Appendix
78
PE7324G / PE8324G / PE9324G
Function
PE7324G
PE8324G
PE9324G
Power Outlets Direct
24
Connectors
Power Cord
1 x IEC 309 32A
Power
Outlets
IEC
Total: 21 x IEC 320 C13 + 3 x IEC 320 C19
Bank 1-1, Outlet 1–8: 7 x C13 + 1 x C19.
Bank 1-2, Outlet 9–16: 7 x C13 + 1 x C19
Bank 2, Outlet 17–24: 7 x C13 + 1 x C19
Environment Sensors
4 x RJ-11 Female (Black)
Door Sensor
1 x 4-pin Dry Contact
LAN
1 x RJ-45 Female (Silver) + LEDs (Orange/Green)
LEDs
Outlet Status
NA
24 (Orange)
16 (Orange)
PDU / Bank / Outlet
2-digit 7-segment (Orange)
PDU / Bank / Outlet
3 (Green)
Current / Volt / P.D. /
Sensor1–Sensor4 /
FW Upgrade
3-digit 7-segment (Orange)
Current / Volt / P.D. / IP /
Sensor1–Sensor4
7 (Green)
Door Open
1 (Red)
IP
1 (Green)
Power
1 (Blue)
Switches
LED Display Select
1 x Pushbutton
PDU / Bank / Outlet
Select
2 x Pushbutton
Reset
1 x Semi-recessed Pushbutton
Power
2 x Non-fuse Breaker
Nominal Input Power
100–240V~; 50–60Hz; 32A
Nominal Input/Output Voltage
200–240 VAC
Power Capacity
7.36kW
Nominal
Output Power
Per Port
IEC 320 C19
100–240V~; 50–60Hz; 15A (TUV), 16A (Max.)
IEC 320 C13
100–240V~; 50–60Hz; 10A
Total
100–240V~; 50–60Hz; 30A (TUV), 32A (Max.)
Environment
Operating Temperature
0–40
o
C
Storage Temperature
-20–60
o
C
Humidity
0–80% RH Non-condensing
Physical
Properties
Housing
Metal
Weight
6.5 kg
Dimensions (L x W x H)
177.50 x 6.60 x 4.40 cm
Summary of Contents for eco PDU PE series
Page 21: ...Chapter 1 Introduction 12 PE8121kJ 1 2 3 4 PE8121kJ 1 5 5 5 1 ...
Page 25: ...Chapter 1 Introduction 16 PE7328 1 2 3 4 1 PE7328 5 5 ...
Page 27: ...Chapter 1 Introduction 18 PE9330 1 2 6 3 4 1 6 PE9330 5 ...
Page 34: ...eco PDU PE Series User Manual 25 Installation Diagram 6 2 3 2 4 5 ...