background image

Indicator N1500G 

NOVUS AUTOMATION 

2/6 

4.

 

ALARMS 

The  indicator  features  2  alarm  outputs  in  the  basic  version.  Each 
alarm has a corresponding LED indicator in the front panel to show 
alarm status. 

TYPE 

PROMPT 

ACTION 

Disabled 

off

off

off

off

 

 

 

 

Alarm is inactive 

Sensor Break 

(

i

nput 

Err

or) 

ierr

ierr

ierr

ierr

 

 

 

 

Alarm will go ON if sensor breaks, input 

signal is out of range or Pt100 is shorted. 

 Low Alarm 

Lo

Lo

Lo

Lo

 

 

 

 

Alarm SP

PV

 

High Alarm 

Ki

Ki

Ki

Ki

 

 

 

 

Alarm SP

PV

 

Diferential Low 

Dif.lo

Dif.lo

Dif.lo

Dif.lo

 

 

 

 

 

PV

AL SP + Deviation 

AL SP 

 

Diferential High 

Dif.ki

Dif.ki

Dif.ki

Dif.ki

 

 

 

 

PV

AL SP + Deviation

AL SP

 

Diferential 

Dif

Dif

Dif

Dif

 

 

 

 

PV

AL SP + Deviation

Positive Deviation

AL SP

AL SP - Deviation

 

 

PV

AL SP - Deviation 

Negative Deviation 

AL SP 

AL SP + Deviat. 

 

Table 2

 - Alarm functions 

4.1.

 

ALARM FUNCTIONS 

The  alarms  can  set  to  operate  in  six  different  functions:  Sensor 
break,  Low  Alarm,  High  Alarm,  Differential  Low,  Differential  High  or 
Differential  (Band).  These  functions  are  shown  in 

Table  2

  and 

described as follows. 

4.1.1.

 

Sensor break 

The  alarm  will  go  ON  whenever  the  sensor  breaks  or  is  badly 
connected. 

4.1.2.

 

Low alarm 

The alarm relay will go ON whenever the measured value is 

below

 

the alarm set point. 

4.1.3.

 

High alarm 

The alarm relay will be ON whenever the measured value is 

above

 

the alarm set point. 

4.1.4.

 

Differential (Band) 

For  differential  alarm  2  parameters  must  be  set:  Differential  Alarm 
Reference  value  (

ALrEF

ALrEF

ALrEF

ALrEF

)  or  alarm  setpoint  and  Alarm  Deviation 

(Band). 

For  a  positive  deviation  the  alarm  will  switch  on  whenever  the 
measured value is 

out

 of the band defined as: 

 (

ALrEF

ALrEF

ALrEF

ALrEF

 - Deviation) and (

ALrEF

ALrEF

ALrEF

ALrEF

 + Deviation) 

For a negative deviation the alarm will be switched on whenever the 
measured value is 

within

 the band defined above. 

4.1.5.

 

Differential Low 

The alarm relay will be ON whenever the measured value is 

below

 

the band defined as: 

 (

ALrEF

ALrEF

ALrEF

ALrEF

 - Deviation) 

4.1.6.

 

Differential High 

Alarm relay will be ON when the measured value is 

above

 the band 

defined as: 

(

ALrEF

ALrEF

ALrEF

ALrEF

 + Deviation) 

4.2.

 

ALARM TIMER 

The  alarms  can  be  programmed  to  have  timer  functions  where  the 
user  can  set  a  delayed  alarm  action,  just  one  pulse  in  an  alarm 
event, or an oscillator function with sequential pulses. 

Table 3 shows these advanced functions. Times T1 and T2 can be 
programmed from 0 to 6500 seconds (refer to item 8.2). Set 0 (zero) 
at the T1 and T2 prompt for a normal non-timer alarm operation. 

The  LEDs  alarm  indicators  will  go  ON  whenever  there  is  an  alarm 
condition  regardless  of  the  present  alarm  status  which  may  be 
temporarily off because of timer action. 

Advanced 

Function 

T1 

T2 

ACTION 

Normal 

Operation 

Alarm Event

Alarm

Output

 

Delayed 

1s to 6500s 

Alarm Event

Alarm

Output

T2

 

Pulse 

1s to 6500s 

Alarm Event

Alarm

Output

T1

 

Oscillator 

1s to 6500s  1s to 6500s 

Alarm Event

Alarm

Output

T1

T2

T1

 

Table 3

 - Timer Alarm Functions 

4.3.

 

ALARM INITIAL BLOCKING 

The initial blocking option inhibits the alarm from being recognized if 
an  alarm  condition  is  present  when  the  controller  is  first  energized. 
The  alarm  will  actuate  only  after  the  occurrence  of  a  non  alarm 
condition followed by a new occurrence for the alarm. 

The initial blocking is disabled for the 

sensor break

 alarm function. 

5.

 

SPECIAL FUNCTIONS 

5.1.

 

MAXIMUM AND MINIMUM 

The  indicator  memorizes  the  measured  maximum  and  minimum 
values  (peak  and  valley).  These  two  values  are  shown  by  pressing 
either the 

 or 

 key. Pressing both keys simultaneously will 

clear the memory for a new peak and valley detection. 

5.2.

 

SPECIAL FUNCTION KEY AND DIGITAL INPUT 

The 

key

 

and the optional digital input can execute special functions 

according to the user selection. 

These functions can be chosen independently to the 

F

 key or to the 

digital input. A closed contact or a short circuit at terminals 12 and 13 
is recognized as activating the digital input. 

The  special  functions  for  the 

F

  key  and  for  the  digital  input  are 

explained as follows. 

5.2.1.

 

Hold 

The 

hold

  function  freezes  the  measured  value  in  the  display.  Each 

touch at the 

F

 key or closing the digital input alternates from 

hold

 to 

normal mode.  

Whenever  the  indicator  is  in  the 

hold

  mode  a  “

HoLd

HoLd

HoLd

HoLd

”  message  is 

briefly displayed to show the operator that the displayed value is the 
frozen value and not the present reading. 

5.2.2.

 

Peak Hold 

The indicator turns automatically to 

Peak Hold

 mode whenever the 

F

 

key or the digital input are programmed for “

P

P

P

PHoLd

HoLd

HoLd

HoLd

”  

This operation mode makes the indicator display only the maximum 
reading value from the time the key was pressed of the digital input 
was activated. 

Each activation of the 

F

 key or digital input triggers a new 

Peak Hold

 

cycle and the display resets with a new peak value. 

5.2.3.

 

rESEt

rESEt

rESEt

rESEt

 (clears maximum and minimum) 

This  function  works  the  same  way  as  the 

  and 

  keys 

pressed simultaneously, as explained in the 5.1 section. 

If this “

rESEt

rESEt

rESEt

rESEt

” function is programmed, for every touch of the 

F

 key 

or activation of the digital input the memory will be cleared and a new 
cycle of maximum and minimum will start. 

5.2.4.

 

AL.oFF

AL.oFF

AL.oFF

AL.oFF

 - 

Alarm blocking

 

This  function  allows  the  user  to  block  or  inhibit  the  alarm  relays  by 
pressing  the  F  key  or  by  activating  the  digital  input.    Each  touch  of 
the key or activation of the digital input will alternate the function from 
ON to OFF and vice-versa. 