background image

Indicator N1500G 

NOVUS AUTOMATION 

4/6 

Within  a  certain  cycle  just  press 

 

to  go  to  the  following 

parameters. At the end of each cycle the display will go back to the 
work cycle. 

At the desired prompt just press the 

 

or 

 

key to

 

change this 

parameter accordingly. 

All changes are recorded in non-volatile memory as we move to next 
prompt. After 25 seconds with no key pressed the indicator will return 
to the measuring cycle (work cycle). 

7.1.

 

CYCLE PROTECTION 

The values of parameters of a certain cycle can be protected against 
non-authorized users. 

The  protected  parameters  can  still  be  viewed  but  can  not  be 
changed. 

To protect a cycle just press the 

 and 

 keys for 3 seconds at 

the  beginning  of  the  referred  cycle.  To  unlock  this  cycle  (allow 
changes  in  parameters),  press  the  keys 

  and 

  for  3 

seconds. 

The  display  will  briefly  blink  confirming  that  the  locking  or 
unlocking of the cycle. 

8.

 

PROGRAMMING THE INDICATOR 

8.1.

 

WORK CYCLE 

This is the first and main cycle. At power up the indicator will display 
the Process Variable (PV). The alarm setpoints are also displayed at 
this cycle. To run through this cycle just press the 

 

key. 

Whenever  an  alarm  is  set  with  differential  function  the  respective 
alarm  setpoint  is  blocked  (

SP.AL1

SP.AL1

SP.AL1

SP.AL1

SP.AL2

SP.AL2

SP.AL2

SP.AL2

,  ...)  and  the  display 

shows  “

diF

diF

diF

diF

”  to  advise  the  operator  that  this  is  a  configuration 

parameter  and  that  the  respective  deviation  value  must  be 
programmed  at  the  Alarms  Cycle.  The  “

AL.rEF

AL.rEF

AL.rEF

AL.rEF

”  prompt  will  be 

displayed showing the reference value for the alarm with differential 
function. 

SCREEN 

PARAMETER DESCRIPTION 

8.8.8.8.8.

8.8.8.8.8.

8.8.8.8.8.

8.8.8.8.8. 

 

 

 

Measure

  Shows  the  measured  variable.  For  Pt100 

or thermocouples the display will show the absolute 
temperature value. 
For 4-20 mA, 0-50 mV and 0-5 V inputs the display 
shows  the  values  defined  in  the  “

in.LoL

in.LoL

in.LoL

in.LoL

”  and 

in.HiL

in.HiL

in.HiL

in.HiL

” prompts. 

With  the 

hold

  function  programmed  the  display 

shows  the  frozen  variable  and  alternates  with  the 
message “

HoLd

HoLd

HoLd

HoLd

”. 

Likewise,  with 

Peak

 

Hold

  function  programmed  the 

high  limit  is  displayed  with  the  “

P.HoLd

P.HoLd

P.HoLd

P.HoLd

”  prompt 

alternately. 
Should  any  fault  situation  occur  the  indicator  will 
display an error message which can be identified at 
item 10 of this manual.  

Al.ref

Al.ref

Al.ref

Al.ref 

 

 

 

Differential  Alarm  Reference  Value 

-  This  prompt 

is  shown  only  when  there  is  an  alarm  programmed 
with differential function. 

Sp.al1

Sp.al1

Sp.al1

Sp.al1 

 

 

 

Sp.al2

Sp.al2

Sp.al2

Sp.al2 

 

 

 

Set  Points  of  Alarms  1  and  2 

-  Defines  the 

operation point of each alarm programmed with “

Lo

Lo

Lo

Lo

” 

or “

Hi

Hi

Hi

Hi

” function. 

Note:  When  the  alarms  are  programmed  with 
differential  function,  the  alarm  setpoint  cannot  be 
changed at this cycle and a  “

diF

diF

diF

diF

”  message will be 

shown. The SP differential (deviation) value is set at 
the Alarm Cycle.  

8.2.

 

ALARM CYCLE 

fV.al1

fV.al1

fV.al1

fV.al1 

 

 

 

fV.al2

fV.al2

fV.al2

fV.al2 

 

 

 

Alarm

 

Function

 - Defines the alarms 1, 2, 3 and 4 

function, as defined in item 4.1 

oFF

oFF

oFF

oFF

 

: Alarm off 

iErr

iErr

iErr

iErr

  : Broken or Shorted Sensor  

Lo

Lo

Lo

Lo

   

: Low value 

Hi

Hi

Hi

Hi

   

: High value  

DiFL

DiFL

DiFL

DiFL

  : Differential low 

DiFH

DiFH

DiFH

DiFH

  : Differential high 

DiF

DiF

DiF

DiF

 

: Differential 

Df.al1

Df.al1

Df.al1

Df.al1 

 

 

 

Df.al2

Df.al2

Df.al2

Df.al2 

 

 

 

Differential  SP  for  Alarms  1  and  2 

-  Defines  the 

deviation value from the alarm setpoint in relation to 
the Reference Value defined in the “

ALdiF

ALdiF

ALdiF

ALdiF

” prompt. 

Note: This value cannot be changed at this cycle for 
alarms with non-differential function and the “

AbS

AbS

AbS

AbS

” is 

then displayed.  

Ky.al1

Ky.al1

Ky.al1

Ky.al1 

 

 

 

Ky.al2

Ky.al2

Ky.al2

Ky.al2 

 

 

 

Alarm Hysteresis

 

This is the difference from the measured value to the 
point where the alarm is turned ON and OFF. 

Bl.al1

Bl.al1

Bl.al1

Bl.al1 

 

 

 

Bl.al2

Bl.al2

Bl.al2

Bl.al2 

 

 

 

Alarm Blocking

 

Should  any  alarm  condition  occur,  each  alarm  can 
be  disabled  when  energizing  the  indicator.  Refer  to 
item 4.3. 

Al1t1

Al1t1

Al1t1

Al1t1 

 

 

 

Al1t2

Al1t2

Al1t2

Al1t2 

 

 

 

Al2t1

Al2t1

Al2t1

Al2t1 

 

 

 

Al2t2

Al2t2

Al2t2

Al2t2 

 

 

 

Time Alarms

 

The  user  can  set  delayed  or  sequential  alarms  as 
shown in table 3 by defining times T1 and T2. 

To disable this function just set zero for T1 and T2. 

8.3.

 

FUNCTION CYCLES 

f.fvnc

f.fvnc

f.fvnc

f.fvnc 

 

 

 

F KEY FUNCTION 

- Options are: 

oFF

oFF

oFF

oFF

 -         Key no used. 

Ho

Ho

Ho

Hold

ld

ld

ld

 -         Hold PV 

AL.oFF

AL.oFF

AL.oFF

AL.oFF

 - 

Alarm disabled 

rESEt

rESEt

rESEt

rESEt

 - 

Resets Peak and Valley 

PHoLd

PHoLd

PHoLd

PHoLd

 - 

Peak Hold 

tArE

tArE

tArE

tArE

 -         Tare zeroing 

These functions are described in item 5.2. 

Dig.in

Dig.in

Dig.in

Dig.in

 

Digital  Input  Function 

-  The  same  function 

available for the 

F

 key: 

oFF

oFF

oFF

oFF

 

-

 

Hold

Hold

Hold

Hold

 - 

AL.o

AL.o

AL.o

AL.oFF

FF

FF

FF

 

-

 

rESEt

rESEt

rESEt

rESEt

 

-

 

PHoLd

PHoLd

PHoLd

PHoLd

 

-

 

tArE

tArE

tArE

tArE

  

Refer to item 5.2. 

filtr

filtr

filtr

filtr

 

Input Digital Filter 

- Adjustable from 0 to 20, this is 

used to reduce instability of the measured value. 

0  means  the  filter  is  off  and  20  means  maximum 
filtering.  The  higher  the  filter  value  the  lower  is  the 
measured value response. 

ofset

ofset

ofset

ofset

 

Display Offset

 - This a value which is added to the 

PV  to  offset  any  measurement  deviation  or  sensor 
error. The offset is shown directly in the programmed 
engineering unit. 

For °F measurements the null reference is at 32 °F. 

bavd

bavd

bavd

bavd

 

Baud  Rate 

-  Serial  digital  communication  speed  in 

bps

Programmable:  1200,  2400,  4800,  9600  and  19200 
bps. 

Adres

Adres

Adres

Adres

 

Communication  Address

  -  A  number  which 

identifies the instrument in a multidrop network. 

Reviews: