background image

TxMini-M12 Transmitter 

NOVUS AUTOMATION

 

3/3

 

 

Fig. 4

 – TxMini-M12 / TxMini

 

Connection Diagram

 

SENSOR CONNECTION 

Terminals 1, 2 and 3 are dedicated to sensor connection. Terminals 

1 and 2 must be shorted, as shown in the figure below.

 

 

Fig. 5

 – Input 3-wire Pt100 / Pt1000  

M12 CABLE CONECTION 

See below guidelines for making or purchasing the M12 cable. 

 

Fig. 6

 – Connecting pins for M12 cable mounting 

For appropriate cable resistance compensation, the same cable type 

should be used for all terminals. Maximum wire resistance is 25 

Usage of a 3 or 4 wire with conductors of equal length and gauge is 

recommended (cable not supplied). 

 

OPERATION 

The sensor offset can be adjusted through the 

TxConfig II

 software. 

The USB cable may be connected to the transmitter without causing 

any measurement errors.  
The user must select the sensor and most suitable range to the 

process. The chosen range must not  exceed the maximum range 

specified for that sensor and should not be narrower than the 

minimum range for that same sensor. 
It is important to note that the transmitter accuracy is based on the 

maximum range of the sensor used, even when a narrower range is 

programmed. Example: 

 

The Pt100 input has a max. range of –200 to +650 °C. Its 

accuracy is 0.2 % of  the full range, resulting in a  maximum 

allowed error of 1.7 °C (0.2 % of 850 °C).  

 

This error  may be present even when a narrower range is 

configured for the sensor (for example: 0 to 100 °C.). 

Note

: When Pt100 simulators are used with the transmitter, make 

sure the excitation current of the simulator is compatible with the 

Pt100 excitation current of the transmitter, which is 0.8 mA. 

WARRANTY 

Warranty conditions are on our web site 

www.novusautomation.com/warranty

Reviews: