47
Specifications
Mechanical Specifications
FXM 1100/1500/2000
Dimensions, in (mm)
H x W x D
5.2 x 15.5 x 8.75
(133 x 394 x 222)
FXM 1100/1500/2000
Weight, lb (kg)
35 (15.9)
FXM 500
Dimensions, in (mm)
H x W x D
3.5 x 17 x 9
(89 x 432 x 229)
FXM 500 Weight, lb (kg)
25 (11.3)
Mounting
Shelf, rack or wall; horizontal
or vertical mount.
Humidity (operating)
Up to 95% (non-condensing)
Temperature Range, °C
Operating
Storage
(Notes 1, 2)
-40 to 55
-40 to 75
Altitude
Operating (Note 3)
Storage
Up to 12,000 ft. (3658 m)
Up to 15,000 ft. (4572 m)
AC Input and Output
Connectors
Terminal block
(maximum 10 AWG)
Dry Contact Connectors
Terminal block
(maximum 16 AWG)
RS-232 Connector
DE-9, female
Ethernet Connector
Optional, factory installed
RJ-45
Dry Contacts
6 sets of single-pole, double-
throw relays located on the
front panel. They are rated
at 250VAC, 1A. The factory
default settings are:
C1:
On Battery
C2, C3:
Low Battery
C4:
Timer
C5:
Alarm
C6:
48VDC for an external
fan. It can be factory
configured as a dry
contact.
User Inputs
Three optically-isolated inputs
are located on the front panel.
When they are shorted, their
functions are:
S1:
Starts the Self test
S2:
Activates an alarm
S3:
Unit shutdown
User Input
(Note 4)
2 x 20 backlit alpha-numeric
LCD screen. Three control
buttons located below.
Electrical Specifications
Input
Voltage (nominal, VAC)
120 or 230 (optional 220)
Frequency, Hz ±5%
60/50 (autofrequency)
Current, A
(@ nominal Vin and 6A
battery charger
)
–500W:
7.5/3.8 @120/230VAC
–1100W:
12.6/6.5 @120/230VAC
–1500W:
16/8.4 @120/230VAC
–2000W:
20.5/10.7 @120/230VAC
Output
Voltage (nominal, VAC)
120 or 230 (optional 220)
Frequency, Hz ±5%
60/50 (autofrequency)
Current, A
–500W:
4.2/2.2 @120/230VAC
–1100W:
9.4/4.8 @120/230VAC
–1500W:
12.5/6.5 @120/230VAC
–2000W:
16.7/8.7 @120/230VAC
AC Input and Output
Connectors
Terminal block
(maximum 10 AWG)
Power, W/VA
500/1100/1500/2000
Waveform
Sinewave
Load Crest Factor
3:1 (load dependant)
Output Voltage Distortion
< 3% THD (resistive load)
Efficiency (typical)
Normal Mode
Backup Mode
>98%
>84%
Transfer Time (mS)
AVR to Backup
Backup to AVR
5 (Typical)
3 (Typical)
Line Qualification Time
3 seconds (factory default),
user adjustable to 3, 10, 20,
30, 40, or 50 seconds.
Battery String Voltage
48VDC
24VDC (FXM 500 only)
Battery Charger Current
6A (factory default), user
adjustable to 3, 6 or 10 A.
Battery Charger
Temperature
Compensation
-5mV/°C/Cell (factory default),
user adjustable to -2.2, -4, -5
or -6mV/°C/Cell.
Due to ongoing product improvements, specifications are subject to change without notice