background image

RNPP-301

2. DESCRIPTION

1

2

The RNPP-301 relay (hereafter “the relay”) is a digital microprocessor device that provides a high degree of 

reliability and accuracy. The relay doesn’t require any auxiliary power supply because it is self-powered by the 

three-phase voltage to be monitored. This permits the relay to keep operate capability even when only one 

phase is present (in the three-phase systems with neutral). Two modes of the mains voltage monitoring can 

be selected at the user’s option:

The line voltage monitoring mode

.

To go into this mode of operation one needs to apply the jumper strap between terminals 8-9; in this case to 

connect the neutral is not necessary. This mode of operation is recommended when the neutral drift value and 

phase voltage imbalance is not important as well as for isolated neutral three-phase systems. The relay will 

trip when line voltage imbalance between phases occurs.

Note

:To keep the relay operative and informative when only one phase is present it’s advisable to connect the 

neutral to the terminal 7 not removing the jumper strap between terminals 

8-9.

 In 3-Phase systems without 

neutral the relay keeps operational capability when at least two phases are present.

The relay is connected in parallel to load by the 

L1, L2, L3 

input contacts (the 

4, 5, 6

 terminals respectively). 

The  neutral  connection  mode

  (N,  the  7  terminal)

  corresponds  to  the  mains  voltage  monitoring  mode  of 

operation selected by user. The 

1, 2, 3

 terminals provide the MS power contacts status monitoring and are 

connected to the output MS power contacts terminals (see the wiring diagram). The relay has two groups of 

independent output contacts 

(10-11, 12-13)

. In the “dead status” of the relay (a voltage is not applied to the 

relay, the relay is not connected) the 

12-13

 are the 

N.O.

 contacts and the 

10-11

 are 

N.C.

 contacts. After the 

relay has been connected in parallel to load when voltage is present in the mains and there is no cause for the 

relay to trip, the 

12-13

 contacts are being closed and the 

10-11

 contacts are being opened with the user-set 

reset delay Ton.

It is recommended the 

12-13

 contacts to connect in series with the MS coil power supply.

When the relay tripped, load is de-energized due to the break in the MS coil power curcuit by the 

N. O. 12-13 

contacts

THE 10-11, 12-13 OUTPUT CONTACTS SPECIFICATION

Max. current for 

~ 250 V A. C.

Max. power

Max sustained 

safe voltage ~

Max. current for 

U = 30V D.C.

Cosφ = 0.4

3A

Cosφ = 1.0

5A

2000VA

460V

3V

One of the relay functions is the monitoring of the MS power contacts position before load energization and 

after load is energized. The monitoring is performed if the1, 2, 3 terminals are connected to the corresponding 

phases of the MS output contacts. The monitoring is performed as follows:

Before load is energized a test for open position of all three MS power contacts is performed. If at least 

• 

one contact is closed (“sticks”) the relay will be disabled, the load is not energized, all red “FAULT” LEDs 

are ON. To enable the relay one needs to remove supply voltage from it. It’s recommended to test the MS 

running order, following safety regulations. 

When load is energized, the test for closed position of all three MS power contacts is performed. If at least 

• 

one MS phase contact is open, the relay will trip to de-energize load and will be disabled. All red “FAULT” 

LEDs are ON. To enable the relay one needs to remove supply voltage from it. It’s recommended to test 

the MS running order, following safety regulations. 

MS POWER CONTACTS TRANSFER MONITORING

Summary of Contents for RNPP-301

Page 1: ...RNPP 301 Three phase voltage and phase monitoring relay NOVATEK ELECTRO LTD Research and Manufacturing Company www novatek electro in TECHNICAL DESCRIPTION AND USERS MANUAL...

Page 2: ...setting 1 adjustments for the minimum maximum voltage thresholds monitoring of the correct phase sequence and phase non coincidence the phases are supposed to be 2 coinciding when a load is energized...

Page 3: ...0 11 12 13 In the dead status of the relay a voltage is not applied to the relay the relay is not connected the 12 13 are the N O contacts and the 10 11 are N C contacts After the relay has been conne...

Page 4: ...m switched current of output contacts A 5 Output contacts life under load 5A operations under load 1A operations 100 000 1 mln Protection degree of apparatus terminal block IP40 IP20 Operating tempera...

Page 5: ...to the relay front panel Umin trip threshold for the minimum allowable voltage of rated voltage Umax trip threshold for the maximum allowable voltage of rated voltage PI phase line voltage imbalance...

Page 6: ...relay should be connected in parallel to load according to the diagrams shown below The RNPP 301 wiring diagram with selectable mode of operation For line voltage monitoring mode that is not necessari...

Page 7: ...nnect the relay output contacts the 10 11 12 13 terminals to the MS coil power circuit the control circuit 4 To connect the 1 2 3 terminals to the MS output contacts If there is no need in the MS powe...

Page 8: ...RNPP 301 NOVovatek LTD C 30 Patparganj Industrial Area 1st floor Delhi 110092 INDIA Email info novatek electro in Tel 91 11 42143253 Fax 91 11 43010600 www novatek electro in...

Reviews: