SFP-400B Control Panel containing the main control board, cabinet (backbox and door), main supply transformer
and power supply.
Batteries (refer to Appendix A for Standby Power Requirements).
Initiating Devices - connected to one of the control panel's Initiating Device Circuits.
Notification Appliances - connected to one of the control panel's Notification Appliance Circuits.
The following additional equipment is needed for compliance with the NFPA standards listed below:
NFPA 72-1993 Signaling Systems for Central Station Service (Protected Premises Unit)
NOTI-FIRE 911A/911AC DACT - for connection to a compatible listed Central Station DACR or Protected
Premises Receiving Unit. This unit must be installed as outlined in Figure B-3A/B.
NFPA 72-1993 Auxiliary Protective Signaling System
4XTM Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit must be
installed as outlined in Figure B-1.
NFPA 72-1993 Remote Station Protective Signaling System
4XTM Transmitter Module for connection to the Fire•Lite RS82-9 Remote Station Receiver. See Figure
B-2 for installation instructions for this unit
OR
NOTI-FIRE 911A/911AC DACT - For connection to a compatible listed remote station DACR. This unit must be
installed as outlined in Figure B-3A/B.
NFPA 72-1993 Proprietary Protective Signaling System
Potter EFT-C McCulloh Transmitter. See Figure B-4 for installation instructions for this unit .
Appendix B: NFPA Standard-Specific Requirements
The Notifier SFP-400B has been designed for use in commercial, industrial, and institutional applications and meets
the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this
appendix. The minimum system components required for compliance with the appropriate NFPA standard are
listed below.