background image

TagTemp-S 

NOVUS AUTOMATION 

3/12

 

4

 

OPERATION 

To operate the device, the user must install the 

NXperience

 or the 

LogChart-NFC

  application according to the instructions given in 

sections 5 and 6 of this manual. 
To communicate with the 

TagTemp-S

, you must put your 

smartphone or an NFC interface next to the device. The range of 

communication is a few centimeters, being a characteristic limitation 

of NFC technology. 
If the device has not been communicating for a long time and if it is in 

circular log mode, it is recommended to stop the operation first. To 

do this, simply press the "

Stop

" button through the 

NXperience

 or 

the 

LogChart-NFC

 configuration software. 

4.1

 

Memory Modes 

There are two ways to program the use of device memory: 

 

Memory Full:

 Logs stop when there is no more free memory. 

 

Circular Memory:

  When reaching the end of the memory, it 

continues recording, overwriting the oldest records. 

Logging must begin with 

NXperience

 or 

LogChart-NFC

 applications. 

The log stop can be one of the following (whichever comes first): full 

memory (when this mode of memory usage is configured); a 

smartphone command;  by pressing the application button or by 

NXperience TagTemp-S

Note

: The start and stop of the data record can be set using the 

 

button on the device, when set in that way through the computer or 

smartphone.

 

4.2

 

Luminous Notification 

TagTemp-S

 has a LED that indicates its operation: 

 

1 flash every 10 seconds: Active; 

 

2 flashes every 10 seconds: Recording; 

 

3 flashes every 10 seconds: Active alarm; 

 

A quick flash followed by a slow flash: Start or end of the records. 

If the LED is always off, it can be for one of the following reasons: 

 

Registration has stopped; 

 

It is set to low power mode; 

 

The battery has run out. 

Note

: The LED flashing is intentionally weak and can be difficult to 

see in bright places. 

4.3

 

Start Delay 

The Start Delay is a start-up delay, set by the user, in which 

TagTemp-S

 will wait before starting the logs. During this delay time, 

the LED flashes every 5 seconds. 

4.4

 

 Button 

The 

 button, located on the front of the product, can be used to 

start or stop data logging, according to the settings. 
To give the command to start or stop logs, press this button until the 

LED turns on and then release it before it goes out. 
If the LED goes off before releasing the button, the command will not 

be validated and the button will be disabled for 30 seconds. This is a 

protective measure to prevent accidental touches of the button from 

discharging the device's battery. 
This button is also used to remove the device from low-power mode 

(see "Device Power Options" section). 

4.5

 

Temperature Unit 

The unit of temperature can be chosen by the user between degrees 

Celsius (standard) and Fahrenheit. Changing the temperature unit 

causes a new setting to be sent. 

4.6

 

Range of Alarms 

It is common for the transport of perishable products and other 

temperature sensitive cargoes to have a preset temperature range at 

which the cargo is to be maintained. With the 

LogChart-NFC

  and 

NXperience

 applications, you can configure alarms for viewing at the 

time a download is performed. 
Two alarm conditions can be set: 

 

Temperature above desired limit; 

 

Temperature below desired limit. 

This indication can be viewed in the 

LogChart-NFC

 or 

NXperience

In  the app 

LogChart-NFC

, you can check all alarm occurrence 

records in the "

Events Screen

". 

4.7

 

User

 

Offset 

A zero offset can be set up  ± 3 °C (± 5.4 ° F) for temperature 

adjustment. This makes it possible to reduce (or even cancel) the 

temperature measurement error for a given point. 

5

 

LOGCHART-NFC MOBILE APPLICATION 

LogChart-NFC

  is a mobile application for 

ANDROID™

  that allows 

you to configure, download, view and share the data stored in the 

TagTemp-S

.  

To use this application, follow the steps below. 

5.1

 

Installing the App

 

To install it, look for the 

LogChart-NFC

  application in the 

Google 

Play Store

. After the download, open the application. 

If your 

smartphone does not have support for NFC technology

, the 

application will display the following message: 

 

Fig. 01

 – Warning screen when the NFC interface it is not available  

5.2

 

App Operation 

The communication of the mobile application with the 

TagTemp-S

 is 

done through the NFC interface of the smartphone and, therefore, 

must be enabled in it. 

Summary of Contents for TagTemp-S

Page 1: ...NOVUS AUTOMATION 1 12 TagTemp S INSTRUCTION MANUAL V1 0x A ...

Page 2: ...ion tag Another way is to use the blister hole to attach the transmitter 3 TECHNICAL FEATURES Operating Temperature 30 C to 60 C Storage Temperature From 30 C to 65 C Measuring Range Temperature 30 0 C to 60 0 C Accuracy of Measurement 1 C max over the full measuring range Note The user can correct the measurement error in the Offset parameter using the configuration software Measurement Resolutio...

Page 3: ...ted on the front of the product can be used to start or stop data logging according to the settings To give the command to start or stop logs press this button until the LED turns on and then release it before it goes out If the LED goes off before releasing the button the command will not be validated and the button will be disabled for 30 seconds This is a protective measure to prevent accidenta...

Page 4: ...on about TagTemp S Log interval Indicates the value defined of the interval between each acquisition Loggings Indicates the number of records made by TagTemp S Logging state Indicates hether the log is running stopped or waiting for loggings to start Start Delay Memory usage Indicates the memory usage mode full or circular Battery Indicates the status of the battery charge Good Perfect to use Medi...

Page 5: ... option you can start logging data by pressing the device button Stop loggings by button When you enable this option you can stop logging by pressing the device button Enable circular memory When this option is enabled when the memory is complete the recording will continue overwriting the oldest records Use Fahrenheit degrees When this option is enabled the temperature unit of Celsius default is ...

Page 6: ...sured value was below the specified lower limit for the range First occurrence The time of the first event the measured value was below the minimum limit Last occurrence The time from the last event the measured value was below the minimum limit Total logs within occurrences Number of acquisitions below the minimum range limit Average temperature within occurrences Average value of temperatures be...

Page 7: ...the last 2000 To select a graph display range the Chart range option can be used 5 2 4 1 Data Chart Options Screen When the user selects the icon in the upper right of the screen the chart options will appear Fig 14 Data Chart Options Screen 1 Share By pressing the icon the user can share the obtained data using the applications already installed in the smartphone or through the option of publishi...

Page 8: ...atible with NXperience nxd so that the data can be read and displayed by this application Initial Screen Selection Allows the user to select the startup screen after reading the data from the device NOVUS Cloud Authentication Hire an account in the NOVUS Cloud to store the TagTemp S data Enter the login credentials in the Username and Password fields to send the data Export Automatically If this o...

Page 9: ...sage will be displayed Fig 24 Reading Device Screen Stop logging This option stops data logging and is read allowing the device to be configured Show Only By choosing this option the user can only view the device s settings Functions such as saving settings changing the password or setting the device to idle mode will be disabled After reading the device the configuration screen is shown below in ...

Page 10: ...de for the connected device Save File This option allows the user to save the configuration settings made to a file so it can be reused to configure other devices Security This option allows the user to create change or delete a password The password must be four digits long Fig 29 shows the definition and password change screen Fig 29 Definition and Password Change Screen Idle Mode This option pl...

Page 11: ...files for viewing customizing preparing reports or other functions Fig 36 Downloading the Device Logs 6 4 2 Viewing Downloaded Data After the transfer of the records the data downloaded are presented graphically as shown in the images below Fig 37 Viewing Downloading Data 6 4 1 Sharing and Processing Data After completing the download a screen will be displayed with the downloaded data and these a...

Page 12: ... 7 Zoom 8 Properties 9 Report Export Logs 10 NOVUS Cloud 11 Exit 6 5 Exporting and Creating Reports Using the NXperience the user can export the downloaded data to various file formats or create reports from the available models These two features are accessed by clicking the Report Export Logs button in the function menu Export to Other Formats Selecting this option from the Model options a secon...

Reviews: