Document 51303 Revision A1    ECN 01-293    10/15/01

Wiring Instructions

1) Surface mount the supplied Weatherproof Backbox (WBB)

using the side flanges incorporated into the backbox design.

The box can be positioned to allow conduit connection from

any side.  The pull station will mount in any position desired.

2) Before mounting the pull station, pull all necessary wiring

through the backbox.

3) Remove the correct amount of wire insulation.  The pull

station’s backplate is molded with a strip gauge to measure

the amount of insulation to be removed.

4) Connect  the  wiring  from  the  fire  alarm  control  panel’s

Initiating Device Circuit (IDC), or any previous device on

the IDC to terminals 1 and 2 located on the pull station’s

terminal strip.  Connect the next device on the IDC or End-

of-Line Resistor (ELR) to terminals 1 and 2.  Note:  Maintain

consistent polarity with all connections throughout the IDC.

CAUTION

Install the pull station in accordance with the supplied instructions, applicable NFPA standards, national and local Fire and Electrical

codes and the requirements of the Authority Having Jurisdiction (AHJ).  Conduct regular testing of the devices using appropriate

NFPA standards.  Notifier is not responsible for devices that have not been properly installed, tested or maintained.  For ADA

compliance, if the clear floor space only allows forward approach to an object, the maximum forward reach height allowed is 48 inches

(121.92cm).  If the clear floor space allows parallel approach by a person in a wheelchair, the maximum side reach height allowed is

54 inches (137.16cm).

12l

obwi

ring.

wm

f

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234

1234567

1234567

1234567

From FACP

IDC

To Next Device
IDC

Outdoor-Use Gasket

(Does not cover any

user-serviced connections)

12

12

12

Outdoor Stations

Install the NBG-12LO with a listed, outdoor-approved backbox

(WBB or WP-10) to meet UL requirements for outdoor use.

Without one of these backboxes, the NBG-12LO is not listed

for outdoor applications.  Use the four supplied 8-32 x .375"

mounting  screws  to  attach  the  Pull  Station  to  the  outdoor-

approved backbox.

Operation

To activate the dual-action station, first push in the handle, and

then pull the handle down.  The handle locks into the activated

position.  The word ‘ACTIVATED’ appears after the handle is

pulled down.  The pull station remains in the activated position

until reset with the key lock.
1) Reset the NBG-12LOB by

inserting the key into the

lock and turning it ¼ turn

(counter-clockwise).

2) Open  the  door  until  the

handle  returns  to  the

‘NORMAL’ position.

3) Close and lock the door.

Closing  the  door  auto-

matically resets the switch

to  the  ‘NORMAL’  posi-

tion.  Note: Opening the

pull station door will not

activate or deactivate the

FACP alarm switch.

NBG-12LO + WBB

=  NBG-12LOB

12LO

B

m

ount

.w

m

f

N

B

G

12LO

B

-A

ct

ive

NBG-12LOB

Pull Station

(Shown Activated)