background image

Indicator N1500  

NOVUS AUTOMATION 

3/7 

PROCESS VARIABLE RETRANSMISSION 
As an option, the indicator can be supplied with an isolated 0-20 mA 

or 4-20 mA analog output for Process Variable (PV) retransmission. 
The PV values that define the scale of the 0 mA / 4 mA to 20 mA 

retransmission can be programmed by the user in the high and low 

output limits (

0v.lol

 e 

0v.kol

), at configuration level. High and 

low limits can be freely programmed, even with a low limit higher than 

high limit, resulting in a reversed retransmission signal (decreasing 

signal when PV increases). 
When this option is available, retransmission will be always active, so 

that the user will not be required to turn it on or off. 
For a voltage output signal an external shunt (calibrated resistor) 

should be installed at the analog output terminals. 

AUXILIARY 24 VDC POWER SUPPLY – AUXILIARY P.S. 
The indicator provides a voltage power supply of 24 Vdc to excite 

field transmitters with 25 mA current capacity. Available at the back 

panel terminals 16 and 17. 

CUSTOMIZED LINEARIZATION. 
Three types of signals can be user-customized to fit particular 

linearization profiles. This means that the operator can configure the 

instrument to read non-standard crescent non-linear signals with high 

accuracy. 

INSTALLATION 

The indicator is designed to be panel mounted. Remove the two plastic 

fixing clamps from the instrument, insert the unit into the panel cut-out 

and slide firmly the fixing clamps from the rear against the panel. 

RECOMMENDATIONS FOR INSTALLATION  

 

Input signal wires should be laid out away from power lines and 

preferably inside grounded conduits. 

 

Instrument mains (line) supply should be suitable for this purpose 

and should not be shared. 

 

In controlling and monitoring applications, possible consequences 

of any system failure must be considered in advance. The internal 

alarm relay does not warrant total protection. 

 

Use of RC filters (47 R and 100 nF, serial) are highly 

recommended when driving solenoids, contactor coils or other 

inductive loads. 

ELECTRICAL CONNECTIONS 
The internal electronics can be removed from the front panel without 

any cable disassembly. The input signals and power connections are 

shown in Fig. 1

 

Fig. 1 – Back Panel Terminals 

 

POWER CONNECTION 

 

 

 

Fig. 2 – Power Connection 

SENSOR AND INPUT SIGNAL CONNECTIONS 
These connections should be properly done and terminals must be 

well tightened. Thermocouples must  be installed with proper 

extension or compensation cables. 
Pt100 RTDs must be 3-wire connected and the wires connected to 

terminals 22 and 23 should have the same electrical resistance 

(same wire gauge) for correct cable length compensation. Four-wire 

RTDs can be connected by disconnecting the fourth wire. Two-wire 

RTDs can be connected by shortening terminals 22 and 23 and 

connecting the Pt100 to terminals 23 and 24. 
The figures below show the connections relative to each type of input. 

 

 

 

Fig. 3 – Thermocouple input 

Fig. 4 – 3 wire Pt100 input 

 

 

 

 

Fig. 5 – Voltage input 

Fig. 6 – Current input 

 

 

 

 

Fig. 7 – Connection for 0-5 V or 0-

10 V 

Fig. 8 – Digital Input 

Fig. 10 shows the connections for a 4-20 mA transmitter powered by 

the 24 V power supply of the indicator. 

 

Fig. 9 – Two-wire transmitter with internal power supply 

DIGITAL INPUT (DIG IN) 
The digital input is activated by connecting a switch (or equivalent) to 

its terminals, as shown in Fig. 8 above. 

ANALOG OUTPUT 
The N1500 can deliver either 0-20 mA or 4-20 mA analog output, 

depending on how the instrument is configured. The output is 

available at terminals 29 and 30. 

 
 
 
 
 
 

Summary of Contents for N1500

Page 1: ...ommunication optional 3rd and 4th alarm relays optional PROCESS VARIABLE INPUT PV The process variable PV input type is configured through the frontal keypad according to the codes shown in Table 1 re...

Page 2: ...rm output to be delayed or to deliver a single pulse or a train of pulses The delay the pulse width and the period are defined by the user Table 3 shows these advanced functions Times T1 and T2 can be...

Page 3: ...uld be suitable for this purpose and should not be shared In controlling and monitoring applications possible consequences of any system failure must be considered in advance The internal alarm relay...

Page 4: ...a level press the and keys simultaneously for 3 seconds while in the level To unlock the level press and for 3 seconds The display will briefly flash confirming that the level was successfully locked...

Page 5: ...ay will show the low limit in LoL value should the input signal be below 1 of the range Scale Scale Defines the indication range for linear inputs 0 50 mV 20 mA 0 5 V and 0 10 V 0 Configurable indicat...

Page 6: ...en The device must be withdrawn from the case and immediately placed in an anti static wrap protected from heat and humidity INPUT CALIBRATION All inputs are factory calibrated and recalibration shoul...

Page 7: ...imum RH 80 up to 30 C For temperatures above 30 C decrease 3 per C Panel protection IP65 for indoor use Installation category II pollution degree 2 altitude 2000 m INPUT Keyboard selection of input ty...

Reviews: