NBG-12LO/-12LOB Manual Pull Station

(Listed for Outdoor Applications)

Document 51303   Revision A1   ECN: 01-293   10/15/01

Description

The NBG-12LOB Pull Station is a non-coded manual pull station

which provides a Fire Alarm Control Panel (FACP) with a single

alarm initiating input signal.  The pull station is a dual action

model equipped with a key lock reset, an approved outdoor

gasket, and an accompanying outdoor backbox.  It is UL listed

and meets the ADA requirement of a 5-lb. maximum pull down

force to activate.  Operating instructions are molded into the

handle.  Molded terminal numbers can also be found adjacent

to the wiring terminals.

Door ‘keys’ into

backplate at this point

12LAdoormount.wmf

1. Position the door and backplate side

by side in the full open position.  (i.e.

180-degrees  with  respect  to  each

other.)

2. With  the  backplate  position  fixed,

move the door behind the backplate,

as shown in the illustration, part A.

3. Align the hinge posts and holes by

bringing  the  door  up  to  meet  the

backplate,  paying particular attention

to the ‘keying’ that occurs when the

door’s  post  hole  is  aligned  to  the

backplate’s hinge post.  Refer to the

illustration, part B.

4. With  the  two  pieces  aligned  and

‘keyed’  together,  slide  the  holes

down onto the posts.  Refer to the

illustration, part C.

5. Holding the backplate, close the door

slightly to lock the door and backplate

together.

NBG-12LOB

The features of the pull station include Dual-Action operation,

Key-Lock Reset function, Screw Terminal Wire connections,

outdoor-use gasket, an outdoor approved 4-inch backbox, and a

sealed switch with gold-plated contacts.
Note:  The NBG-12LOB is applicable with the WP-10 backbox

in retrofit applications.  To meet UL requirements for outdoor

use, the NBG-12LO Pull Station must be mounted to the WBB

or WP-10 Backbox to create the NBG-12LOB model.

Switch Contact Rating

FACP Circuit (Terminals 1 & 2):

Rated to .25 Amp at 30 Volts (AC or DC).

Door Attachment and Reattachment
If the door becomes detached,

 complete the following steps to

reattach the door to the backplate.  The door cannot be connected

to the pull station if the unit is mounted to a backbox.

Dual Action NBG-12LOB

With the door and backplate

aligned and ‘keyed’ together,

slide the holes down onto the

posts.

Closing the door slightly

locks  the  door  and

backplate together.

Door mated to Backplate

at this stage.

      Post

 Hole

Post

      Hole

Post

UL

Product ID

Label

UL

Product ID

Label

N

B

G

12LO

B

Fa

ce3.

wm

f