background image

N1040i Indicator 

NOVUS AUTOMATION 

3/7 

In  the  models  with  two  alarms  and  serial  communication,  the 
connections are: 

 

 

 

Figure 02

 - Alarms and serial communication connections  

In  the  models  with  one  alarm,  retransmission  of  PV  and  serial 
communication, the connections are: 

 

 

 

Figure 03

 - Alarm, retransmission and serial communication connections 

In  the  models  with  one  alarm,  24  Vdc  auxiliary  voltage  source  and 
communication, the connections are: 

 

 

 

Figure 04

 - Alarm, auxiliary source and communication connections 

A typical application of the auxiliary voltage source is to supply loop 
power for field transmitters (two-wire 4-20 mA). 

Figure 05

 shows the 

necessary wiring for this application. 

 

 

 

Figure 05

 – Example for the use of the indicator auxiliary voltage source 

RECOMMENDATIONS FOR THE INSTALLATION 

 

To  minimize  the  pick-up  of  electrical  noise,  the  low  voltage  DC 
connections  and  the  sensor  input  wiring  should  be  routed  away 
from  high-current  power  conductors.  If  this  is  impractical,  use 
shielded cables. In general, keep cable lengths to a minimum. 

 

The  input  signals  conductors  shall  be  positioned  throughout  the 
factory  separate  from  the  output  and  the  power  supply 
conductors, in grounded conduits if possible. 

 

The power supply of the electronic instruments shall come from a 
proper source for the instrumentation network. 

 

It is recommended to use RC FILTERS (0.1 uF in series with 100 
ohms)  to  suppress  the  noise  generated  by  contactors  coils, 
solenoids, etc. 

OPERATION 

The indicator front panel, together with its elements, can be seen on 

Figure 06

 

Figure 06

 - Identification of the front panel parts 

Display

:  Shows  the  process  variable 

PV

,  the  configuration 

parameters prompts and their respective values/ conditions. 

Indicators  A1  and  A2

:  signalize  the  occurrence  of  an  alarm 

condition. 

Key P

: used to walk through the parameters in the menu cycles. 

 

  Increment  key  and 

 

  Decrement  key

:  Used  to  change 

parameter values. 

 

 

Key: 

A  key  used  to  retrocede  to  the  previous  displayed 

parameter. 

START UP 

When the indicator is powered up, its firmware version is displayed 
for 3 seconds, after which the 

N1540

 starts normal operation, when 

the value of 

PV

 is displayed and the outputs are enabled. 

Before the indicator is ready to be used in a given process, it requires 
some  basic  configuration,  consisting  of  assigning  values  to  the 
parameters  according  to  the  desired  behavior.  The  user  shall 
understand the importance of each parameter and determine a valid 
condition or a valid value for each one of them. 
The  configuration  parameters  are  grouped  in  parameters  levels 
according to their functionalities. The 4 parameters levels are: 

1 – Operation 

2 – Alarms 

3 – Input 

4 – Calibration 

The

 “P”

 key provides the access to the levels and to the parameters 

of these levels. 
Keeping the 

P

 key pressed, at every 2 seconds, the indicator jumps 

from  one  level  to  another,  presenting  the  first  parameter  of  each 
level: 

PV

  >>  

fva1

  >>  

type

  >>  

pass

  >>  

PV

  … 

To  enter  into  a  particular  level,  simply  release  the 

P

  key  when  the 

first parameter in that level is displayed. 
To walk through the parameters in a level, press the P key with short 
strokes. To go back to the previous parameters, use the 

 

 Key. 

Each  parameter  symbol  is  shown  on  the  upper  display  while  its 
respective value/condition is shown on the lower display. 
Depending  on  the  level  of  parameter  protection  adopted,  the 
parameter 

PASS

 precedes the first parameter in the level where the 

protection is active. See section PROTECTION CONFIGURATION. 

Summary of Contents for N1040i

Page 1: ...Analog Linear Signal Indication programmable from 1999 to 9999 4 20 mA L4 20 0 50 mV L0 50 0 5 Vdc L0 5 0 10 Vdc L0 10 4 20 mA NON LINEAR Lnj Non Linear Analog Signal Indication range according to the...

Page 2: ...the indicator s digital inputs and outputs It is intended for temporary use during CONFIGURATION and MONITORING periods For the safety of people and equipment it must only be used when the piece of eq...

Page 3: ...iable PV the configuration parameters prompts and their respective values conditions Indicators A1 and A2 signalize the occurrence of an alarm condition Key P used to walk through the parameters in th...

Page 4: ...fset Parameter that allows the user to make corrections in the value of PV indicated inll Input Low Limit It defines the lower value of the indication range when the input types of 0 20 mA 4 20 mA 0 5...

Page 5: ...requiring maintenance service When contacting the manufacturer inform the instrument serial number obtained by pressing the key for more than 3 seconds INPUT CALIBRATION All inputs are factory calibr...

Page 6: ...oduct failures Independent safety devices should be always provided if personnel or property are at risk Product performance and specifications may be affected by its environment and installation It s...

Page 7: ...Communication signals are electrically isolated from the INPUT and POWER terminals Not isolated from the retransmission circuit and the auxiliary voltage source when available Maximum connection dist...

Reviews: