ON/OFF TIME SETTING INSTRUCTIONS

FOR LOADS USING NORMALLY OPEN (NO) RELAY CONTACTS 

To set the ON DELAY time:

1. Set dial to the desired length of time that is required to elapse before the load (fan, light, etc.) is to be turned ON. The dial can be set to various positions 

within three different time ranges: 5-50 seconds, 1-50 minutes, and 1-3 hours. The dial can also be set to continuous ON and continuous OFF positions. 

2. The timer will begin timing the desired interval after the dial is set and the external trigger (by others) connected to START terminal is closed. 

3. The red OFF LED will once a second when the load circuit is OFF and is timing the delay. The green ON LED will be permanently ON when the load circuit 

is ON.

4. The timing interval can be restarted from an ON position by opening and reclosing the external trigger.

To set for CONTINOUS ON:

Set dial and align the pointer to the ON position (approximately 12:00 o’clock position). The timer ignores any external trigger signals in this mode. The 

green ON LED will be permanently ON when the timer is set for a continuous ON condition.

To set for CONTINOUS OFF:

Set dial to and align the pointer to the OFF position. The timer ignores any external trigger signals in this mode. The red OFF LED will be permanently ON when the timer is 

set for a continuous OFF condition.

FOR LOADS USING NORMALLY CLOSED (NC) RELAY CONTACT:

The normally closed relay contact is provided to enable a secondary load to be switched at opposite time intervals of the main load (the load controlled by the 

normally open contact.) When the load that is connected to the normally open relay contact is ON, the load connected to the normally closed contact is OFF. 

When the load that is connected to the normally open relay contact is OFF, the load that is connected to the normally closed contact is ON.

PROGRAMMING & OPERATING THE TIMER

OPERATING PARAMETERS

• 

The control relay will be energized continuously if the time interval dial is turned to ON. The control relay will be de-energized continuously if the time interval 

dial is turned to OFF.

• 

The control will repeat cycle within 1% of timing range.

• 

The control will automatically reset after a 1 second power interruption and remain OFF with the red OFF LED be permanently ON until the external contacts 

connected to the START terminal are closed.

• 

If the external trigger is removed from the timer, it will immediately reset to an “output disabled” condition, thus removing power from the load. It will then 

wait for the next timing cycle to commence with an external trigger closure.

• 

If the time interval dial is moved from one position to another during the active timing cycle, no change will result in the timing or output status for that cycle.

ONE YEAR LIMITED WARRANTY: If this product fails because of a manufacturing defect within one year after purchase, we will, at our option, either repair or replace it at no charge. 

Our warranty does not cover damage caused by accident, abuse or misuse. We assume no further liability with respect to the sale or use of this product. THIS WARRANTY IS IN LIEU 

OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE WARRANTY OF MERCHANTABILITY. We make no warranty with respect to the fitness of any goods for the 

users particular application. This warranty gives you specific legal rights, and you also may have other rights which vary from state to state. 

MLI-195(B)                             

NSI INDUSTRIES, LLC • 888.500.4598 • www.nsiindutries.com

Summary of Contents for TORK E500T

Page 1: ...FOR TECHNICAL SUPPORT SOUTIEN TECHNIQUE PARA COMUNICARSE CON EL SERVICIO TÉCNICO techsupport nsiindustries com 888 500 4598 ...

Page 2: ...E500T ON DELAY TIMER INSTRUCTIONS ...

Page 3: ...r to clean the enclosure INSTALLATION WIRING INSTRUCTIONS Note Wiring connections are made to a six position terminal block All terminals accept AWG 18 to AWG 12 wire 1 Turn off all power to the timer circuit at the distribution panel before beginning the installation 2 The E500T box contains knockouts on two sides Determine the most convenient way to mount the box to the conduit and remove the ap...

Page 4: ...contact is ON the load connected to the normally closed contact is OFF When the load that is connected to the normally open relay contact is OFF the load that is connected to the normally closed contact is ON PROGRAMMING OPERATING THE TIMER OPERATING PARAMETERS The control relay will be energized continuously if the time interval dial is turned to ON The control relay will be de energized continuo...

Page 5: ...G 12 1 Avant de commencer l installation coupez complètement l alimentation du circuit de la minuterie à partir du panneau de distribution 2 Des pastilles défonçables se trouvent des deux côtés du boîtier de la mi nuterie E500T Déterminez la manière la plus pratique d installer le boîtier sur le conduit puis retirez la pastille défonçable appropriée Pour fixer le boîtier à un emplacement précis ut...

Page 6: ...branchée sur le contact de relais normalement fermé est à OFF arrêt Lorsque la charge raccordée au contact de relais normalement ouvert est à OFF arrêt celle qui est branchée sur le contact de relais normalement fermé est à ON marche PROGRAMMATION ET FONCTIONNEMENT DE LA MINUTERIE PARAMÈTRES OPÉRATIONNELS Le relais de commande sera sous tension de manière continue si le cadran de sélection de l in...

Page 7: ...cte por completo la alimentación al circuito del temporizador en el panel de distribución antes de comenzar con la instalación 2 La caja del E500T contiene orificios en ambos lados Determine la forma más conveniente para montar la caja al conducto y retire el orificio apro piado Para asegurar la caja a una ubicación fija utilice al menos dos de los orificios de montaje ubicados en la parte posteri...

Page 8: ...secundaria en intervalos de tiempo opuestos de la carga principal la carga controlada por el contacto normalmente abierto Cuando se activa la carga conectada al contacto del relé normalmente abierto se desactiva la carga conectada al contacto normalmente cerrado Cuando se desactiva la carga conectada al contacto del relé normalmente abierto se activa la carga conectada al contacto normalmente cerr...

Reviews: