background image

 

NOVUS AUTOMATION 

8/8 

SPECIFICATIONS 

DIMENSIONS: ........................................ 25 x 48 x 105 mm (1/16 DIN) 

Approximate Weight: .............................................................. 75 g 

PANEL CUTOUT: ..................................... 23 x 46 mm (+0.5 -0.0 mm) 
POWER SUPPLY: ..................... 100 to 240 Vac/dc (±10 %), 50/60 Hz 

Optional 24 V: ..................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %)   

  Maximum consumption: .........................................................  9 VA 
CONDITIONS ENVIRONMENTAL

Operation Temperature: ...............................................  0 to 50 

°

Relative Humidity: ......................................................... 80 % max. 

INPUT .............................. T/C, Pt100 an voltage (according Table 01

Input Resolution: ....................................... 32767 levels (15 bits) 

Resolution of Display: ...... 12000 levels (from -1999 up to 9999) 

Rate of input reading: .................................. up to 55 per second 

Precision: .. Thermocouples JKT, E: 0.25 % of the span 

±

1 ºC 

 ................... Thermocouples NRSB: 0.25 % of the span 

±

3 ºC 

 ............................................................... Pt100: 0.2 % of the span 

 ....................................................................................... mV: 0.1 % 

Input Impedance: ................ Pt100 and thermocouples: > 10 M

 

Measurement of Pt100: ....................... 3-wire type, (

α

=0.00385) 

With compensation for cable length, excitation current of 0.170 mA 

OUTPUT 

OUT1: .................................................. Voltage pulse; 5 V / 25 mA 
OUT2: ................................ Relay SPST, 1.5 A / 240 Vac / 30 Vdc 

FRONT PANEL:  .................................. IP65, Polycarbonate (PC) UL94 V-2 
ENCLOSURE
:  ....................................................... IP30, ABS+PC UL94 V-0 

ELECTROMAGNETIC COMPATIBILITY: ............... EN 61326-1:1997  

and EN 61326-1/A1:1998 
EMISSION: ............................................................ CISPR11/EN55011 
IMMUNITY: ...................... EN61000-4-2, EN61000-4-3, EN61000-4-4,  

EN61000-4-5, EN61000-4-6, EN61000-4-8 and EN61000-4-11 
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995 

(UL file E300526) 
USB INTERFACE 2.0, CDC CLASS (VIRTUAL COMMUNICATIONS 

PORT), MODBUS RTU PROTOCOL. 
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS; 
PROGRAMMABLE LEVEL OF PWM DE 0.5 UP 100 SECONDS; 
STARTS UP OPERATION AFTER 3 SECONDS CONNECTED TO 

THE POWER SUPPLY; 
CERTIFICATION:   

  and  

 

IDENTIFICATION 

N1020  - A 

- B 

- C 

A:  Output: 

PR: OUT1= Pulse / OUT2= Relay  

B:  Digital Communication: 

485: Interface communication RS485 

C:  Power Supply:  

Nothing shown (100~240 Vac) / 48~240 Vdc; 50~60 Hz 

  24V: 12~24 Vdc / 24 Vac 
 
 
 
 
 
 
 

SAFETY INFORMATION 

Any control system design should take into account that any part of 

the system has the potential to fail. This product is not a protection or 

safety device and its alarms are not intended to protect against 

product failures. Independent safety devices should be always 

provided if personnel or property are at risk. 
Product performance and specifications may be affected by its 

environment and installation. It’s user’s responsibility to assure 

proper grounding, shielding, cable routing and electrical noise 

filtering, in accordance with local regulations, EMC standards and 

good installation practices. 

SUPPORT AND MAINTENANCE 

This product contains no serviceable parts inside. Contact our local 

distributor in case you need authorized service. For troubleshooting, 

visit our FAQ at 

www.novusautomation.com

LIMITED WARRANTY AND  LIMITATION OF 

LIABILITY 

NOVUS warrants to the original purchaser that this product is free 

from defects in material and workmanship under normal use and 

service within one (1) year from the date of shipment from factory or 

from its official sales channel to the original purchaser.  
NOVUS liability under this warranty shall not in any case exceed the 

cost of correcting defects in the product or of supplying replacement 

product as herein provided and upon the expiration of the warranty 

period all such liability shall terminate. 
For complete information on warranty and liability limitations, check 

appropriate section in our web site: 

www.novusautomation.com/warranty

Summary of Contents for N1020

Page 1: ...nsult the DEVICE MANAGER in the Windows CONTROL PANEL to identify the COM port that was assigned to the controller Consult the mapping of the MODBUS memory in the controller s communications manual an...

Page 2: ...the value of measured PV is above the value defined for alarm Setpoint SPA1 PV dif Alarm of Differential Value In this function the parameters SPA1 and SPA2 represent the deviation of PV in relation...

Page 3: ...ine trimming the PV indication to compensate for sensor errors Default value zero SERIAL COMMUNICATION For full documentation download the Registers Table N1020 for Serial Communication on our web sit...

Page 4: ...opriate for cooling Turns control output on when PV is above SP sfst Softstart SoftStart Function Time in seconds during which the controller limits the MV value progressively from 0 to 100 It is enab...

Page 5: ...fications carried out by the user ovll Output Low Limit Lower limit for the control output Minimum percentage value assumed by the control output when in automatic mode and in PID Typically configured...

Page 6: ...E indication on the display It is recommended not to turn the controller off neither change the SP during this learning period It is recommended not to turn the controller off neither change the SP du...

Page 7: ...tion with a Pt100 simulator pay attention to the simulator minimum excitation current requirement which may not be compatible with the 0 170 mA excitation current provided by the controller N1020 PARA...

Page 8: ...PR OUT1 Pulse OUT2 Relay B Digital Communication 485 Interface communication RS485 C Power Supply Nothing shown 100 240 Vac 48 240 Vdc 50 60 Hz 24V 12 24 Vdc 24 Vac SAFETY INFORMATION Any control sys...