LED OPERATION
Alarm:
Steady RED
Normal CLIP Systems:
Flash RED
Normal FlashScan
TM
:
Flash GREEN
Note: LED is visible
through translucent
handle.
Setting the NBG-12LX Address
The NBG-12LX Addressable pull station is factory preset with
address 00. Set the address for the pull station by turning the
rotary address switches on the addressable module mounted inside
the pull station. Only one device per address is allowed. Multiple
modules may not be set to the same address on the Signaling Line
Circuit. Once the address is set, record it in the space provided on
the product ID label located inside the pull station.
NBG-12LX Addressable Pull Station
Description
The NBG-12LX Addressable pull station is a non-coded, dual-
action manual pull station with a key-lock reset feature. It
provides NOTIFIER intelligent control panels with one addres-
sable alarm initiating input. The addressable module is housed
inside the pull station. The NBG-12LX is compatible with all
Notifier intelligent panels and will automatically operate in either
FlashScan or CLIP (Classic Loop Interface Protocol) mode.
FlashScan is a patented (U.S. Pat. No. 5,539,389) High Speed
Communications Protocol. Refer to the FACP Installation
Manual to determine if FlashScan protocol is supported.
FlashScan or CLIP operating mode must be selected in the
FACP. (This selection is not available or required in FACPs that
do not support FlashScan, therefore CLIP mode is enabled
by default.) No selection is required in the Pull Station. The
NBG-12LX meets the ADA requirement for a 5-lb. maximum
pull force to activate the pull station. Operating instructions are
molded into the pull station handle along with Braille text.
Molded Terminal numbers are also present.
Ratings
Normal Operating Voltage: 24 VDC.
Average Operating Current (LED Flash): 300 µA.
Temperature Range: 32o F - 120o F (0o C - 49o C).
Relative Humidity Range: 10% - 93% non-condensing.
Document 51093 Revision A2 ECN: 01-293 09/14/01
Installation
The NBG-12LX Addressable pull station can be surface mounted
to a NOTIFIER SB-10 surface backbox or semi-flush mounted
on a standard single-gang, double-gang or 4 (10.16 cm) square
electrical box. The optional BG-TR trim ring can be used if the
NBG-12LX is to be semi-flush mounted.
Software Note for AM2020/AFP1010 Programming
The NBG-12LX is an Alarm Initiating Module of software type
mpul. If you have an older system that does not support the mpul
software type, the software type mon may be used.
If, during mounting of the pull station, the door becomes de-
tached
, complete the following steps to reattach the door to the
backplate. The door cannot be connected to the pull station if the
unit is mounted to the backbox.
1) Position the door and backplate side by side in the full open
position. (i.e. 180-degrees with respect to each other.)
2) With the backplate position fixed, move the door behind the
backplate, as shown in the illustration, part A.
3) Align the hinge posts and holes by bringing the door up to
meet the backplate, paying particular attention to the keying
that occurs when the doors post hole is aligned to the
backplates hinge post. Refer to the illustration, part B.
4) With the two pieces aligned and keyed together, slide the holes
down onto the posts. Refer to the illustration, part C.
5) Holding the backplate, close the door slightly to lock the door
and backplate together.
To use the NBG-12LX
with panels capable of
supporting up to 159
addresses, pry off the
break-away address
block using a flat-
bladed screwdriver.
The break-away piece
is illustrated below.
ROTARY ADDRESS SWITCHES
LED
LOOP
N O T I F I E R
NBG - 12 Series
NON-C ODED
FIRE ALARM BOX
LISTED
23424
REFER TO DOC UMENT
Made in
U. S. A.
M
AD DRESS
L
U
PRODUCT IDENTIFICATION LABEL
ro
t s
w
itc
h
9-
13
.c
dr
, l
ab
el
_1
.cd
r,
ro
ta
ry
b
ox.c
dr
N
B
G
12-F
ac
e2
.cd
r
www.PDF-Zoo.com
firealarmresources.com