7.  Motor operation 

Ste

Content 

Confirm wiring for Input and Output signals. 

Confirm wiring for Input / Output signals work properly by Host equipment and application software 

MEGATORQUE MOTOR SETUP

 

Set Tuning mode and Load inertia moment ratio.

 

Set Tuning mode 

Gr.0_ID00 : Tuning mode (TUNMODE)

 to 01

AutoTun_JRAT-Fix

 
Set the ratio of Load moment inertia against Motor rotor inertia to 

Gr.1_ID14:Load inertia moment ratio 1 

(JRAT1)

 

  JRAT1 setting value = (Load moment inertia) / (Motor rotor inertia) × 100    [%] 

 

Execute Magnetic pole position estimation. 

Close 

Magnetic pole position estimation

 input after confirming 

Magnetic pole position estimation ready

 

output. Motor will start m/-18 degree reciprocal motion. 

 

Close Servo On. 

Close Servo On input signal. Confirm motor servo against external force, and 7 segment display on the front 
panel of model EGA driver shows character 

8

 

Input pulse command.

 

Input Pulse command to model EGA driver. 
 
In case of no motor motion, please check pulse command from host equipment to model EGA driver which can 
be confirmed by monitor function 

Monitor _ID13

Command pulse frequency (FMON1)

 
No number (

0

) appears on monitor if Model EGA driver does not receive position command pulse from host 

equipment. 

Please check wiring from host equipment to model EGA driver.

 

 

 

Note:

 

Apply slow motor speed pulse command to confirm motor speed and motor rotating direction with secured 
interlock signals such as Emergency stop and Over travel. 
 
Stop motor operation immediately in case of any abnormal motion. 
 
Shipping set of Tuning mode 

Gr.0_ID00 : Tuning mode (TUNMODE)

 is 

00

 as Auto-tuning for such as 

servo gain and is valid. 
 

 

 Display of the Digital operator 

NO 

Display 

Description 

Check points to get proper state 

 

Control power supply established. 
Control  power  supply  (r,  t)  is  established, 
and driver ready (RDY) is ON. 

 

Main circuit power supply established. 
Main  power  supply  (R,  S  and  T)  is 
established, 

but 

operation 

preparation 

completion signal is OFF. 

Confirm main AC voltage line 

connected to model EGA driver. 

 

Operation  preparation  completion  signal  is 
established. 
Main  power  supply  (R,  S  and  T)  is 
established, 

and 

operation 

preparation 

completion signal is ON. 

Confirm input signal polarity of Over 

travel and Emergency stop. 

Confirm magnet pole position 

estimation has completed properly. 

 

Servo is ON. 
Segment  repeats  on  and  off  individually  to 
display character 

8

Confirm Servo On input signal is closed 

properly. 

Summary of Contents for Megatorque Motor EGA

Page 1: ...MEGATORQUE MOTORTM SYSTEM Start up Guide Driver Model EGA NSK Ltd Document No C20195 02 ...

Page 2: ... nsk com 2 System configuration Noise filter Installed to protect power line from external noise 防ぐために取り付けます Citcuit Breaker Used to protect power line Turns off the power supply when overload runs MEGATORQUE MOTOR SETUP Enables parameter set up and monitoring through communication with a PC Host equipment Switches power On Off Please place safeguard circuit T S R Electromagnetic contactor Convert...

Page 3: ...a for load compared to the moment of inertial for rotor Remember to check for appropriate allowable moment load allowable axial load and allowable radial load for your specific applications of the motor Table Table fixing bolt MEGATORQUE MOTOR Mounting base Motor fixing bolt Flatness of mounting surface 0 02 mm or less Load The load is not directly applied to the motor rotor The motor is not direc...

Page 4: ...pole position estimation input 12 SG Common for pins 3 to 11 36 CONT2 Emergency stop function 17 Do not connect 37 CONT1 Servo ON function 18 Do not connect 50 CONT COM General input power supply 19 Do not connect 39 OUT1 In Position window 20 Do not connect 40 OUT2 Magnetic pole position estimation ready 21 Do not connect 41 OUT3 Operation setup completion 22 T COMP Torque compensation input 42 O...

Page 5: ...avel function CW over travel function Host equipment Driver model EGA Z phase pulse output B phase pulse output A phase pulse output 5 12 24 VDC VDC SG 50 CONT COM 37 CONT1 36 CONT2 35 CONT3 34 CONT4 33 CONT5 32 CONT6 13 CONT7 38 SG 15 CONT8 38 SG 26 F PC 27 F PC 47 SG 28 R PC 29 R PC 48 SG 49 OUT PWR 39 INP 40 CSETRDY 41 S RDY 42 CSETCMP 46 ALM 24 25 OUT COM 3 AO 4 AO 5 BO 6 BO 7 ZO 8 ZO 12 SG CN...

Page 6: ...y Stop Function EMR are normal close polarity input as shipping set To enable motor operation wire these input signals properly or change its polarity by parameter setting value 6 Operation sequence 0 msec Min Control source Main circuit power Magnetic Pole Position Estimation ready signal output Magnetic Pole Position Estimation input signal input Magnetic Pole Position Estimation end signal outp...

Page 7: ...MON1 No number 0 appears on monitor if Model EGA driver does not receive position command pulse from host equipment Please check wiring from host equipment to model EGA driver Note Apply slow motor speed pulse command to confirm motor speed and motor rotating direction with secured interlock signals such as Emergency stop and Over travel Stop motor operation immediately in case of any abnormal mot...

Page 8: ...atively large 5000 Although temporary setting value for JRAT1 may able to provide some degree of performance enter proper JRAT1 value for faster motor speed and better accuracy positioning operation To improve responsiveness of motor motion and positioning settling time increase Gr 0_ID00 Auto Tuning response ATRES setting value gradually Decrease Gr 0_ID00 Auto Tuning response ATRES setting value...

Page 9: ...iddle point between Z phase signal described in below Adjust home sensor turn off position around 32767 pulse by monitoring motor position using Monitor_ID80 Resolver sensor electric angle RESANG Home sensor turn off position Driver condition code at alarm 9 Implementing Magnetic pole position estimation Alarm code 44 Magnetic pole position estimation error Start homing Motor motion Home sensor Z ...

Page 10: ...fications 2 2 1 Specifications of driver 2 3 Specifications of converter 2 12 Motor installation 3 3 4 Set main circuit power input type as Single phase AC power 5 5 1 Motor and signal state at occurrence of alarm 5 12 Monitor Input Output signal state 5 16 Parameters for tuning 5 29 Servo Tuning functions and basic adjustment procedure 6 6 1 Set Load inertia moment 6 9 Manual tuning 6 13 Digital ...

Reviews: