background image

~ 5 ~ 

NOVATEK-ELECTRO

                                                                                                                                                         

PH-260t

 



Maximal voltage threshold  from 230 to 280 V 





AR time by voltage 

from 1 to 900 s 





Displayed parameter by 
default 

«



» – total power;          «



» – consumed current; 

«



» – active power;       «



» – mains voltage. 

«



» – reactive power; 





Parameter indication 
mode 

«



» – parameter value is displayed continuously; 

«



»  –  parameter  value  is  displayed  for  15  seconds  (then  a 

default parameter will be displayed); 
«



» – a continuous cyclic parameter displaying. 





Password setting 

allowable values from 000 to 999 



 

3 THE INTENDED USE 
3.1 Preparation for operation 
3.1.1

 Preparation for connection: 

  unpack  and  check  the  device  for  damage  absence  after  transportation;  in  case  of  such  damages 

detection, contact the supplier or the manufacturer; 

   carefully study the Operation Manual; 

  If  you  have  any  questions  regarding  the  installation  of  the  device,  please  contact  the  manufacturer  by 

telephone number indicated at the end of this Operating Manual. 

 

3.1.2

 

Connection

 

  

 

ATTENTION! ALL CONNECTIONS MUST BE PERFORMED WHEN THE DEVICE IS DE-ENERGIZED. 

 

Error when performing the installation works may damage the device and connected devices. 

 

To ensure reliability of electrical connections, flexible (multi-wire) conductors with voltage insulation for at least 

450  V  should  be  used.  The  wire  cross  section  for  connecting  protected  equipment  depends  on  the  load  current 
(power), and should be: for current of 40 A (9 kW) 

– at least 6 mm

2

; for current of 63 A (14 kW) - at least 10 mm

2

The ends of the wires must be stripped of insulation for 5 ± 0.5 mm and crimped with bushings. Fastening of the 
wires should exclude mechanical damage, twisting and abrasion of wire insulation. 

If necessary, it is allowed to use a wire with cross-section of 0.5 - 1 mm

2

 for connection of supply to the 

device (terminal 2, Fig. 1). 

 

IT IS NOT ALLOWED TO LEAVE EXPOSED PORTIONS OF WIRE PROTRUDING BEYOND THE TERMINAL 

BLOCK. 

 

For a reliable contact, tighten the terminal screws with the force indicated in Table 2. 

 

When reducing the tightening torque, the junction point is heated, the terminal block may be melted and wire can 

burn. If you increase the tightening torque, it is possible to have thread failure of the terminal block screws or the 
compression of the connected wire. 

 

 

 

QF 

–  a circuit breaker. 

 

Figure 2

 

– Device connection diagram 

Summary of Contents for PH-260t

Page 1: ...ith requirements ISO 9001 2015 Dear customer Company NOVATEK ELECTRO Ltd thanks you for purchasing our devices You will be able to use properly the device after carefully studying the Operating Manual...

Page 2: ...l Installations Installation adjustment and maintenance of the device must be performed by qualified personnel having studied this Operating Manual In compliance with the requirements of this Operatin...

Page 3: ...arameters to be measured and controlled Name Controlled range Measured range Total power kVA 1 14 0 14 Active power kW 1 14 0 14 Reactive power kVAr 1 14 0 14 Load current A 1 63 0 5 63 Input voltage...

Page 4: ...V 5 Rated mode of operation long Degree of device protection IP 10 Electric shock protection class II Climatic version NF 3 1 Permissible pollution II Overvoltage category II Wire cross section for co...

Page 5: ...installation works may damage the device and connected devices To ensure reliability of electrical connections flexible multi wire conductors with voltage insulation for at least 450 V should be used...

Page 6: ...ons or and choose it by pressing button The device will move to the state Setting of parameters items of the menu are described in Table 4 to change the value of the selected parameter by means of but...

Page 7: ...or if the voltage is higher than 285 V the device will go into the Fault state After the countdown of the re closure time by voltage the device will move to the Normal operation state if the mains vo...

Page 8: ...IF THE DEVICE HAS BEEN OPERATED WITH THE VIOLATION OF THE REQUIREMENTS OF THIS USER MANUAL THE USER WILL LOSE THE RIGHT TO WARRANTY MAINTENANCE 5 4 Warranty service is performed at the place of purcha...

Reviews: