Dimensions

: 60 x 70 x 35 mm 

 

PACKAGE CONTENTS 

Besides  this  manual,  the  user  must  check  if  the  items  below 
accompany the product. 

 

The electronic logger 

LogBox-AA

 

The  LogChart-II  software  installation  disk.  The  disk includes  the 
USB. 

 

Two cables for sensor wiring (IP67 model only). 

WARRANTY 

Warranty  conditions  are  available  on  our  web  site 

www.novusautomation.com/warranty

Summary of Contents for LogBox-AA-32k-IP67

Page 1: ...ccording to user defined settings Note Besides configuration performed through the software the definition of input signal requires two internal jumpers to be configured DATA ACQUISITION LOGGING Data can be acquired through different modes The logger can be configured to perform a single measurement within a time interval storing the value read or perform ten measurements within the time interval ...

Page 2: ...e entered The user can also obtain general information about the device The fields of the configuration window are described below Fig 6 Configuration window GENERAL INFORMATION FIELD General information on the top of the screen informs the model serial number logger current date time PC date time firmware version logger model version memory capacity and used memory This information is displayed i...

Page 3: ...iggering situation has ceased LOW defines the minimum value under which the alarm is triggered HIGH defines the maximum value above which the alarm sensor is triggered After filling all the fields send the configuration to the logger by clicking on the button New settings and PC current date time are then sent to the logger ELECTRICAL CONNECTIONS Only the input connections and the External Battery...

Page 4: ...STALLATION RECOMMENDATIONS Signal wires should be installed in grounded conduits and away from power or contactor wires Instruments must be powered only by an exclusive power supply System failure should always be taken into account when designing a control panel to avoid irreversible damage to equipment or people Installing RC filters 47 R and 100 nF serial is strongly recommended at contactor co...

Page 5: ...ned are displayed in engineering units in a table format The table displays register number date time and the record values Fig 15 Screenshot showing the acquisitions table VISUALIZING THE DATA Three windows support data visualization Graph Acquisitions Table and General Information windows Data can be originated from direct reading from the logger or from a file previously recorded in a computer ...

Page 6: ...NAL INFORMATION If you have any doubt concerning this or other NOVUS products e mail us at info novusautomation com or visit our home page www novusautomation com SPECIFICATIONS Inputs Thermocouples according to the NBR 12771 99 standard Pt100 RTD s NBR 13773 97 TYPE CHARACTERISTICS J Range 50 to 760 C 58 to 1400 ºF K Range 90 to 1370 C 130 to 2498 ºF T Range 100 to 400 C 148 to 752 ºF N Range 90 ...

Page 7: ...nual the user must check if the items below accompany the product The electronic logger LogBox AA The LogChart II software installation disk The disk includes the USB Two cables for sensor wiring IP67 model only WARRANTY Warranty conditions are available on our web site www novusautomation com warranty ...