~ 16 ~
UBZ-304
NOVATEK-ELECTRO
Converter reaction to
loss of connection
Loss
connect
0
3
0
0
–
"non"
–
continuation without
warning;
1
–
"Alarm"
–
warning and
continuation of operation;
2
–
"StpAR"
–
warning and motor
stop
with
ARS
permit
after
restoring the connection;
3
–
"StpnA"
–
warning and motor
stop with ARS disabled after
restoring the connection.
224
Detection of response
overtime, s
Overexceed
ing
0
120
0
0
–
It is disabled.
225
Permit of UBZ
communication via
serial link
Communi-
cation
0
2
0
0
–
"Off "
–
communication is
disabled;
1
–
"RS232"
–
communication via
RS-232;
2
–
"RS485"
–
communication via
RS-485.
226
Type of communication
protocol2
ASCII- RTU
0
1
1
0
–
"ASCII";
1
–
"RTU"
–
MODBUS modes.
227
Parity check2
Even parity
0
1
0
0
–
"Off"
–
parity check is disabled;
1
–
"On"
–
parity check is enabled.
228
Number of stop bits2
Stop bit
1
2
2
229
Table 3.6 (Continued)
Settings and readings
Parameter
on LCD
Min.
value
Max.
value
Factory
setting
Message on LCD, actions
Address
Unit version
Version
9
The parameter value depends on
software version.
230
Indicator illumination
1
Indicator L
0
2
1
0
–
"Off"
–
illumination is off;
1
–
"On15s"
–
illumination is on for
15 s after pressing any buttons;
2
–
"On"
–
illumination is on
continuously.
231
Clock correction, s
Correct
Time
-10
10
0
Correction of the real time clock.
Compensation of time for the day.
232
Control via analog input 0-20 mA
Upper threshold, mA
Input I UP
0
20
10
233
Lower threshold, mA
Input I
DOWN
0
20
1
234
Control algorithm
Input I ALG
0
2
0
0
–
"Off"
–
control is off;
1
–
"OffUP"
–
the motor is off when
the current is higher than the
upper threshold and it is on when
the current is lower than the lower
threshold;
2
–
"OnUP"
–
the motor is on when
the current is higher than the
upper threshold and it is off when
the current is less than the lower
threshold.
235
Entry in faults logbook
Input I log
0
1
0
0
–
"OffWr"
–
motor cutoff is
considered the fault but not
recorded in the fault logbook;
1
–
"OnWr"
–
motor cutoff is
considered the fault and is
recorded in the fault logbook.
236
Control via analog input 0-10 V
Upper threshold, V
Input U UP
0
10
5
237
Lower threshold, V
Input U
DOWN
0
10
1
238