N1040i Indicator 

UNIVERSAL INDICATOR – INSTRUCTIONS MANUAL – V2.0x A 

PRESENTATION 

N1040i is a quite versatile process indicator. With a  wide list of input 
types  -  thermocouples,  thermo-resistance,  voltage  and  current  –  the 
N1040i  is  capable  of  measuring  the  majority  of  the  variables  and 
sensors encountered in industrial processes. 
The configuration can be performed directly on the indicator or through 
the  USB  interface.  The 

NConfig

  software  (free)  is  the  configuration 

management tool. Connected to the USB of a 

Windows

 computer, the 

indicator is recognized as a serial communications port (COM) running 
with a Modbus RTU protocol. 

Through  the  USB  interface,  even  if  disconnected  from  the  power 
supply, the configuration performed in a piece of equipment can be can 
be  saved  in  a  file  and  repeated  in  other  pieces  of  equipment  that 
require the same configuration. 
It  also  features  various  alarm  functions,  display  offset,  configuration 
with password  protection, serial communication, indication in degrees 
Celsius (°C) or Fahrenheit (°F), among others. 

FEATURES 

SIGNAL INPUT (INPUT) 

The input type to be used by the indicator is defined in the equipment 
configuration. 

Table  01

  presents  the  input  options  available  for  the 

user. 

TYPE 

CODE 

RANGE OF MEASUREMENT 

Tc j 

Range: -110 to 950 ºC (-166 to 1742 ºF) 

Tc k 

Range: -150 to 1370 ºC (-238 to 2498 ºF) 

Tc t 

Range: -160 to 400 ºC (-256 to 752 ºF) 

Tc n 

Range: -270 to 1300 ºC (-454 to 2372 ºF) 

Tc r 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc s 

Range: -50 to 1760 ºC (-58 to 3200 ºF) 

Tc b 

Range: 400 to 1800 ºC (752 to 3272 ºF) 

Tc e 

Range: -90 to 730 ºC (-130 to 1346 ºF) 

Pt100 

Pt 

Range: -200 to 850 ºC (-328 to 1562 ºF) 

0-20 mA 

L0.20 

Analog Linear Signal 

Indication programmable from -1999 to 

9999. 

4-20 mA 

L4.20 

0–50 mV 

L0.50 

0-5 Vdc 

L0.5 

0-10 Vdc 

L0.10 

4-20 mA 

NON 

LINEAR 

Lnj 

Non Linear Analog Signal  

Indication range according to the 

associated sensor. 

Ln k 

ln t 
ln n 
ln r 
ln s 
ln b 
ln E 

Ln.Pt 

Table 01

 – Inputs Types 

ALARMS 

The 1040i can have none, one or two alarms. Each alarm present is 
associated to one output with the same name (ALARM1 and ALARM2). 

OUTPUT 

ALARM1

 -  Relay SPDT. Available in terminals 10, 11 and 

12 of the indicator. 

OUTPUT 

ALARM2 

-  Relay SPST-NA. Available in terminals 13 and 

14 of the indicator. 

The alarms can assume the functions described on 

Table 02

off

  Alarm off. 

lo

 

Alarm of the Absolute Minimum 
Value.  It  triggers  when  the 
value  of  the 

PV

  is 

below

  the 

value  defined  by  the  alarm 

Setpoint (SPA1 or SPA2)

 

SPA1 

PV 

 

ki

 

Alarm 

of 

the 

Absolute 

Maximum  Value.  It  triggers 
when  the  value  of  the 

PV 

is 

above

 the value defined by the 

alarm 

Setpoint

 

SPA1 

PV 

 

dif

 

Alarm  of  the  Differential  Value.  In  this  function  the 
parameters  “

SPA1

”  and  “

SPA2

”  represent  errors 

(difference)  between  the  PV  and  one  reference  value 

ALrF

 

ALrF 

PV 

ALrF+SPA1 

ALrF

–SPA1 

 

 

ALrF 

PV 

ALrF 

– SPA1 

 alarme 

ALrF + SPA1 

alarme 

 

SPA1 positive 

SPA1 negative 

difl

 

Alarm of the Minimum Differential Value. It triggers when 
the value of the PV is 

below

 the point defined by: 

ALrF-SPA1

 (using alarm 1 as an example). 

 

ALrF 

PV 

ALrF 

– SPA1 

 

 

ALrF 

PV 

ALrF 

– SPA1 

 

SPA1 positive 

SPA1 negative 

difk

 

Alarm of the Maximum Differential Value. It triggers when 
the value of the PV is 

above

 the point defined by: 

ALrF+SPA1

 (using alarm 1 as an example). 

 

ALrF 

PV 

ALrF + SPA1 

 

 

ALrF 

PV 

ALrF + SPA1 

 

SPA1 positive 

SPA1 negative 

ierr

 

Alarms of the Sensor Break (Sensor 

Break Alarm

). It is 

activated  when  the  Input  presents  problems  such  as 
interrupted sensor, bad connection, etc. 

Table 02

 – Alarm Functions 

Note

: The figures are also valid for Alarm 2 (SPA2). 

Summary of Contents for N1040i

Page 1: ...Analog Linear Signal Indication programmable from 1999 to 9999 4 20 mA L4 20 0 50 mV L0 50 0 5 Vdc L0 5 0 10 Vdc L0 10 4 20 mA NON LINEAR Lnj Non Linear Analog Signal Indication range according to the...

Page 2: ...the indicator s digital inputs and outputs It is intended for temporary use during CONFIGURATION and MONITORING periods For the safety of people and equipment it must only be used when the piece of eq...

Page 3: ...iable PV the configuration parameters prompts and their respective values conditions Indicators A1 and A2 signalize the occurrence of an alarm condition Key P used to walk through the parameters in th...

Page 4: ...fset Parameter that allows the user to make corrections in the value of PV indicated inll Input Low Limit It defines the lower value of the indication range when the input types of 0 20 mA 4 20 mA 0 5...

Page 5: ...requiring maintenance service When contacting the manufacturer inform the instrument serial number obtained by pressing the key for more than 3 seconds INPUT CALIBRATION All inputs are factory calibr...

Page 6: ...oduct failures Independent safety devices should be always provided if personnel or property are at risk Product performance and specifications may be affected by its environment and installation It s...

Page 7: ...Communication signals are electrically isolated from the INPUT and POWER terminals Not isolated from the retransmission circuit and the auxiliary voltage source when available Maximum connection dist...