background image

N1050 Controller 

NOVUS AUTOMATION 

2/8 

PID AUTOMATIC MODE  

For the Automatic mode, there are two different strategies of control: 

PID control and ON/OFF control.  
PID control has its action based on a control algorithm that takes into 

account the deviation of PV with respect to SP, the rate of change of 

PV and the steady state error.  
On the other hand, the ON/OFF control (obtained when Pb=0) 

operates with 0 % or 100 % of power, when PV deviates from SP.  
The determination of the PID parameters 

(

Pb

,

 

ir

  and 

Dt

) is 

described in the item DETERMINATION OF PID PARAMETERS of 

this manual. 

CONTROL OUTPUT 

The control strategy can be 

ON/OFF

 (when 

PB

 = 

0.0

or 

PID

. The 

PID parameters can be automatically determined enabling the auto-

tuning function (

ATun

). 

ALARM OUTPUT 

The controller contains 2 alarms that can be directed (assigned) to any 

output channel. The alarm functions are described in 

Table 02

off 

Output is not used as alarm. 

Lo 

Alarm of Absolute Minimum 

Value. Triggers when the 

value of measured 

PV

  is 

below

  the value defined for 

alarm 

Setpoint

 

SPA1 

PV 

 

Hi 

Alarm of Absolute Maximum 

Value. Triggers when the 

value of measured 

PV

  is 

above

  the value defined for 

alarm 

Setpoint

 

SPA1 

PV 

 

dif 

Alarm of Differential Value. In this function the 

parameters 

SP.A1

 

and 

SP.A2

 

represent the deviation 

of PV in relation to the SP of CONTROL. 

 

SP 

PV 

SP + SPA1 

SP – SPA1 

 

 

SP 

PV 

SV – SPA1 

 

 

SV + SPA1 

 

 

Positive SPA1  

Negative SPA1  

Dif.L 

Alarm of Minimum Differential Value. It triggers when 

the value of PV is 

below

 the defined point by (using 

the Alarm 1 as example). 

 

SP 

PV 

SP – SPA1 

 

 

SP 

PV 

SP – SPA1 

 

Positive SPA1 

Negative SPA1  

Dif.H 

Alarm of Valor Maximum Differential Value. Triggers 

when the value of PV is 

above

  the defined point by 

(using Alarm 1 as example). 

 

SP 

PV 

SP + SPA1 

 

 

SP 

PV 

SP + SPA1 

 

Positive SPA1  

Negative SPA1  

ierr 

Alarms of the Sensor Break (Sensor 

Break Alarm

). It is 

activated when the Input presents problems such as 

interrupted sensor, bad connection, etc. 

r5 

Event (

r

amp and 

S

oak). Activated in a specific 

segment of program. 

Table 02

 – Alarm functions 

Note

: Alarm functions on 

Table 02

  are also valid for Alarm 2 

(

SP.A2

). 

Important note

: Alarms configured with the 

ki

dif

, and 

difk

 

functions also trigger their associated output when a sensor fault is 

identified and signaled by the controller. A relay output, for example, 

configured to act as a High Alarm (

ki

), will operate when the SPAL 

value is exceeded and also when the sensor connected to the 

controller input is broken. 

INITIAL BLOCKING OF ALARM 

The 

Initial Blocking

 option inhibits the alarm from being recognized 

if an alarm condition is present when the controller is first energized 

(or after a transition from run YES 

 NO). The alarm will be enabled 

only after the occurrence of a non-alarm condition followed by a new 

occurrence for the alarm. 
The initial blocking is useful, for instance, when one of the alarms is 

configured as a minimum value alarm, causing the activation of the 

alarm soon upon the process start-up, an occurrence that may be 

undesirable. 
The initial blocking is disabled for the sensor break alarm function 

ierr

SAFE OUTPUT VALUE WITH SENSOR FAILURE

 

Function that ensures that the control output is in a safe condition for 

the process when an error in the sensor input is identified.  
When a fault is identified in the sensor, the controller will determine 

the percentage value set in the parameter 

iE.ou

 

for the control 

output. The controller will remain in this condition until the sensor 

failure disappears. When in ON/OFF mode, the values for

  iE.ou

 

are only 0 and 100%. With control in PID mode, any value between 0 

and 100% will be accepted. 

LBD FUNCTION – LOOP BREAK DETECTION

 

The parameter defines a time interval, in minutes, within which the 

PV is expect to react to a control output signal. If the PV does not 

react properly within the time interval configured in 

Lbd.t

, the 

controller interprets this as a control loop break and signals this 

occurrence in the display. 
A LBD event may be sent to any output channel. Simply configure 

the LDB function to the desired output channel (OUT1 or OUT2): the 

selected output will be activated when a LDB condition is detected. 

When the 

Lbd.t 

parameter is programmed with 0 (zero), the LDB 

function is disabled. 
The LBD is useful in detecting system failures, such us defective 

sensors or actuators, loads and power supply, among others. 

OFFSET  

Allows fine adjustments to the PV  reading for compensation of 

sensor error. 

USB INTERFACE 

The USB interface is used for CONFIGURING or MONITORING the 

controller. The 

NConfig

 software must be used for the configuration. 

It makes it possible to create, view, save and open configurations 

from the equipment or files in your computer. The tool for saving and 

opening configurations in files makes it possible to transfer 

configurations between pieces of equipment and to make backup 

copies. For specific models, the 

NConfig

  software also makes it 

possible to update the firmware (internal software) of the controller 

through the USB. 
For MONITORING purposes you can use any supervisory software 

(SCADA) or laboratory software that supports the MODBUS RTU 

communication on a serial communications port. When connected to 

the USB of a computer, the controller is recognized as a conventional 

serial port (COM x). Use the 

NConfig

  software or consult the 

DEVICE MANAGER in the Windows CONTROL PANEL to identify 

the COM port that was assigned to the controller. Consult the 

mapping of the MODBUS memory in the controller’s communications 

manual and the documentation of your supervisory software to 

conduct the MONITORING process. 
Follow the procedure below to use the USB communication of the 

equipment: 
1.

 

Download the 

NConfig

 software from our website and install it on 

your computer. The USB drivers necessary for operating the 

communication will be installed together with the software. 

2.

 

Connect the USB cable between the equipment and the 

computer. The controller does not have to be connected to a 

Summary of Contents for N1050

Page 1: ...mum All electronic instruments must be powered by a clean mains supply proper for instrumentation It is strongly recommended to apply RC S FILTERS noise suppressor to contactor coils solenoids etc In any application it is essential to consider what can happen when any part of the system fails The controller features by themselves cannot assure total protection FEATURES INPUT TYPE SELECTION Table 0...

Page 2: ...um value alarm causing the activation of the alarm soon upon the process start up an occurrence that may be undesirable The initial blocking is disabled for the sensor break alarm function ierr SAFE OUTPUT VALUE WITH SENSOR FAILURE Function that ensures that the control output is in a safe condition for the process when an error in the sensor input is identified When a fault is identified in the s...

Page 3: ...rs are gathered into groups of affinities called parameter cycles The 6 parameter cycles are 1 Operation 2 Tuning 3 Programs 4 Alarms 5 Input 6 Calibration The key gives access to the cycles and their parameters When you hold the key down the controller will cycle from one cycle to another every 2 seconds displaying the first parameter of each cycle PV atun Pr tb fu a1 type pass PV To enter the de...

Page 4: ... the controller when it resumes from a power failure in the middle of a program execution of ramps and soaks Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns at the exact point where it stopped off Return with control disabled RUN No Pr n Program number Selects the ramp and soak profile program to be edited viewed The sequence of parameters that...

Page 5: ...mber that identifies the controller in the serial communication network between 1 and 247 CALIBRATION CYCLE All types of input are calibrated in the factory In case a recalibration is required it shall be carried out by a specialized professional In case this cycle is accidentally accessed do not perform alteration in its parameters Pass Password This parameter is presented before the protected cy...

Page 6: ...ogram execution of ramps and levels The restore options are Prog Returns at the beginning of the program P seg Returns the beginning of the segment t seg Returns to the point of the previous program segment the power failure off Returns with control disabled RUN No The t seg option has its performance related to the configuration adopted by the parameter P toL Thus it also has the following functi...

Page 7: ...d by the controller SERIAL COMMUNICATION The controller can be supplied with an asynchronous RS 485 digital communication interface for master slave connection to a host computer master The controller works as a slave only and all commands are started by the computer which sends a request to the slave address The addressed unit sends back the requested reply Broadcast commands addressed to all ind...

Page 8: ...NPUT J K T S and Pt100 according of Table 01 Internal Resolution 32767 levels 15 bits Resolution of Display 12000 levels from 1999 up to 9999 Rate of input reading up 10 per second Accuracy Thermocouples J K T 0 25 of the span 1 C Thermocouple S 0 25 of the span 3 C Pt100 0 2 of the span Input Impedance Pt100 and thermocouples 10 MΩ Measurement of Pt100 3 wire type α 0 00385 With compensation for ...

Reviews: