Indicator N1500
NOVUS AUTOMATION
7/7
REDUCED REGISTERS TABLE FOR SERIAL
COMMUNICATION
Communication Protocol
The MOSBUS RTU slave is implemented. All configurable
parameters can be accessed for reading or writing through the
communication port. Broadcast commands are supported as well
(address 0).
The available Modbus commands are:
01 – Read Coils
05 – Write Single Coil
03 - Read Holding Register
06 - Write Single Register
Holding Register Table
Follows a description of the usual communication registers. For full
documentation download the Registers Table for Serial
Communication in the N1500 section of our web site –
www.novusautomation.com
.
All registers are 16 bit signed integers.
Address Parameter
Register Description
0000
PV
Read: process variable.
Write: not allowed.
Range: the minimum value is in
inlol
seted and the maximum value is in
inkil
seted an the decimal point
position depends of
dppos
.
0003
PV
Read: normalized Process Variable.
Write: not allowed.
Maximum range: 0 to 62000.
0004
Display
Value
Read: current display value.
Write: current display value.
Maximum range: -31000 to 31000.
The range depends of the showed
display.
SPECIFICATIONS
DIMENSIONS: ......................................... 48 x 96 x 92 mm (1/16 DIN).
.................................................................... Approximate weight: 250 g
PANEL CUT-OUT: .................................... 45 x 93 mm (+0.5 -0.0 mm)
POWER: ...................................... 100 to 240 Vac/dc ±10 %, 50/60 Hz
Optional 24V: .................... 12 to 24 Vdc / 24 Vac (-10 % / +20 %)
Max. Consumption: ............................................................ 7.5 VA
ENVIRONMENTAL CONDITIONS:
Operating temperature: .................................................. 5 to 50 ºC
Maximum RH: ......................................................... 80 % up to 30 ºC.
...................... For temperatures above 30 ºC, decrease 3 % per ºC.
Panel protection: ............................................ IP65, for indoor use;
....................................... Installation category II, pollution degree 2;
altitude < 2000 m
INPUT .................... Keyboard selection of input type (refer to Table 1)
Internal resolution: ................................................ 128000 levels
Display resolution:
Temperature: ......................................................................1 / 0.1
Other measures ..............................1 / 0.1 / 0.01 / 0.001 / 0.0001
Input sample rate: ............................. 5 per second for Pt100 and T/C
................. 15 per second to 0-50 mV, 4-20 mA, 0-5 V and 0-10 V
Accuracy: ........ Thermocouples J, K, T, N: 0.25 % of span
±
1 ºC
........................... Thermocouple E, R, S, B: 0.25 % of span
±
3 ºC
...................................................................... Pt100: 0.2 % of span
.............................................................. mA, mV, V: 0.2 % of span
Input impedance: ..........................................................................
............................... 0-50 mV, Pt100 and thermocouples: >10 M
Ω
..................................................................... 0-5 V, 0-10 V: >1 M
Ω
................................. 0-20 mA, 4-20 mA: 15
Ω
(+2 Vdc @ 20 mA)
Pt100 measurement: ............... DIN 43760 standard (
α
=0.00385)
Excitation current: ................................. 0.750 mA. 3-wire circuit,
cable resistance compensation
ANALOG OUTPUT: ........................ 0-20 mA or 4-20 mA, 500
Ω
max.
.............................................................................. 4000 levels, Isolated
RELAY OUTPUT:..................................................................................
........................ ALM1, ALM2: SPDT 3 A / 240 Vac (3 A / 30 Vdc Res.)
.............. ALM3, ALM4: SPST-NO: 1.5 A / 250 Vac (3 A / 30 Vdc Res.)
EMC: ................................ EN 61326-1:1997 and EN 61326-1/A1:1998
SAFETY: .......................... EN61010-1:1993 and EN61010-1/A2:1995
SPECIFIC CONNECTIONS FOR TYPE FORK TERMINALS OF 6.3
MM;
CASE: Polycarbonate UL94 V-2; Caixa: ABS+PC UL94 V-0;
START UP: 3 seconds after power up.
CERTIFICATIONS: ....................................... CE / UL (FILE: E300526)
ORDERING INFORMATION:
N1500 -
4R -
RT -
485 -
24V
A
B
C
D
E
A: Series model: N1500
B: Relays outputs: blank (2 relays); 4R (4 relays)
C: Analog output: RT – (Retransmission of the input
signal) or Blank
D: Digital Communication: 485 – (RS485, ModBus protocol) or
Black
E: Voltage rating: blank (100-240 Vac/dc); 24V (12 to 24
Vdc / 24 Vac)
WARRANTY
Warranty conditions are available on our web site
www.novusautomation.com/warranty
.