background image

N1040i Indicator 

NOVUS AUTOMATION 

2/7 

BLOCKING INITIAL OF THE ALARM 

The 

initial

 

blocking 

option inhibits the alarm from being recognized 

if an alarm condition is present in the process when the indicator is 
first energized. The alarm will be enabled only after the occurrence of 
no alarm condition. 
The initial blocking is useful, for example, when one of the alarms is 
set up as a minimum value alarm, which may cause the activation of 
the  alarm  soon  upon  the  process  start-up;  an  occurrence  that  may 
undesirable in many cases. 
The initial blocking is not valid for the function 

ierr

 (Sensor Break). 

OFFSET 

Allows  the  user  to  perform  fine  adjustments  to  the  PV  indication.  It 
allows  the  correction  of  measuring  errors  that  appear,  for  example, 
on the replacement of the temperature sensor. 

USB INTERFACE 

The USB interface is used for CONFIGURING or MONITORING the 
indicator. The 

NConfig

 software must be used for the configuration. It 

makes it possible to create, view, save and open configurations from 
the  equipment  or  files  in  your  computer.  The  tool  for  saving  and 
opening  configurations  in  files  makes  it  possible  to  transfer 
configurations  between  pieces  of  equipment  and  to  make  backup 
copies.  For  specific  models,  the 

NConfig

  software  also  makes  it 

possible  to  update  the  firmware  (internal  software)  of  the  indicator 
through the USB. 
For MONITORING  purposes you can use any supervisory software 
(SCADA)  or  laboratory  software  that  supports  the  MODBUS  RTU 
communication on a serial communications port. When connected to 
the USB of a computer, the indicator is recognized as a conventional 
serial  port  (COM  x).  Use  the 

NConfig

  software  or  consult  the 

DEVICE  MANAGER  in  the  Windows  CONTROL  PANEL  to  identify 
the  COM  port  that  was  assigned  to  the  indicator.  Consult  the 
mapping of the MODBUS memory in the indicator’s communications 
manual  and  the  documentation  of  your  supervisory  software  to 
conduct the MONITORING process. 
Follow  the  procedure  below  to  use  the  USB  communication  of  the 
equipment: 
1.

 

Download the 

NConfig

 software from our website and install it on 

your  computer.  The  USB  drivers  necessary  for  operating  the 
communication will be installed together with the software. 

2.

 

Connect  the  USB  cable  between  the  equipment  and  the 
computer.  The  indicator  does  not  have  to  be  connected  to  a 
power supply. The USB will provide enough power to operate the 
communication (other equipment functions cannot operate). 

3.

 

Open  the 

NConfig

  software,  configure  the  communication  and 

start recognition of the device.  

 

 

The  USB  interface  IS  NOT  SEPARATE  from  the 
signal  input  (PV)  or  the  indicator’s  digital  inputs  and 
outputs.  It  is  intended  for  temporary  use  during 
CONFIGURATION  and  MONITORING  periods.  For 
the safety of people and equipment, it must only be 
used  when  the  piece  of  equipment  is  completely 
disconnected from the input/output signals. Using the 
USB in any other type of connection is possible but 
requires a careful analysis by the person responsible 
for installing it. When MONITORING for long periods 
of  time  and  with  connected  inputs  and  outputs,  we 
recommend  using  the  RS485  interface,  which  is 
available or optional in most of our products. 

RETRANSMISSION OF PV 

The  indicator  may  include  an  analog  output  which  performs  the 
retransmission of the values of PV into a signal of 0-20 mA or 4-20 
mA.  The  analog  retransmission  can  be  scaled,  i.e.,  there  are 
minimum and maximum limits to establish the retransmission range, 
defined in the parameters 

rtLL

” 

and

 “

rtkL

The  analog  output  is  available  on  terminals  13  and  14  for  models 

N1040i-RA

 and 

N1040i-RA-485

In order to obtain retransmission in electrical voltage, the user shall 
install  a 

shunt

  resistor  (500



  max.)  across  the  analog  output 

terminals. This resistor value depends on the desired voltage range. 
The analog retransmission output is not electrically isolated from the 
RS485 serial communication. 

24 Vdc AUXILIARY VOLTAGE SOURCE  

Another feature that may be available in the indicator is an auxiliary 
power  supply  for  exciting  field  transmitters  (two-wire  4-20  mA 
transmitters). 
The 24 Vdc output is on terminals 13 and 14 for models 

N1040i-RE

 

and 

N1040i-RE-485

The 24 V auxiliary power supply is not electrically isolated from the 
RS485 serial communication. 

INSTALLATION / CONNECTIONS 

The indicator shall be fastened on a panel, following the sequence of 
steps described below: 

 

Prepare a cut-out of 46 x 46 mm on the panel; 

 

Remove the mounting clamp from the indicator; 

 

Insert  the  indicator  into  the  cut-out  from  the  front  side  of  the 
panel; 

 

Place the clamp on the indicator again, pressing until firm grip to 
the panel. 

SAFETY ALERTS  

The  symbols  below  are  used  on  the  equipment  and  throughout  this 
manual  in  order  to  draw  the  user´s  attention  to  important  information 
related to the equipment safety and operation. 

 

 

CAUTION: 

Read the manual thoroughly     

before installing and operating 

the equipment 

CAUTION OR DANGER: 

Electrical shock hazard 

All  safety  related  instructions  that  appear  in  the  manual  must  be 
observed  to  ensure  personal  safety  and  to  prevent  damage  to  either 
the instrument or the system. If the instrument is used in a manner not 
specified  by  the  manufacturer,  the  protection  provided  by  the 
equipment may be impaired. 

ELECTRICAL CONNECTIONS  

The position of the features on the indicator back panel is shown on 

Figure 01

 

 

 

Figure 01

 – Inputs connections and power supply 

Summary of Contents for N1040i

Page 1: ...Analog Linear Signal Indication programmable from 1999 to 9999 4 20 mA L4 20 0 50 mV L0 50 0 5 Vdc L0 5 0 10 Vdc L0 10 4 20 mA NON LINEAR Lnj Non Linear Analog Signal Indication range according to the...

Page 2: ...the indicator s digital inputs and outputs It is intended for temporary use during CONFIGURATION and MONITORING periods For the safety of people and equipment it must only be used when the piece of eq...

Page 3: ...iable PV the configuration parameters prompts and their respective values conditions Indicators A1 and A2 signalize the occurrence of an alarm condition Key P used to walk through the parameters in th...

Page 4: ...fset Parameter that allows the user to make corrections in the value of PV indicated inll Input Low Limit It defines the lower value of the indication range when the input types of 0 20 mA 4 20 mA 0 5...

Page 5: ...requiring maintenance service When contacting the manufacturer inform the instrument serial number obtained by pressing the key for more than 3 seconds INPUT CALIBRATION All inputs are factory calibr...

Page 6: ...oduct failures Independent safety devices should be always provided if personnel or property are at risk Product performance and specifications may be affected by its environment and installation It s...

Page 7: ...Communication signals are electrically isolated from the INPUT and POWER terminals Not isolated from the retransmission circuit and the auxiliary voltage source when available Maximum connection dist...

Reviews: