83112-1 DIVIDER PLATE INSULATION 
REPLACEMENT KIT

  

 

This boiler must be serviced by a qualified heating technician. Failure to properly maintain or 
service this appliance may result in property damage, serious injuryto occupants or, death. 
 

 

The installation of this kit must be performed by a qualified boiler technician. Installing this kit 
without the proper qualifications and training is hazardous and may result in property damage or 

death. 

 

Applicable Boiler Models: 

 

Lx150-800 

 

M100, M100V 

 

T150-200 

 

Ti100-400 

 

Ts80 

 
Kit Contents: 

 

83112 – 3/8” Divider Plate Insulation 

o

 

83340 Stainless Steel Washer 

o

 

83339 M4 x 8 mm Screw 

(use with models T150, T150C, T200 & T200C; and non-ASME Lx150, M100, M100V, Ti100, Ti150, Ti150C, 
Ti200 & Ti200C) 
 

 

84742 – 5/8” Divider Plate Insulation 
(use with all other models) 

 

Replacement Instructions: 

1)

 

Initiate a post-purge cycle to clear any gas from the combustion chamber, 
and then turn gas and power supply off. 
 

2)

 

Lx300-800: 

To disconnect the metallic tubing between the blower and the 

high-vent pressure switch, loosen the compression fitting at the high-vent 
pressure switch with a ½” wrench.  At the blower end, support the brass 
fitting body with a ½” wrench to keep it from rotating while loosening the 
compression fitting nut with a 9/16” wrench.  Remove tubing assembly 
from blower. 

 
3)

 

Access the combustion chamber by removing the burner door assembly of 
the appliance. 
 

4)

 

Remove the insulation disc located in the back of the combustion chamber.  
When removing a broken Divider Plate, first soak it with water so as not to 
have any of the fibres in the air. Remove all particles of the old disk from 
the combustion chamber. 
 

Crystalline Silica

 – Ensure to read and understand the 

section  on  Refractory  Ceramic  Fibers  (RFC)  in  the 

installation and operation manual that came with the boiler. Failure to comply 
with handling instructions in the manual may result in serious injury or death. 

 

84742 

 5/8” Divider Plate Insulation

 

83112 

 3/8” Divider Plate Insulation

 

Reviews: