~ 22 ~
UBZ-304
NOVATEK-ELECTRO
2) circuits for measurement of temperature, current, voltage (1 - 9)
–
0.5 A;
3) RS-485 (10 - 12)
–
0.5 A.
1 - fastener;
2
–
UBZ;
3
–
rubber gasket;
Figure 5.1
- UBZ Installation
5.1.4 Unit Installation
5.1.4.1 UBZ is the unit of panel design version.
The panel design should meet the following requirements:
- the hole for UBZ installation is square-shaped of 91.5*91.5 mm (+0.5mm tolerance);
- the distance between UBZ panels (top, bottom and side) and the relevant surfaces of the panel should be at
least 10 mm;
- if it is assumed to have operational use of communication via RS-232, the distance between the top panel of
UBZ and the corresponding surface of the panel should be at least 30 mm.
5.1.4.2 Installation procedure:
- put the rubber gasket on UBZ (it.3 Fig.5.1);
- install UBZ into the panel hole;
- install the fasteners (it.1 Fig.5.1) on the lower and upper UBZ panels;
- secure UBZ in the panel with tightening screws of the fastener.