background image

Indicator N1500G 

NOVUS AUTOMATION 

3/6 

If an alarm situation occurs, the respective alarm status LEDs in the 
front panel will light regardless of the relay alarm blocking status. 

5.2.5.

 

Tare 

This function is used to zero the display. The tare residual values is 
subtracted  or  added  to  the  total  measured  value.    This  function  is 
generally used with load cells and strain gauges and applies to linear 
4-20 mA, 0-50 mV and 0-5 V inputs. 

5.3.

 

PROCESS VARIABLE RETRANSMISSION 

As an option, the indicator can be supplied with an isolated 0-20 mA 
or 4-20 mA analog output for Process Variable (PV) retransmission. 

The  PV  values  which  define  the  range  of  the  0-20  mA  or  4-20  mA 
retransmission can be programmed by the user in the 

high and low 

indication limits

Note – PV retransmission does not take an action of the special 

Hold

 

and 

Peak Hold

 functions. 

5.4.

 

CUSTOMIZED LINEARIZATION

 

The  indicator  features  three  types  of  input  signals  that  allow  for 
custom  linearization,  this  is,  the  user  can  configure  the  device  in 
order  to  obtain  accurate  indications  for  electrical  signals  with  non-
linear  and  ever  increasing  characteristics.  The  three  types  of  input 
signal are: 

c.0

c.0

c.0

c.0-

-

-

-50

50

50

50

c.4

c.4

c.4

c.4-

-

-

-20

20

20

20

 and 

c.0

c.0

c.0

c.0-

-

-

-5

5

5

5

. When selected, the indicator 

creates the Custom Linearization Cycle. 

The input signal must be divided in segments (maximum 19), defined 
in  order  to  minimize  the  error  between  the  input  signal  and  the 
corresponding indication. In the

 

Custom Linearization

 

cycle

 

the user 

finds  the  parameter

inp.01

inp.01

inp.01

inp.01

  which  corresponds  to  the  start  point  of 

the first segment and must set the minimum value of the input signal. 
Then  the  parameter 

ovt.01

ovt.01

ovt.01

ovt.01

  that  corresponds  to  the  desired 

indication for this first point. Soon after

inp.02 

inp.02 

inp.02 

inp.02 

which is the starting 

point of the second segment and 

ovt.02 

ovt.02 

ovt.02 

ovt.02 

the respective indication. 

 

In 

Inp.o1 

Inp.o1 

Inp.o1 

Inp.o1 

must always set the minimum value of the selected signal 

type: 0.0 mV for 

c.0

c.0

c.0

c.0-

-

-

-50

50

50

50

, 4.0mA for 

c.4

c.4

c.4

c.4-

-

-

-20

20

20

20

 and 0.0 V for 

c.0

c.0

c.0

c.0-

-

-

-5

5

5

5

For linearization’s that do not require all 19 segments, simply set the 
maximum  value  of  the  selected  input  type  to  the  last  required 
segment. Note: The Lower Indication Limit and Upper Indication Limit 
parameters must be set before these Custom Linearization settings. 

In this mode the sampling rate is 4 measurements per second. 

6.

 

INSTALLATION 

6.1.

 

PANEL ASSEMBLY 

The indicator is composed of two parts: the fixing base and the front 
part with main circuits. The base must be removed from the front and 
fixed  onto  a  wall  by  means  of  four  designed  holes  as  shown  in 

Figure 1. 

90

266

4X 4mm

3X 12mm

 

Figure 1

 - Mounting the indicator in the panel cut-out. 

The  front  part  is  only  attached  to  the  fixing  base  after  all  electrical 
wire connections are done. 

6.2.

 

ELECTRICAL CONNECTIONS 

The internal electronics can be removed from the front panel without 
any cable disassembly. The input signals and power connections are 
shown in 

Figure 2

 

 

Figure 2

 - Back panel terminals 

Note: The left side of the indicator is removable. It is fixed there 

a label containing the connections. 

6.2.1.

 

Recommendations for Installation 

  Input  signal  wires  should  be  laid  out  away  from  power  lines  and   

preferably inside grounded conduits. 

  Instrument mains (line) supply should be suitable for this purpose 

and should not be shared. 

    In controlling and monitoring applications, possible consequences 

of any system failure must be considered in advance. The internal 
alarm relay does not warrant total protection. 

  RC  filters  (47 

  and  100  nF)  are  highly  recommended  for  valve 

and contactor coils, etc. 

6.2.2.

 

  

Sensor or input signal connection 

These  connections  should  be  properly  done  and  terminals  must  be 
well  tightened.  Thermocouples  must  be  installed  with  proper 
extension or compensation cables. 

Pt100  RTDs  must  be  3-wire  connected  and  the  wires  connected 
should  have  the  same  electrical  resistance  (same  wire  gauge)  for 
correct  cable  length  compensation.  Four-wire  RTDs  can  be 
connected by  disconnecting the fourth wire. Two-wire  RTDs can be 
connected by shortening terminals 7 and 8 and connecting the Pt100 
to terminals 8 and 9. 

7.

 

OPERATION 

For best  results this indicator  requires correct setting of parameters 
as  input  type  (T/C,  Pt100,  4-20  mA,  etc),  alarms  actuation  point, 
alarm function, etc. 

These parameters are divided in five levels or groups of parameters 
which we will refer to as CYCLES. 

Cycle 

Access 

1- Work 

free access  

2- Alarms 

reserved access 

3- Functions 

4- Configuration 

5- Calibration 

Table 4

 - Parameters Cycles 

The  work  cycle  has  free  access.  All  other  cycles  require  a  certain 
combination of key strokes to be accessed. The combination is: 

 

and 

 

keys pressed simultaneously 

Reviews: