NOVUS AUTOMATION
25/53
44
FIRST_MONTH
Month of first log.
45
FIRST_DAY
Day of first log.
46
FIRST_HOUR
Hour of first log.
47
FIRST_MINUTE
Minute of first log
48
FIRST_SECOND
Second of first log.
51
CURRENT_YEAR
Year of last log.
52
CURRENT_MONTH
Month of last log.
53
CURRENT_DAY
Day of last log.
54
CURRENT_HOUR
Hour of last log.
55
CURRENT_MINUTE
Minute of last log.
56
CURRENT_SECOND
Second of last log.
61
CHD_LAST_EVENT_YEAR
Year of last digital input event.
62
CHD_LAST_EVENT_MONTH
Month of last digital input event.
63
CHD_LAST_EVENT_DAY
Day of last digital input event.
64
CHD_LAST_EVENT_HOUR
Hour of last digital input event.
65
CHD_LAST_EVENT_MINUTE
Minute of last digital input event.
66
CHD_LAST_EVENT_SECOND
Second of last digital input event.
67
ALARM_STATUS
Alarm status at the current time.
0.
Inactive alarm;
1.
Active alarm.
68
BUZZER_STATUS
Current buzzer status.
0.
Inactive buzzer;
1.
Active buzzer.
70
DIGITAL_OUT_VALUE
Digital output status.
0.
Inactive output;
1.
Active output.
71
CHD_LAST_EVENT_EDGE
Edge of the digital channel where the last
event occurred.
0.
Descent edge;
1.
Rising edge.
72
CHD_ALARM_STATUS
Current channel alarm status.
0.
No alarm;
1.
Minimum alarm;
2.
Maximum alarm.
73
CHD_STATUS
Digital channel status.
1.
Ok;
2.
Underflow;
3.
Overflow.
74
CHD_VALUE
Value of the last digital channel log.
In counts, if set to "Pulse Count"
mode, or 1 or 0, if set in "Event
Log" or "Record Control" modes,
according to the logic level of the
circuit.
75
CHD_VALUE_USER_UNIT_FLOAT_HIGH Digital channel value in user unity (Float –
high part).
76
CHD_VALUE_USER_UNIT_FLOAT_LOW Digital channel value in user unity (Float – low
part).
77
CHD_VALUE_MIN
Minimum value registered on digital channel.
78
CHD_VALUE_MAX
Maximum value registered on digital channel.
79
CHD_ALARM_MIN_STATUS
Minimum alarm status on digital channel.
Stores information if the channel
ever reached the minimum
alarm.
0.
Never alarmed;
1.
Already alarmed.
80
CHD_ALARM_MAX_STATUS
Maximum alarm status on digital channel.
Stores information if the channel
ever reached the maximum
alarm.
0.
Never alarmed;
1.
Already alarmed.
81
CH1_STATUS
Analog channel status 1.
1.
Ok;
2.
Underflow;
3.
Overflow;
4.
Cold joint error;
5.
Open sensor.