25
Version 0.2
SCS-1002
Hospital and refrigerator alarm system
All SCs start operation automatically once the power is supplied.
To power the SCs, firstly, turn on a circuit breaker on the main switchboard, then,
transfer a power button to
ON
position – on SCS-SPS, or press
Power
button – on
SCS-CU, if it is not active.
At least 30 sec after switching on, the System will automatically transfer to wait
mode.
3.2.4
System settings
To provide the System settings, act as follows:
a)
power up the SCs;
b)
follow the steps below to set up RCD (except SCS-WP):
–
set up or reset a password (except SCS-SPS);
– set up a reset timer (20 to 80 sec);
– set up a quantity of controlled calling stations;
– set up a name and background type of the station;
– set up a timer of postponed sound signaling;
– set up an operation mode of reset button (reset or mute);
c)
provide settings of SCS-WP – set up an operation mode of reset button (reset
or mute);
d)
provide settings of controllers – set up a network address using DIP-switches,
see table 13.
Table 13 – Network addresses of controllers
Address
DIP-switch SW2
DIP:5
DIP:4
DIP:3
DIP:2
DIP:1
0
0
0
0
0
0
1
0
0
0
0
1
2
0
0
0
1
0
3
0
0
0
1
1
4
0
0
1
0
0
5
0
0
1
0
1
6
0
0
1
1
0
7
0
0
1
1
1
8
0
1
0
0
0
9
0
1
0
0
1
10
0
1
0
1
0