM

 

control

 

panel,

 

if

 

any,

 

automatically

 

will

 

set

 

a

 

new

 

alignment.

 

Once

 

the

 

alignment

 

is

 

completed,

 

the

 

interface

 

starts

 

saving

 

events

 

into

 

non

 

volatile

 

memory

 

 

the

 

memory

 

capacity

 

is

 

4096

 

events.

 

MOD

PRT

M

 

interface

 

saves

 

for

 

each

 

serial

 

CHANNEL

 

(printer,

 

serial

 

A,

 

B,

 

C,

 

D)

 

the

 

ID

 

of

 

the

 

last

 

sent

 

event

 

and

 

in

 

case

 

of

 

communication

 

stop

 

it

 

restarts

 

from

 

the

 

point

 

of

 

interruption.

 

To

 

eliminate

 

the

 

spooled

 

events

 

for

 

all

 

the

 

CHANNELs,

 

push

 

RST

 

button

 

for

 

more

 

than

 

5

 

seconds,

 

the

 

LED

 

L1

 

is

 

switched

 

off

 

for

 

2

 

seconds

 

and

 

then

 

it

 

becomes

 

green

 

lighted.

 

 

COMMUNICATION

 

INTERRUPTION

 

WITH

 

AM

 

CONTROL

 

PANEL

 

The

 

communication

 

interruption

 

with

 

AM

 

Series

 

control

 

panel

 

is

 

notified

 

by

 

quick

 

flashing

 

green

 

LED.

 

Every

 

communication

 

interruption

 

will

 

start

 

a

 

new

 

MOD

PRT

M

 

alignment.

 

 

ON

LINE

 

PRINT

 

On

line

 

print

 

is

 

a

 

pre

set

 

mode

 

of

 

functioning

 

(fixed

 

green

 

LED).

 

The

 

saved

 

events

 

are

 

sent

 

to

 

the

 

printer,

 

starting

 

from

 

last

 

printed

 

event,

 

as

 

soon

 

as

 

the

 

printer

 

CHANNEL

 

is

 

connected.

 

 

 

 

 

LOG

 

PRINT

 

This

 

function

 

mode

 

allows

 

printing

 

the

 

last

 

1000

 

events

 

saved

 

into

 

MOD

PRT

M.

 

To

 

carry

 

out

 

the

 

log

 

print,

 

push

 

RST

 

button

 

(with

 

LED

 

L1

 

fixed

 

green

 

lighted

 

or

 

quick

 

flashing)

 

for

 

more

 

than

 

2

 

seconds

 

until

 

the

 

LED

 

L1

 

turns

 

into

 

fixed

 

red

 

lighted,

 

then

 

release

 

the

 

button

 

and

 

push

 

it

 

again

 

for

 

less

 

than

 

2

 

seconds;

 

the

 

LED

 

L1

 

turns

 

into

 

quick

 

red

 

flashing

 

and

 

the

 

print

 

starts.

 

SYSTEM

 

PRINT

 

This

 

function

 

mode

 

allows

 

printing

 

the

 

list

 

of

 

sensors

 

(with

 

related

 

chamber

 

value

 

in

 

%),

 

input

 

and

 

output

 

modules.

  

To

 

carry

 

out

 

the

 

system

 

print,

 

push

 

RST

 

button

 

(with

 

LED

 

L1

 

fixed

 

green

 

lighted)

 

for

 

more

 

than

 

2

 

seconds

 

until

 

the

 

LED

 

L1

 

turns

 

into

 

fixed

 

red

 

lighted,

 

then

 

release

 

the

 

button

 

and

 

push

 

it

 

again

 

for

 

more

 

than

 

2

 

seconds

 

until

 

the

 

LED

 

L1

 

turns

 

into

 

slow

 

yellow

 

flashing;

 

once

 

the

 

alignment

 

is

 

completed

 

the

 

LED

 

turns

 

into

 

quick

 

yellow

 

flashing

 

and

 

the

 

print

 

starts

 

PRINT

 

INTERRUPTION

 

To

 

interrupt

 

the

 

log

 

or

 

system

 

print

 

and

 

return

 

to

 

on

line

 

mode,

 

push

 

RST

 

button,

 

the

 

LED

 

L1

 

turns

 

into

 

fixed

 

greed.

 

When

 

the

 

LED

 

is

 

fixed

 

red

 

or

 

yellow

 

and

 

the

 

print

 

will

 

not

 

start

 

within

 

10

 

seconds,

 

MOD

PRT

M

 

interface

 

will

 

automatically

 

return

 

to

 

on

line

 

mode

 

and

 

the

 

LED

 

is

 

fixed

 

green.

 

CHANNELS

 

A,

 

B,

 

C,

 

D

 

The

 

serial

 

CHANNELs

 

are

 

transparent.

 

For

 

each

 

CHANNEL

 

it

 

is

 

possible

 

to

 

select

 

communication

 

protocol

 

CEI

ABI

 

or

 

MODBUS

 

and

 

the

 

connection

 

in

 

232

 

or

 

485.

 

During

 

MOD

PRT

M

 

or

 

CHANNELs

 

alignment

 

every

 

command

 

is

 

ignored.

 

The

 

CHANNELs

 

can

 

carry

 

out

 

the

 

alignment

 

simultaneously.

 

For

 

any

 

CHANNEL,

 

after

 

the

 

related

 

alignment,

 

only

 

new

 

event

 

will

 

be

 

sent.

 

During

 

the

 

alignment

 

the

 

LEDs

 

flash

 

according

 

to

 

cycle

 

2

 

seconds

 

off,

 

on,

 

off,

 

on

 

as

 

quick

 

sequence:

 

Green

 

for

 

CHANNELs

 

A

 ‐ 

C

 

Red

 

for

 

CHANNELs

 

B

 ‐ 

D

 

Yellow

 

for

 

CHANNELs

 

A+B

 

 

C+D

 

TECHNICAL

 

DATA

 

Power

9

30

 

Vcc

Max.

 

Current

 

at

  

12V

325

 

mA

Max.

 

Current

 

at

  

24V

175

 

mA

Temperature

 

range

10

 

+50

 

°C

Dimensions

170X150X30

mm

 

Reviews: