background image

NOVUS AUTOMATION 

2/3 

 

The TxConfig screen in shown in Fig. 3

 

Fig. 3 – TxConfig main screen 

The fields in the screen mean: 
1.

 

Input Sensor: Select the sensor to be used. See Table 1

2.

 

Measuring Range: Define the transmitter measurement range. 

Range Lower Limit: temperature desired for a 4 mA current. 
Range Upper Limit: temperature desired for a 20 mA current. 
When the Lower Limit is set with a value greater than the Upper 

Limit value of the output current operates from 20 to 4 mA (the 

current decreases as the temperature increases). 

Note: The values chosen can not exceed the Sensor Range shown 

in this same field, and also may not establish a range with width 

(span) smaller than the Min. Range indicated later in this same field. 

See Table 1 of this guideline. 

3.

 

Sensor Failure: It establishes the output behavior, when the transmitter 

indicates a failure: 

Minimum: output current goes to 3.8 mA (down-scale), typically used for 

refrigeration. 
Maximum: output current goes to 20.5 mA (up-scale), typically used for 

heating. 

4.

 

Device  Information:  This field contains the data identifying the 

transmitter. This information must be submitted to the manufacturer for 

any queries. 

5.

 

Zero Correction: It corrects small deviations presented in the transmitter 

outlet, for example, when the sensor is replaced. 

6.

 

Send Configuration: It applies the new setup. Once sent, the setup will 

be immediately adopted by the transmitter. 

7.

 

Read  Configuration:  Reads the current setup in the transmitter 

connected. The screen now presents the current setup that may be 

changed by the user. 

Note: The factory default configuration is: 

 

Sensor Pt100, range 0 to 100 °C, 0 °C of zero correction. 

 

Output at maximum for the sensor failures. 

Upon purchase order, the user can define a specific setup. 
 
 
 
 
 
 
 
 
 
 
 
 

MECHANICAL INSTALLATION 

The TxIsoPack  transmitter is suitable to be installed in heads. Vibrations, 

moisture and extreme temperatures, electro-magnetic interference, high 

voltage and other interferences can permanently damage the unit, and could 

cause error in the measured value. 
DIMENSIONS: 

 

Fig. 4 – Transmitter dimensions 

ELECTRICAL INSTALLATION 

Polyamide enclosure. 
Section of the cable used: 0.14 to 1.5 mm². 
Recommended torque in the terminal: 0.8 Nm. 
RECOMMENDATIONS FOR INSTALLATION 

 

Sensor signals conductors must go through the plant system separate 

from power leads (loop), if possible in grounded conduits. 

 

The instruments must be powered from the instrumentation power supply 

circuit. 

 

In control and monitoring applications is essential to consider what can 

happen when any part of the system fails. 

 

It is recommended the use of suppressors in contact coils, solenoids and 

any inductive load. 

 

Use compensation cables in the connections using thermocouples. 

ELECTRICAL CONNECTIONS 
The figures below show the electrical connections required. The terminals 3, 4, 

5 and 6 are dedicated to the sensor connection. LOAD represents the 4-20 mA 

current measuring device (indicator, controller, recorder, etc.) 
PT100 2-WIRES 
Note:
 When the Pt100 2-wires the terminals 3 and 4 must be interconnected, 

according to the figure below. 

 

Fig. 5 – Transmitter electrical connections (Pt100 2-wires) 

 

 
 
 
 
 
 
 
 
 

Reviews: