Document 51303 Revision A1 ECN 01-293 10/15/01
Wiring Instructions
1) Surface mount the supplied Weatherproof Backbox (WBB)
using the side flanges incorporated into the backbox design.
The box can be positioned to allow conduit connection from
any side. The pull station will mount in any position desired.
2) Before mounting the pull station, pull all necessary wiring
through the backbox.
3) Remove the correct amount of wire insulation. The pull
stations backplate is molded with a strip gauge to measure
the amount of insulation to be removed.
4) Connect the wiring from the fire alarm control panels
Initiating Device Circuit (IDC), or any previous device on
the IDC to terminals 1 and 2 located on the pull stations
terminal strip. Connect the next device on the IDC or End-
of-Line Resistor (ELR) to terminals 1 and 2. Note: Maintain
consistent polarity with all connections throughout the IDC.
CAUTION
Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical
codes and the requirements of the Authority Having Jurisdiction (AHJ). Conduct regular testing of the devices using appropriate
NFPA standards. Notifier is not responsible for devices that have not been properly installed, tested or maintained. For ADA
compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is 48 inches
(121.92cm). If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height allowed is
54 inches (137.16cm).
12l
obwi
ring.
wm
f
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234
1234567
1234567
1234567
From FACP
IDC
To Next Device
IDC
Outdoor-Use Gasket
(Does not cover any
user-serviced connections)
12
12
12
Outdoor Stations
Install the NBG-12LO with a listed, outdoor-approved backbox
(WBB or WP-10) to meet UL requirements for outdoor use.
Without one of these backboxes, the NBG-12LO is not listed
for outdoor applications. Use the four supplied 8-32 x .375"
mounting screws to attach the Pull Station to the outdoor-
approved backbox.
Operation
To activate the dual-action station, first push in the handle, and
then pull the handle down. The handle locks into the activated
position. The word ACTIVATED appears after the handle is
pulled down. The pull station remains in the activated position
until reset with the key lock.
1) Reset the NBG-12LOB by
inserting the key into the
lock and turning it ¼ turn
(counter-clockwise).
2) Open the door until the
handle returns to the
NORMAL position.
3) Close and lock the door.
Closing the door auto-
matically resets the switch
to the NORMAL posi-
tion. Note: Opening the
pull station door will not
activate or deactivate the
FACP alarm switch.
NBG-12LO + WBB
= NBG-12LOB
12LO
B
m
ount
.w
m
f
N
B
G
12LO
B
-A
ct
ive
NBG-12LOB
Pull Station
(Shown Activated)