~ 15 ~
NOVATEK-ELECTRO
UBZ-304
Indications on UBZ
display before starting
the motor
Indicat
<Start
0
1
0
0
–
"LineU"
–
line voltage: "Line
U1", "Line U2", "Line U3";
1
–
"InsFr"
–
motor running time
("Time motor"), motor insulation
resistance ("Insulation"), mains
frequency ("Frequency").
212
Parameter display mode
Indicat
mode
0
1
0
0
–
"Conti"
–
the parameter value
is displayed continuously,
1
–
">15s"
–
the parameter value
is displayed for 15 s
213
Functional relay
operating mode
Relay F
mode
0
2
0
0
–
"Alarm"
–
relay is used as
alarm relay;
1
–
"Timer"
–
the relay is used as
time relay (it is enabled after
214
Table 3.6 (Continued)
Settings and readings
Parameter
on LCD
Min.
value
Max.
value
Factory
setting
Message on LCD, actions
Address
enabling the load relay after the time
set parameter of
“Relay F time”)
;
2
–
"St->D "
–
the relay is used for
motor star
–
delta switching (after
time of
“Relay F time” (
address -
215) the load relay is disabled, and
after time of
“Relay F time”
(address-
215) + “Delay RP RF”
(address-216) the functional relay is
enabled).
Timer value, s
Relay F
time
0
300
30
See it.2, it.3 of the parameter
“Relay F
mode“ (
address-214).
215
Star-delta mode.
Switching time, s
Delay RP
RF
0.1
2
0.4
The time between the load relay
disabling and functional relay
enabling in star-delta mode.
216
Total time of the unit
operation, day
Time UBZ
0
999
0
*When
data
transmitting
by
MODBUS/RS-232 interface the ope-
rating time is transmitted in hours.
217
Motor operating time,
day
Time motor
0
999
0
*When
data
transmitting
by
MODBUS/RS-232 interface the ope-
rating time is transmitted in hours
218
Access code of user
Users code
0
9
0
0
–
keyboard is unblocked;
1-9
–
user password.
219
Access code of
advanced user
Password
000
999
123
000
–
access to advanced user
level is permitted;
000-999
–
advanced user password
220
Factory settings
reactivating
Default
Factor
0
1
0
0
–
"Off",
1
–
"On"
After "On" message and the set-
tings setup mode quit, the factory
settings will be reactivated (except
the access code of advanced user)
221
The serial interface parameters (RS-485/ RS-232)
UBZ communication
address
Address
UBZ
1
247
1
222
Transfer rate
2
Data speed
0
1
0
0
–
"9.6 k"
–
9600 baud;
1
–
"19.2k"
–
19200 baud.